Zinc Oxide Arrester

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Contact Us

Product Details

Zinc Oxide Arrester

The zine oxide arrester is the most advanced over-voltage protector in the world;Due to make the risistor disc of core componet mainly adopt zine oxide arrester.Compared with the conventional silicon carbide arrester, this presciption of theproduct improves gr-eatly the volt-Ampere characterisics of the

resistor disc andincreased through-current capability at over-voltage so as to dring a rad-icalchanges for the characteristics of the arresters.

Under the circumstance of normal operating voltage, the current through thearrester is just on microampere degree, When suff- ered from over-voltage, thearrester's excellent nonlinear characteristics will make the current through thearrester incrase to several thousand amperse, while the arrester will be

under thecirculating state and release over-voltage energy so as to protecting the powertransmission equipments against the demage caused by th over-voltage.

Operating conditions

1. The ambient air temperatures is no higher than +40℃,no lower than -40℃ ;

2. The altitude above sea level dose not exceed 1000-2000m(the plateau ares should be indicated when ordering);

3. AC systen frequency is 50Hz or 60Hz;

4. The power frequency voltage applied to the arrester for a long time does not exceed the continuous working voltage of the arrester; 5. Maximum wind speed does not exceed 35m/s;

6. The earthquake intensity does not exceed 7 degrees;

7. The filthy area should be given clear indication.

Features

The zinc oxide arrester is applied to protect the electrical equimpent in AC power system against the damage resulted from atmospheres over-voltage and operational over-voltage.

Technical performance

The technical performance of the product confirms to GB11032-2000, IEC60099-4,IEEE.C62.11 standard technical requirements.

 HYWS1 serise arrester

HYWS1 serise arrester

Technical data

Type System Rated
voltage
KV(rms)
Arrester Rated
voltage
KV(rms)
Continuous
Rated voltage
KV(rms)
DC1mA
voltage
(kv)
Lightning
Impulse residual
voltage
(kv)
Steep wave
Impulse residual
voltage
(kv)
2ms square
wave Impulse
current
withstand
(A)
HYWS -3.8/17 3 3.8 2.4 7.5 17 19.6 100
HYWS -7.6/30 6 7.6 4 15 30 34.5 100
HYWS -12.7/50 10 12.7 6.6 26 50 57.5 150
HYWS17/50 10 17 13.6 26.5 50 57.5 150
HYWZ-7.6/27 6 7.6 4 14.5 27 31 200
HYWZ-12.7/45 10 12.7 6.6 24 45 51.8 200
HYWZ-17/45 10 17 12.7 24 45 51.8 200
HYWZ-42/134 35 52 40.8 78 134 154 400
HY2.5WD-7.6/19 605 7.6 4.8 11.5 19 21.9 200, 400
HY2.5WD-12.7/31 10.5 12.7 6.6 19 31 35.7 200, 400
HY2.5WD-16.7/40 13.8 16.7 9 25 40 46 400
HY2.5WD-19/45 15.7 19 10 28.5 45 51.8 400
HY5WR-7.6/27 6 7.6 4.8 13.8 27 20.8 400
HY5WR-12.7/45 10 12.7 6.6 23 45 35 400
HY5WR-42/134 35 52 23.4 73 134 105 400

Application

Take HY5WS-17/50 as an example: H-Compound coat in organism ;Y-Metals oxide lightning arrester; 5-The mark calls to turn on electricity the electric current(KV);W-TheW mean to have no clefthe C means to establish the cleft; S-The S means to go together

with the electricity; Z electricity stands; D electrical engineering type; R electric capacity type 17-Avoiding the thunder sum settles the electric voltage(KV)50-

The mark calls to turn on electricity electric current bottom biggest press(KV).

HY5W、HY10W serise polymer Type lightining arrester

0

0

Technical data

5KA Gapless Arrester Electrical Character

Type Rated
voltage
(kV)
MCOV
(kV)
Residual voltage(kV) 2000μs square
wave impules
current
withstand
4/10μs high current
impules
Steep current impulse Switching
current
impulse
8/20μs
Lighting
current
impulse
HY5W-3 3 2.55 9.5 7.7 9 100 65
HY5W-6 6 5.1 19 15.4 18 100 65
HY5W-9 9 7.65 28.5 23.1 27 100 65
HY5W-12 12 10.2 38 30.8 36 100 65
HY5W-15 15 12.7 47.5 38.5 45 100 65
HY5W-18 18 15.3 57 46.2 54 100 65
HY5W-21 21 17 66.5 53.9 63 100 65
HY5W-24 24 19.2 76.5 61.6 72 100 65
HY5W-27 27 21.9 85.5 69.3 81 100 65
HY5W-30 30 24.4 95 76.5 90 100 65
HY5W-33 33 26.8 104.5 84.7 99 100 65
HY5W-36 36 29 114 91.4 108 100 65
HY5W-42 42 34.1 132.3 100.1 126 100 65

