YCQR7 Soft Starter
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCQR7 Soft Starter
Picture
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter
  • YCQR7 Soft Starter

YCQR7 Soft Starter

General

Read the ZR 900 installation instructions carefully before use. If you do not read the relevant instructions carefully, you will violate the relevant safety regulations, which may affect the

normal use of the soft starter. To install the ZR900, please prepare the following tools : small word screwdriver, wire cutter, wrench, etc.

Contact Us

Product Details

Technical data

project name

performance index

scope of application

3 phase rat cage asynchronous motor

power bracket

5.5-450kW

input voltage

380V ± 15%

supply frequency

50/60HZ ± 5%

overload capacity

400%60sec,120% continuous

Adjustable current multiple

From 1 to 5 times each time

Soft up time

1-90 Seconds

Module working mode

over a long period of time

cooling-down method

forced air cooling

 

Secondary interace terminal

on-off input

3 Road

relay output

1 (programmable) or 3 (programmable)

4-20MA

Route (extension is optional)

RS485

1-way (extended as optional)

Protect

Short circuit speed break, overcurrent, overheat protection, reverse time

overload, voltage phase deficiency, imbalance, lnsient stop, undervoltage,

overvoltage, underload, starting failure, phase sequence error.

Host overload protection

Overload and reverse time limit, level 1 -5 is optional

Host current imbalance protection

Unbalanced trip standard: 5- 100% any two-phase unbalanced trip delay: 1-60 seconds can be set

Host short circuit protection

Quick break time . 0.18, can be set

Bus function

Interface : RS485 protocol · ModbusRTU

human-computer interface

4 Line COG Screen

Language

Chinese, English

Technical data

Order number

Name

Set the scope

Windows default

Explain

Soft-up parameters

A1

Start way

0~3

3

0: aging 1: voltage ramp

2: constant current3:current ramp

A2

Starting voltage

0~100%

45%

0,1,2 The starting mode is effective

A3

Initial current

0~2.5 Times

2.0 Times

Method 3 valid

A4

Flow limit multiple

1.8~6.0 Times

3.5 Times

Method 1,2,3 valid

A5

Sudden jump peak

0~100

90%

 

A6

The jump cycle

0~2.0S

0.4S

 

A7

Start delay

0~240.0S

0.0S

Delayed start time

A8

Soft up time

0~90.0S

20.0S

All starting modes are valid

A9

Soft stop time

0~60S

0S

Set to 0 no soft stop function, non-0 valid

A10

Joint control delay

0~240.0S

0.0S

Start the delay relay output, use with programmable relay

 

A11

mode of operation

 

0~6

 

3

0: Full open 1: keyboard 2: external control

3: keyboard + external control 4: Communication 5:Communication

+ keyboard

6:communication + external control

A12

Rated current

0~Current limit

100A

Set according to the rated current on the motor nameplate

A13

Upper limitcurrent

0~200%

120%

The relay is set to feed effectively

A14

Lower limit current

0~120%

90%

The relay is set to feed effectively

A15

actuation time

0~10.0S

1.0S

The relay is set to feed effectively

A16

Soft startplus time

0~60.0S

0

"Soft start time" does not complete the start, automatic extra time

A17

Soft strength

2.0 Times

0

"Soft start time" does not complete the start, automatic extra time

Protection parameters

A18

Short circuit multiple

0~12.0 Times

5.5 Times

Set greater than (current limit multiple + soft starting force + 0.5), the whole process is effective

A19

Speed break time

0~2.00S

0.20S

Short circuit block (break) time

A20

Overflow multiple

0~8.0

1.2

Bypass effective

A21

Overflow time

0~60.0S

10.0S

If the overflow exceeds this value, block the silicon

A22

Overheat time

0~60.0S

10.0S

When oyerheating exceeds this value, blocking the SCR,the whole process is effective

A23

Overload curve

1~6

1

Motor reverse time limit protection, reverse time limit curve

number, the larger the value, the longer the time, bypass (full

pressure) after the effective

A24

Lack of phase time

0~60.0S

10.0S

If the voltage phase deficiency exceeds this value,the SCR is blocked, and the whole process is effective

A25

Current imbalance

0~100%

30%

Current imbalance ratio, soft rise, bypass, soft stop effective

A26

Imbalance time

0~60.0S

5.0S

If the accumulated time of imbalance exceeds this value, block the silicon controller

A27

Underpress ure lower limit

0~100%

70%

Full effective

A28

Overpressure time

0~60.0S

2.0S

If the accumulated time of underpressure exceeds this value, the thyristor is blocked

A29

Overpressure upper limit

0~150%

120%

Full effective

A30

Overpressure time

0~60.0S

2.0S

If the cumulative time of overpressure exceeds this value,the thyristors is blocked

A31

Under-load current

0~100%

50%

Lower undercurrent, bypass and full pressure effective

A32

Adue time

0~30.0s

2.0s

If the cumulative time exceeds this value, the thyristor is blocked

Order number

Name

Set the scope

Windows default

Explain

Protection switch

A33

Short-circuiting switch

Close, open

Open

Output short-circuit protection is enabled or prohibited

A34

Overflow switch

Close, open

Open

Overcurrent protection enables or forbids

A35

Overheat awitch

Close, open

Open

Overheat protection enables or prohibited

A36

overload cut-out

Close, open

Open

Motor overload protection is enabled or prohibited

A37

Lack of phases witch

Close, open

Open

Input voltage phase absence protection enabled or prohibition

A38

Imbalance switch

Close, open

Open

Current imbalance (output phase deficiency) protection enabled or prohibition

A39

Instantaneo us stop switch

Close, open

Open

External instantaneous stop fault protection enabled or prohibited, enabling can be set to self-recovery

A40

Undervoltag e switch

Close, open

Open

Input voltage protection enabled or prohibited

A41

Overvoltage switch

Close, open

Open

Input voltage overvoltage protection enable or prohibited

A42

Starting failure

Close, open

Open

Motor is not enabled or prohibited by full speed protection during

bypass (or full pressure)

A43

Underload switch

Close, open

Open

Underload protection is enabled or prohibited

A44

Phase sequence switch

Close, open

Open

Phase order error protection enables or prohibition

Communication parameters : not considered when not used

A45

principal and subordinate

0,1,2

0

0:Close 1:Host 2:slave

A46

Stop number

0~32

1

 

A47

Digit capacity

0~12

8

Usually set to 8

A48

Stop bit

0~2

0

Usually set to 1

A49

Even-odd check

0~2

1

Usually set to 0

A50

Baud rate

0~96

8

Actual baud rate-baud rate*1200

A51

Current range

0~6000

1000

4 mA corresponds to 0 and 20 macorresponds to range values

Control

A52

Customer privilege

 

 

Password 10, go to the customer privilege menu

A53

Manufacturer setting

 

 

Password 111,enter the manufacturer setting menu

Write your message here and send it to us