YGH-12 environmental protection gas insulated ring main unit series is a complete set of powerdistribution devices for 12kV,three-phase AC 50Hz,single busbar and single busbar segmentedsystem.The product has the characteristics of simple structure,flexible operation,reliableinterlocking,convenient installation,etc.It can provide satisfactory technical solutions for variousapplication occasions and different users.The adoption of sensing technology and informationtechnology,coupled withtechnical performance and simple and flexible configuration schemes,canmeet the ever-changing needs of the market and are suitable for the requirements of gridintelligence.
Contact Us
YGH-12 environmental protection gas insulated ring main unit series is a complete set of power distribution devices for 12kV, three-phase AC 50Hz, single busbar and single busbar segmented system.The product has the characteristics of simple structure, flexible operation, reliable interlocking, convenient installation, etc. It can provide satisfactory technical solutions for various application occasions and different users.The adoption of sensing technology and information technology, coupled with technical performance and simple and flexible configuration schemes, can meet the ever-changing needs of the market and are suitable for the requirements of grid intelligence.
The YGH12 environmentally friendly gas-insulated ring main unit (RMU) series is suitable for industrial and civil cable ring networks and distribution network terminal projects. It is designed for receiving and distributing electrical energy. It is particularly well-suited for use in urban residential areas, small-scale substations, open/close stations, cable branching boxes, containerized substations, industrial and mining enterprises, shopping malls, airports, subways, wind power generation, sports stadiums, railways, tunnels, and other locations.
The YGH-12 series environmentally friendly gas-insulated ring main unit complies with relevant national standards and industry standards in the power sector. Its switches and main electrical components are integrated into modular units, and the interphase conductive components are enclosed in solid insulation. External wiring is done using shielded cable connectors, while the functional unit connections utilize shielded insulated busbars. These design features significantly enhance safety during operation.
The operating mechanism of the YGH-12 series employs a spring mechanism, providing a mechanical lifespan of over 10,000 operations. The operational data and equipment status can be remotely monitored, allowing for unmanned operation.
The YGH-12 series serves as a distribution device with certain performance capabilities.
●Environmental protection
The YGH-12 series environmentally friendly gas-insulated ring main unit is manufactured using non-toxic andharmless materials. It utilizes N2 (nitrogen) or dry air as the insulating medium, reducing greenhouse gas emissionsand achieving environmental objectives.During its usage, the YGH-12 series environmentally friendly gas-insulatedring main unit does not emit any toxic or harmful substances, ensuring its environmental friendliness. Additionally, theunit is designed to be recyclable and reusable, further enhancing its eco-friendliness.
●Wide range of application
The non-use of any toxic or harmful gases ensures the safety of the operating environment, whether it is in basements, tunnels, ships, or various indoor and outdoor environments. The interior of the high-pressure chamber can be filled with dry air or nitrogen, which is suitable for harsh conditions such as: high altitude, strong wind and sand, low temperature, severe cold, high environmental protection requirements, frequent operation sites, safe explosion-proof sites, high salt fog, and safe use under condensation conditions . Fully insulated and fully enclosed, it is suitable for the equipment to continue to operate after taking some cleaning and drying measures after a short period of water inflow.
●Maintenance-free
Apart from the operating mechanism, the YGH-12 series environmentally friendly gas-insulatedring main unit is in a fully sealed state. The high-voltage switch part is completely sealed,eliminating the need for cleaning and maintenance. This reduces operational and maintenancecosts. Switchgear has a high level of automation, and its online monitoring capabilities provide real-timenotifications of equipment operating conditions to users. This enhances the automation of thedistribution network, reduces manual operation costs, and lowers production costs for powercompanies.
●High security
The switchgear system features a comprehensive interlocking system and clearly visible three-phase isolationdistances to prevent accidents caused by misoperations. By eliminating the use of SF6 gas and strengthening theinterphase isolation structure, risks of expansion or explosion accidents due to interphase or multiple circuit shortcircuits are minimized. The switchgear incorporates a vacuum arc-extinguishing chamber with explosion-proof andenvironmentally friendly gas insulation, enhancing the protective performance of the switch. Additionally, theswitchgear utilizes sealed pole-pair designs for further protection.
●Easy to operate
The isolation switch and grounding switch are equipped with a single operating handle, eliminating the need foridentification and concerns about misoperations. When the circuit breaker is operation, the operating handles ofthe isolation switch and grounding switch are unable to be operated, simplifying the operation process andeliminating the need for complex technical training. This design ensures that the operation is extremelystraightforward and minimizes the chances of operational errors.
●The sealed pole-pair is formed using the epoxy resin APG (Automatic Pressure Gelation) process, providing excellent electrical and mechanical performance. It is a critical component and an essential part of the switch, serving both as an insulation element and a load-bearing component. It meets technical requirements for heat resistance, cold resistance, crack resistance, high mechanical strength, and good insulation strength.
