Product Overview
Product Details
Data Download
Related Products
Contact Us
General
YCW8HUseries air circuit breaker(hereinafter called ACB) is suitable for the circuit of AC 50Hz/60Hz with rated service voltage
800V, 1140V and rated service current between 630A and 4000A. It is mainly used to distribute electric energy and protect
circuits and electric equipment against over-load, under-voltage, short-circuit and single-phase earthing fault.
With intelligent and selective protection functions, the breaker can improve the reliability of power supply, and avoid unnecessary power failure.
The breaker is applicable for power stations, factories.
Standard: IEC 60947-2,IEC 60947-4-1
Type designation
YCW8 product name |
|
4000 Shell framecurrent |
HU Breaking Capacity |
/ / |
3 number of poles |
2500A Rated current |
D Installation type |
H Connection |
M controller type |
YCW8 |
|
2500(630~2500A) 4000(2000~4000A) |
HU : AC800 /1140V |
/ |
3:3P 4:4P |
630 800 1000 1250 1600 2000 2500 2900 3200 3600 3900 4000 |
D: Drawer style F: Fixed |
H: Horizontal wiring V: Vertical wiring |
M: LED display 3M: LCD display 3H: LCD display with communication |
Operating conditions
Item |
Description |
Ambient temperature |
-5℃~+40℃;the average value within 24h shall not exceed +35℃; L type and M type controller can be used under -40℃~+70℃ |
Altitude |
≤2000m |
Pollution grade |
3 |
Safety category |
Main circuit and undervoltage tripping coil is IV, other auxiliary and control circuit is III |
Installation position |
Vertically installed, inclination between the mounting plane and the vertical plane should not exceed ±5° |
Technical data
Item |
Description |
||
Shell current Inm (A) |
2500 |
4000 |
|
Rated working current In (A) |
630,800,1000 1250,1600,2000,2500 |
2000, 2500, 2900, 3200, 3600, 3900, 4000 |
|
Rated working voltage Ue (V) |
800/1140 |
||
Rated insulation voltage Ui (V) |
1140 |
||
Rated impulse withstand voltage Uimp (KV) |
12 |
||
Power frequency withstand voltage (V) for 1 minute |
3500 |
||
Number of poles |
3P,4P |
||
Rated limit short breaking capacity Icu (KA) |
800/1140V |
50 |
50 |
Rated operating short-circuit breaking capacity Ics (KA) |
800/1140V |
50 |
50 |
Rated short time withstand current for 1s ICW (KA) |
800/1140V |
50 |
50 |
Full power interruption time (without additional delay) (ms) |
12~18 |
||
Closing time (ms) |
≤60 |
||
Electrical lifespan |
2000 |
||
Mechanical life (maintenance free) |
10000 |
||
Mechanical life (with maintenance) |
20000 |
Basic and optional functions of the controller
Basic function |
Optional function |
Overload long delay, short circuit short delay, and short circuit instantaneous protection |
Signal contact output |
Functional testing |
MCR and over limit tripping |
Fault memory |
Load monitoring |
Thermal memory |
Voltage measurement |
Self diagnosis |
|
Current measurement |
|
Fault status indication and numerical display |
|
Earth fault protection |
Basic function |
Optional function |
Overload long delay, short circuit short delay, and short circuit instantaneous protection |
Current imbalance protection |
Functional testing |
Signal contact output |
Fault memory |
MCR and over limit tripping |
Thermal memory |
Load monitoring |
Self diagnosis |
power measurement |
Current measurement |
Power factor measurement |
Fault status indication and numerical display |
Electric energy measurement |
Communication function (3H) |
Regional interlocking |
Contact wear indicator (3H) |
Harmonic measurement |
Operation fault protection record (3H) |
Voltage protection |
Earth fault protection |
Voltage measurement |
Controller model |
M |
3M |
3H |
Overload long delay protection |
|
|
|
Short circuit short time delay protection |
|
|
|
Short circuit instantaneous protection |
|
|
|
Earth fault protection |
|
|
|
Current imbalance protection |
|
|
|
Functional testing |
|
|
|
Fault memory |
|
|
|
Signal contact output |
|
|
|
Thermal memory |
|
|
|
Self diagnosis |
|
|
|
MCU working instructions |
|
|
|
Current column display |
|
|
|
Current measurement |
|
|
|
MCR and over limit tripping |
|
|
|
Load monitoring |
|
|
|
Fault status indication and numerical display |
|
|
|
Voltage measurement |
|
|
|
Power factor measurement |
|
|
|
power measurement |
|
|
|
Electric energy measurement |
|
|
|
Communication function |
|
|
|
Contact wear indication |
|
|
|
Regional interlocking |
|
|
|
Harmonic measurement |
|
|
|
Voltage protection |
|
|
|
Record of operation times |
|
|
|
Shunt release
Shunt release can realize the remote control to break the circuit breaker.
