General
The YCQR7-G soft starter control cabinet is used in situations where a motor is running.The control cabinet contains a soft starter primarily used for the smooth start of the motor,avoiding the impact and pressure during startup. It is typically employed in scenarios with large motors or where frequent starting and stopping is required, extending the motor’s lifespan and enhancing system stability. Soft starter cabinets are widely used in industrial sectors, energy fields, mining, and other heavy-duty equipment applications.

Contact Us

Product Details

General

The YCQR7-G soft starter control cabinet is used in situations where a motor is running.The control cabinet contains a soft starter primarily used for the smooth start of the motor,avoiding the impact and pressure during startup. It is typically employed in scenarios with large motors or where frequent starting and stopping is required, extending the motor’s lifespan and enhancing system stability. Soft starter cabinets are widely used in industrial sectors, energy fields, mining, and other heavy-duty equipment applications.

Operating conditions

1. Incoming line power supply: AC 380V ± 5% 50/60 Hz
2. Power supply is applicable: mouse cage three-phase asynchronous motor
3. Cooling mode: forced air cooling
4. App licable temperature: -10°C ~ ± 40°C ,1°C,2%, + 50°C
5. App licable humidity: 90% without frost
6. Place of use: No corrosive gas without conductive dust indoor is well ventilated
7. Elevation vibration: The altitude is below 3000 meters, and the vibration power device is below 0.5G.

Type designation

Naming method of the soft start cabinet

Technical data

Project name performance index
Scope of application 3 phase rat cage asynchronous motor
Power bracket 5.5-450kW
Input voltage 380V±15%
Supply frequency 50/60HZ±5%
Overload capacity 400%60sec,120%continuous
Adjustable current multiple From 1 to 5 times each time
Soft uptime 1-90 Seconds
Module working mode over a long period of time
Cooling-down method forced air cooling
Secondary interace terminal On-off input 3 Road
Relay output 1(programmable)or 3(programmable)
4-20MA Route (extension is optional)
RS485 1-way (extendedas optional)
Protect   Short circuit speed break,overcurrent,overheat protection,reverse time
overload,voltage phase deficiency,imbalance,Insient stop,undervoltage,
overvoltage,underload,starting failure,phase sequence error.
Host overload protection Overload and reverse time limit,level 1-5 is optional
Host current imbalance protection Unbalanced trip standard:5-100%any two-phase
unbalanced trip delay:1-60 seconds can be set
Host short circuitprotection Quickbreak time.0.18,can be set
Bus function Interface:RS485 protocol ·ModbusRTU
Human-computer interface 4 Line COG Screen
Language Chinese,English

Wiring diagram

Soft start control cabinet topology

Overall and mounting dimensions(mm)

Soft start control cabinet size
Specifications and models Overall dimensions(mm)
D W1 H1 D
YCQR7-G 5.5KW-30KW 315  810  320 
37KW-45KW 350  1000  400 
55KW-115KW 400  1160  400 