●The switchgear features a single cabinet structure and utilizes universal insulated busbars and cableconnectors produced by professional cable accessory manufacturers. This allows for on-site assembly of theswitchgear and provides the flexibility to expand as needed, eliminating the inconvenience of transporting andinstalling multiple grouped cabinets. Additionally, if required, combination cabinets can also be providedaccording to specific requirements.
● Single cabinet structure, using general insulated busbars and cable connectors produced by professional cable accessory manufacturers. The switchgear can be combined on site, and can be expanded at will, to avoid the inconvenience of transportation and installation caused by multiple groups of combined cabinets. Of course, combined cabinets can also be provided upon request.
●Clearly visible real isolating break
●The whole series of products are designed in a unified manner, providing various cabinet types (circuit breaker, load switch, PT, busbar, busbar connection, etc.) required by users, and the shape and geometric dimensions are the same.
●The switch cabinet has intelligent interfaces and sensor installation positions, which can meet the requirements of the smart grid after the configuration of intelligent equipment.
●The main busbar adopts standard silicon rubber dry busbar.
● The disconnector adopts three-working position disconnector, which is installed on the busbar side.
●Replace SF6 load switch ring main unit
Circuit Breaker Switchgear | ||||
ltems | Unit | Values | ||
Rated voltage | kV | 12 | ||
Rated frequency | Hz | 50 | ||
Rated insulation level | 1min power frequency withstand voltage | To earth, phase-to-phas | kV | 42 |
Across isolating dist | 48 | |||
Lightning impulse withstand voltage (peak) | To earth, phase-to-pha | 75 | ||
Across isola | 85 | |||
Auxiliary/control circuit 1min power frequency withstand voltage (to earth) | 2 | |||
Rated current | A | 630 | ||
Rated short time withstand current (RMS) |
Main circuit/earth switch | kA | 25/4s | |
Grounding connection circuit | 21.7/4s | |||
Rated short time withstand current (peak) |
Main circuit/earth switch | 63 | ||
Grounding connection circuit | 54.5 | |||
Rated short circuit breaking current and numb | kA/ times | 25/30 | ||
Rated short circuit making current(peak) | kA | 63 | ||
Rated cable charging breaking current | A | 25 | ||
Rated operating sequence of circuit breaker | O-0.3s-CO -180s-CO |
|||
Mechanical life | Circuit breaker/disconnector | times | 10000/3000 | |
Protection degree | Sealed gas tank | IP67 | ||
Switchgear enclosure | IP4X | |||
Gas pressure | Gas rated fill level (20°C, gauge pressure) | Mpa | 0.02 | |
Gas min. fill level (20°C, gauge pressure) | 0 | |||
Sealing performance | Annual leakage rate | %/year | ≤0.05 |
Load Switch Switchgear | ||||
ltems | Unit | Values | ||
Rated voltage | kV | 12 | ||
Rated frequency | Hz | 50 | ||
Rated insulation level | 1min power frequency withstand voltage | To earth, phase-to-phas | kV | 42 |
Across isolating dist | 48 | |||
Lightning impulse withstand voltage (peak) | To earth, phase-to-pha | 75 | ||
Across isola | 85 | |||
Auxiliary/control circuit 1min power frequency withstand voltage (to earth) | 2 | |||
Rated current | A | 630 | ||
Rated short time withstand current (RMS) |
Main circuit/earth switch | kA | 25/4s | |
Grounding connection circuit | 21.7/4s | |||
Rated short time withstand current (peak) |
Main circuit/earth switch | 63 | ||
Grounding connection circuit | 54.5 | |||
Rated short circuit making current (peak) |
Load switch/earth switch | kA | 63 | |
Rated active load breaking curren | A | 630 | ||
Rated closed loop breaking curren | A | 630 | ||
5% rated active load breaking curren | A | 31.5 | ||
Rated cable charging breaking current | A | 10 | ||
Rated active load breaking number | A | 100 | ||
Grounding fault current breaking | A/times | 31.5/10 | ||
Circuit and cable charging current breaking under grounding fault condition |
A/times | 17.4/10 | ||
Mechanical life | Load switch/earth switch | times | 10000/3000 | |
Protection degree | Sealed gas tank | IP67 | ||
Switchgear enclosure | IP4X | |||
Gas pressure | Gas rated fill level (20°C, gauge pressure) | Mpa | 0.02 | |
Gas min. fill level (20°C, gauge pressure) | 0 | |||
Sealing performance | Annual leakage rate | %/year | ≤0.05 |
●GB/T11022 Common specifications for high-voltage alternating-current switchgear and controlgear
●GB/T3906 Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6 kV and up to and including 40.5 kV
●GB/T1985 High-voltage alternating-current disconnectors and earthing switches
●GB/T3804 High-voltage alternating current switches for rated voltage above 3.6 kV and less than 40.5 kV
●GB/T1984 High-voltage alternating-current circuit-breakers