● rated control power voltage Us(V) AC220V/230V, AC380V/400V, DC220V, DC110V
● work voltage (0.7~1.1)Us
● breaking time (50±10)ms
Forbid making the power for longtime to avoid the shunt release being damaged.
Closing electromagnet
After the motor finishes the energy storage, closing release can instantly close the circuit breaker.
● rated control power voltage Us(V) AC220V/230V, AC380V/400V, DC220V, DC110V
● work voltage (0.85~1.1)Us
● closing time (55±10)ms
Forbid making the power for longtime to avoid the closing release being damaged.
Under-voltage release
Without power supply, under-voltage release can't close. It is classified into instantaneous and time-delay type.
After closing the circuit breaker, under-voltage release can break the circuit breaker when the voltage drops to (70%~35%) Us. The circuit breaker can be closed again when power voltage recovers and exceeds 85%Us.
● rated control power voltage Us(V) AC220V/230V,AC380V/400V
● action voltage (0.35~0.7)Us
● reliable making voltage (0.85~1.1)Us
● reliable non-making voltage ≤0.35Us
● delay time: 0.5s,1s,1.5s,3s (YCW3-1600 , non-adjustable);
0.5s, 1s, 3s, 5s(YCW3-2000A, 3200A, 4000A, 6300A, adjustable).
Make sure there is power supply on the under-voltage release before making the circuit breaker.
Motor-driven energy-storage mechanism
With the function of motor-driven storing and auto restoring energy after closing the circuit breaker, the mechanism can ensure to close the circuit breaker instantly after breaking the circuit breaker.
● rated control power voltage Us(V) AC220V/230V,AC380V/400V,DC220V,DC110V
● work voltage (0.85~1.1)Us
● power loss 75W(1600A), 85W(2000A),110W(3200A,4000A),150W(6300A)
● energy-storage time <5s
Auxiliary contact
Standard model: 4NO/4NC
For YCW3-2500,4000: 4NO/4NC, 4NO+4NC, 2NO+6NC, 3NO+3NC.
Ith: AC380V/AC400V 0.75A, DC220V 0.15A, AC220V/AC230V 1.3A.
Key lock
The OFF button of the circuit breaker can be locked in the depressed position and the circuit breaker cannot be closed in that case; when the user selects the option, the factory provides locks and keys;
One breaker is provided with one lock and one key for the lock; two breakers are provided with two locks and one key for the locks; three breakers are provided with three same locks and two same keys for the locks.
Note: It is necessary to firstly press the OFF key and turn it anticlockwise before pulling out the key for the air circuit breaker with key lock equipped.
"Disconnected" position locking device for the draw-out type
For the “disconnected” position of the draw-out circuit breaker, a lock rod can be pulled out to lock the matter, and the breaker locked will be unable to be turned towards the TEST or CONNECTION position.
Padlocks have to be provided by users themselves.
Three position locking device for the draw-out
It is the locking device for three positions(disconnected, test, connection) of drawout type.
Three positions of circuit breaker is indicated by the indicator, the driving and the reversing handle which is locked in the exact position, and the lock can be released by the reset button.
Door-case
Installed on the door of the distribution cubicle, for sealing the distribution cubicle and making the protection class to IP40(fixed type and draw-out type).
Phases barrier (optional)
Installed between the bus-bars to increase the creepage distance.
Controller accessories
External N-pole transformer
In 3P+N system, it is used to measure N-pole current and fitted on the bus-bar by user.
Leakage current transformer
1. If the grounding protection is the leakage type, then a rectangular transformer will be needed.