ZN63(VS1)-12S Indoor Vacuum Circuit Breaker (pole-fixed and sealed)
Picture
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)
  • ZN63(VS1)-12S Indoor Vacuum Circuit Breaker  (pole-fixed and sealed)

ZN63(VS1)-12S Indoor Vacuum Circuit Breaker (p...

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

● ZN63(VS1)-12P indoor AC MV vacuum circuit breaker is a three-phase AC 50HZ indoor switchgear with a rated voltage of 12KV. It can be used in industrial and mining enterprises, power plants and substations for the control and protection of electrical facilities, and is suitable for places with frequent operations.
● Standard: IEC 62271-100.

Selection

ZN63(VS1) - 12 P T 630 - 25 HT P210
Name Rated
voltage(KV)
Pole type Operating mechanism Rated    current(A) Rated short-circuit   breaking current(KA) Installation Phase  spacing
Indoor vacuum circuit breaker 12:12KV P:Solid
-sealing
type
T:
Spring type
630, 1250,
1600, 2000,
2500, 3150,
4000
20,
25,
31.5,
40
HT: Handcart
FT: Fixed type
P150,
P210,
P275

Note: ZN63(VS1)-12P adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the model backup;

Operating conditions

1. The ambient temperature is not higher than +40°C and not lower than -15°C (storage and transportation at -30°C are allowed);

2. The altitude is not higher than 1000m;

3.  Relative temperature: the daily average is not more than 95%, and the monthly average The value is not more than 90%, the daily average value of saturated vapor  pressure  is  not  more  than  2.2×10-’MPa,  and  the  monthly  average value  is  not  more  than 1.8×10MPa;

4. The seismic intensity does not exceed 8 degrees;

5. There is no fire, explosion hazard, serious pollution, Places subject to chemical corrosion and severe vibration.

Features

1. The arc extinguishing chamber and operating mechanism of the circuit breaker are arranged in a front-to-back configuration and connected as a whole through a transmission mechanism.

2. The hermetically sealed pole adopts epoxy resin insulation material to seal the vacuum arc extinguishing chamber and the main circuit conductive components as a whole.

3. The  vacuum  arc   extinguishing  chamber   utilizes  a   hermetically   sealed  pole,  enhancing  the   product’s  ability  to  withstand environmental pollution.

4. The operating mechanism adopts a spring-stored energy design, providing both electric and manual energy storage functions.

5.  It features an advanced and rational buffer device, ensuring no rebound during disconnection and reducing disconnection impact and vibration.

6.  It has advantages such as simple assembly, high insulation strength, high reliability, good product consistency, and maintenance- free operation.

7. The mechanical lifespan can reach up to 20,000 operations.

Technical data 

Technical datas are shown in Table 1

Item Unit Value
Rated voltage kV 12
Rated insulation level Rated lightning impulse withstand voltage (peak) 75
1min power frequency withstand voltage 42
Rated current A 630
1250
630, 1250, 1600,
2000, 2500, 3150
1250, 1600, 2000,
2500, 3150, 4000
Rated short circuit breaking current(KA) KA 20 25 31.5 40
Rated thermal stable current (effective value) KA 20 25 31.5 40
Rated dynamicstable current (peak value) 63 80 100
Rated short-circuit making current (peak value) 50 63 80 100
Rated short-circuit breaking current breaking times Times 80 50 30
Secondary circuit power frequency withstand current V 2000
Rated operating sequence / Opening -0.3s – closing and opening -
180s – closing and opening -180s – closing
and opening -180s – closing and opening (40kA)
Rated thermal stability time s 4
Rated single/back to back capacitor bank breaking current A 630/400 800/400
Mechanical life Times 20000 10000

The mechanical characteristic parameters are shown in Table 2

Item Unit Value
Contact distance mm 11+1
Contact travel 3.3±0.6
Average closing speed (6mm~contact closed) m/s 0.6±0.2
Average opening speed (contact separation -6mm) 1.2±0.2
Opening time (rated voltage) m/s 20~50
Closing time (rated voltage) 35~70
Contact closing bounce time m/s ≤2 ≤3(40kA)
Three phase opening asynchrony ≤2
Allowable cumulative thickness of wear for moving and stationary contacts mm 3
Main electrical circuit resistance μΩ ≤50(630A)                                      ≤45(1250A)
≤35(1600~2000A)                        ≤25(2500A and above)
Contact pressure of closing contacts N 2000±200(20kA)
3100±200(31.5kA)
2400±200(25kA)
4500±250(40kA)

Opening and closing coil parameters are shown in Table 3

Item Closing coil Opening coil Note
Rated operating voltage(V) AC110/220  DC110/220 AC110/220  DC110/220 The opening coilshall not open when it is less than 30% of the rated operating voltage
Coil power(W) 245 245
Normal operating voltage range 85% -110% rated voltage 65% -120% rated voltage

Energy storage motor parameters are shown in Table 4

Model Rated voltage Rated input power Normal operating voltage range Energy storage time at rated voltage
ZYJ55-1 DC110 70 85% -110% rated voltage ≤15
DC220

Overall and mounting dimensions(mm)

Handcart type outline size drawing (suitable for 800mm cabinet)

6.2

Rated current (A) 630 1250 1600
Rated short-circuit breaking current(KA) 20,25,31.5 25,31.5,40 31.5,40
Equipped static contact size (mm) Φ35 Φ49 Φ55

6.2

Rated current (A) 1600 2000 2500 3150 4000
Rated short-circuit breaking current(KA) 31.5,40 31.5,40 40
Equipped static contact size (mm) Φ79 Φ109

6.3

Rated current (A) 630 1250 1600
Rated short-circuit breaking current(KA) 20, 25, 31.5 25, 31.5, 40 31.5, 40

6.4

Rated current (A) 1600 2000 2500 3150 4000
Rated short-circuit breaking current(KA) 31.5,40 31.5,40 40
Write your message here and send it to us