●GB/T4208 Degrees of protection provide by enclosure (IP code)
●GB/T7354 High-voltage test techniques—Partial discharge measurements
●GB/T311.1 Insulation co-ordination – Part 1:Definitions, principles and rules
●Temperature: -25~+45℃;
●Maximum temperature: (24h average) +35℃;
●Average relative humidity (24h): ≤95%;
●Altitude: ≤1500m;
●Seismic ability: 8 degrees;
●Protection degree: IP67 for live body sealing, IP4X for switchgear enclosure;
●The surrounding air should not be obviously polluted by corrosive flammable gas,water vapor,etc.;
● Places without frequent violent vibration, and the severity design meets various requirements under severe conditions;
●Overall structure
1.Low voltage instrument room
2.Brow
3.Control room
4.Observation tube
5.Live display monitor
6.Cable room
7.Vacuum circuit breaker/load switch
8.Three-position isolation/grounding switch
9.Pressure relief device
10.Switching mechanism
11.Three-position mechanism
12.Five-protection interlock mechanism
13.Cable penetration wall sleeve
Standard Module – Vacuum Circuit Breaker Unit V
■Standard Configuration and Features:
◆630A busbar
◆Vacuum circuit breaker
◆Motorized operating mechanism for vacuum switch
◆Three-position isolation switch
◆Manual operating mechanism for three-position isolation switch
◆Position indicators for vacuum switch and three-position isolation switch
◆Cable connection sleeve
◆Capacitive voltage indicator with live display sleeve
◆Pressure gauge ◆Locking device ◆Cabinet
◆Ground busbar
◆Operating handle
◆Current transformer (for protection only)
◆Digital relay protection device
■Optional Configuration and Features:
◇Short circuit and ground fault indicators
◇Detachable connector (cable connector)
◇Lightning arrester
◇Incoming line live/ground locking device
◇Key mechanical interlocking device ◇Toroidal current transformer and meter
Standard Module – Load Switch Unit C
■Standard Configuration and Features:
◆630A busbar
◆Vacuum load switch
◆Manual operating mechanism for vacuum load switch
◆Three-position isolation switch
◆Manual operating mechanism for three-position isolation switch
◆Position indicators for load switch and three-position isolation switch
◆Cable connection sleeve
◆Capacitive voltage indicator with live display sleeve
◆Pressure gauge
◆Locking device
◆Cabinet
◆Ground busbar
◆Operating handle
■Optional Configuration and Features:
◇Electric operating mechanism for vacuum load switch
◇Short circuit and ground fault indicators
◇Detachable connector (cable connector)
◇Lightning arrester
◇Incoming line live/ground locking device
◇Key mechanical interlocking device
◇Toroidal current transformer and meter
Standard Module – Voltage Transformer Unit PT
■Standard Configuration and Features
◆2 current transformers
◆Fuses to protect PT
◆1 voltmeter with transfer switch
◆Capacitive voltage indicator with live display sleeve
◆Cabinet
◆Pressure gauge
■Optional Configuration and Features
◇3 voltage transformers
◇Lightning arrester
◇Three-position isolation switch
◇Manual operating mechanism for three-position isolation switch
Standard Module -Metering Module M
■Standard Configuration and Features
◆630A busbar
◆2 voltage transformers
◆2 current transformers
◆Fuses to protect PT
◆Capacitive voltage indicator with live display sleeve
◆Cabinet
■Optional Configuration and Features
◇1 transfer switch
◇1 voltmeter
◇1/2/3 ammeters
◇1 active energy meter
◇1 reactive energy meter
Note: The above typical combination reference scheme can be combined according to user needs.
Note: The above typical combination reference scheme can be combined according to user needs.
Note: The above typical combination reference scheme can be combined according to user needs.
Switch position conditions and interlocks
Power transmission: Hanging up (close) the lower door → open the circuit breaker (load switch) →open the earth switch → close the disconnector → close the circuit breaker (load switch) → power transmission completed. Power failure: Open the circuit breaker (load switch) → open the disconnector → close the eath switch → close the circuit breaker (load switch) → unloading (open) the lower door → power failure completed
Foundation and overall dimensions(mm)
This product should be installed on the pre-buriedchannel steel of the concrete platform, and theplatform should be enough to bear the total weightof the equipment.
Note:
The basic channel steel for secondary pouring is reversed, and the roughness is not more than 1mm The switchgear is fixed on the bas channel steel. The basic load of the welding switchgear is 500-700kg/unit.
Switchgear height 1550mm(without independent instrument room) lf need an independent instrument room, the switchgear height is 1950mm. Standard configuration cabinet depth is 850mm.