10KA Gapless Arrester Electrical Character

Type Rated
voltage
(kV)
MCOV
(kV)
Residual voltage(kV) 2000μs square
wave impules
current
withstand
4/10μs high current
impules
Steep current impulse Switching
current
impulse
8/20μs
Lighting
current
impulse
HY10W-3 3 2.55 9.5 7.7 9 1 100
HY10W-6 6 5.1 19 15.4 18 1 100
HY10W-9 9 7.65 28.5 23.1 27 1 100
HY10W-12 12 10.2 38 30.8 36 1 100
HY10W-15 15 12.7 47.5 38.5 45 1 100
HY10W-18 18 15.3 57 46.2 54 1 100
HY10W-21 21 17 66.5 53.9 63 1 100
HY10W-24 24 19.2 76.5 61.6 72 1 100
HY10W-27 27 21.9 85.5 69.3 81 1 100
HY10W-30 30 24.4 95 76.5 90 1 100
HY10W-33 33 26.8 104.5 84.7 99 1 100
HY10W-36 36 29 114 91.4 108 1 100
HY10W-42 42 34.1 133 100.1 126 1 100
HY10W-48 48 39 152 126 150 1 100
HY10W-54 54 43 171 139 162 1 100
HY10W-60 60 48 208 160 180 1 100
HY10W-66 66 52.8 230 172 198 1 100

Note: if is porcelain, without"H".

HY5W  Y5C  Y10W  Y10C serise arrester

0

1

Technical data

Type System
rated
voltage
(kv)
Arrester
rated
voltage
(kv)
Continuous
operation
voltage
(kv)
DC 1mA
voltage
(kv)
Lightning
impulse
residual
voltage
(kv)
Steep wave
impulse
residual
voltage
(kv)
2ms square wave
Impulse current
withstand(A)
Service
scope
Y1.5W-0.28/1.3 0.28 0.22 0.24 0.6 1.3 - 75 Low-voltage
Y1.5W-0.5/2.6 0.5 0.38 0.42 1.2 2.6 - 75
Y5WS-3.8/1.7 3.8 3 2 7.5 17 19.6 100 S
Power of
distribution
Y5WS-7.6/30 7.6 6 4 15 30 34.5 100
Y5WS-10/30 10 6 8 15 30 34.5 100
Y5WS-12.4/50 12.7 10 6.6 25 50 57.5 100
Y5WS-17/50 17 10 13.6 25 50 57.5 100
Y5WZ-3.8/13.5 3.8 3 2 7.2 13.5 14.5 200 Z
Transformer substation
Y5WZ-7.6/27 7.6 6 4 14.4 27 31 200
Y5WZ-10/27 10 6 8 14.4 27 31 200
Y5WZ-12.7/45 12.7 10 6.6 24 45 51.8 200
Y5WZ-17/45 17 10 13.6 24 45 51.8 200
Y5WZ-42/134 42 35 23.4 73 134 154 400
Y5WZ-51/134 51 35 40.8 73 134 154 400
Y5WZ-100/260 100 110 78 145 260 291 400, 600
Y10WE-100/260 100 100 78 145 260 291 600, 800
Y2.5WD-3.8/9.5 3.8 3 2 5.7 9.5 10.7 400 D
Circumvolve
motor
Y2.5WD-7.6/19 7.6 6 4 11.2 19 21.9 400
Y2.5WD-12.7/31 12.7 10 6.6 18.6 31 35.7 400
Y5WR-3.8/13.5 3.8 3 2 7.2 13.5 14.8 400 R
Capacitor
Y5WR-7.6/27 7.6 6 4 14.4 27 30.8 400
Y5WR-10/27 10 6 8 14.4 27 31 400
Y5WR-12.7/45 12.7 10 6.6 24 45 51 400
Y5WR-17/45 17 10 13.6 24 45 51 400
T5WR-51/134 51 35 40.5 73 134 154 400
Y1.5W-2.4/6 2.4 3.2* 1.9 3.4 6 - 5 D
Neuter point
of motor
Y1.5W-4.8/12 4.8 6.3* 3.8 6.8 12 - 10
Y1.5W-8/19 8 10.5 6.4 11.4 19 - 15.9
Y1.5W-60/144 60 110 48 85 144 - 135 Neuter point  of transfomer
Y1.5W-72/186 72 110 58 103 186 - 174

Note:

Pleasa add an "H"beforethspec . in the above table of composite organic housing zinc oxide arrester.

* is the rated voltage of motor.

 

 

 

 