This soft starter is an advanced digital soft start solution suitable for motors with power ranging from 0.37kW to 115kW. Provides a complete set of comprehensive motor and system protection functions, ensuring reliable performance even in the harshest installation environments.
Contact Us
Company code | / | Current | Voltage |
YC | QR8s | 30 | AC380V |
Company code | Model | 30KW | AC380V |
Optional soft start curve
● Voltage ramp start
● Current Limit Start
Optional soft start curve
● Free parking
● Timed soft parking
Expandedinput and output options
● Remote controlinput
● Relay output
● RS485 communication output
Models that meet connectivity requirements
● 0.37-115KW(rated)
● 220VAC-380VAC
● Star shaped connection or inner triangle connection
Customizable protection
● Input phase loss
● Output phaseloss
● Running overload
● Starting overcurrent
● Running overcurrent
● Underload
Easy to read display with comprehensive feedback
● Removable operation panel
● Built-in Chinese + English display
Terminal type | Terminal No. | Terminal name | Instruction | |
Main circuit | R,S,T | Power input | Soft start three-phase AC powerinput | |
U,V,W | Soft Start Output | Connect three-phase asynchronous motor | ||
Controlloop | Communication | A | RS485+ | For ModBusRTU communication |
B | RS485- | |||
Digital input | 12V | Public | 12/24Vcommon | |
IN1 | start | Short connection with common terminal (12/24V) Startable soft start |
||
IN2 | Stop | Disconnect from the common terminal (12/24V)to stop the start soft start |
||
IN3 | ExternalFault | Short-circuit with the common terminal(12/24V), soft start and shutdown |
||
Soft start power supply |
A1 | AC220V | 220V | |
A2 | ||||
Programming Relay 1 |
TA | Programming relay com-mon | Programmable output,available from Choose from the following functions: 0.No action 1.Power-on action 2.Soft start action 3.Bypass action 4.Soft stop action 5.Runtime actions 6.Standby action 7.Failure action |
|
TB | Programming relay normal-ly closed | |||
TC | Programming relay normal-ly open | |||
Programming Relay 218.5- 115kw(Config- uration) |
TA2 | Programming relay normal-ly open | ||
TC2 |