YCQ9HB ATS appliances are suitable for AC 50Hz, rated working voltage 400V and below,rated current 10A to 63A dual power supply system, the power supply system of the two power sources: common power supply (N) and standby power supply (R) at the same time detection, when the power supply occurs undervoltage, phase failure power supply failure that is, automatic switching from the abnormal power supply to the normal power supply (can also be manually switched), to enhance the continuity and reliability of the power supply system in the use of the premises. This improves the continuity, safety and reliability of the power supply system at the place of use. 
Switching appliances are widely used in power systems, hospitals, postal and telecommuni cation, fire fighting, hotels, banks, airports, wharves, residential neighborhoods, TV stations, military facilities, shopping malls and other important places where the continuity of power supply is required.
Standards: IEC 60947-6-1.

Contact Us

Product Details

General

YCQ9HB ATS appliances are suitable for AC 50Hz, rated working voltage 400V and below,rated current 10A to 63A dual power supply system, the power supply system of the two power sources: common power supply (N) and standby power supply (R) at the same time detection, when the power supply occurs undervoltage, phase failure power supply failure that is, automatic switching from the abnormal power supply to the normal power supply (can also be manually switched), to enhance the continuity and reliability of the power supply system in the use of the premises. This improves the continuity, safety and reliability of the power supply system at the place of use. 
Switching appliances are widely used in power systems, hospitals, postal and telecommuni cation, fire fighting, hotels, banks, airports, wharves, residential neighborhoods, TV stations, military facilities, shopping malls and other important places where the continuity of power supply is required.
Standards: IEC 60947-6-1.

Operating conditions

1. The ambient air temperature is -5 °C ~ +40 °C, and the average temperature within 24h does not exceed 35 °C.
2. The altitude of the installation site does not exceed 2000m above sea level.
3. The relative humidity of the air at the installation site should not exceed 50% at an ambient temperature of +40°C. Higher relative humidity is possible at lower temperatures. For example, in the wettest month with an average minimum temperature of +20°C, the monthly average maximum relative humidity for that month can be up to 90%. Appropriate measures should be taken to prevent condensation due to temperature changes
4. The pollution level is 3. There is no danger of explosion in the surrounding air, and there are no gases or conductive dust that could corrode metals and destroy insulation.
5. The installation category is III.
6. The two power lines are connected to the upper end of the switching appliance and the load line is connected to the lower end, and must not be reversed.
7. The installation site should be free from significant vibration and shock.

Type designation

Company
Code
Product
cod
Design
number
Frame
current
Number of
poles
Control
mode
Circuit Breaker
Disconnect Type
Rated
Current
Function codes
YC Q 9HB 63
CNC ATS CB class 63A 2-2 poles;
3-3 poles;
4-4 poles
R-Auto transfer and auto retransfer,
S-Auto transfer and non-auto retransfer,
I- Mutual backup
C-C type; D-D
type
10A, 16A,
20A, 25A,
32A, 40A,
50A, 63A
F-grid to generation;
T-communication

 

Technical data

Technical data YCQ9HB-63
Rated working current le 10A,16A,20A,25A,32A,40A,63A
Rated working voltage Ue AC 230V/50Hz(2P),AC 400V/50Hz(3P,4P)
Rated insulation voltage Ui 500V
Rated impulse withstand voltage Uimp 4kV
Rated short-circuit making capacity 9.18kA
Rated making and breaking capacity 6kA
Mechanical life 10,000 times
Electrical life 3000 times
Usage category AC-33iB
Electrical grade CB grade
Pole 2P,3P,4P
Delay time 0~30s adjustable
Electromagnetic compatibility environmen Environment B
Pollution degree 3
protection class IP30
Installation Vertical Fixed Installation
operating method Automatic/Manual
switch position Common position(I),Standby position(Ⅱ),Disconnect position (0)
Rated control power AC 230V/50Hz
Power supply voltage Undervoltage switching:165V±10%
Control Loss of voltage/phase out,undervoltage,overvoltage switching

Controller Functions

Control function
Auto/Manual Conversion Mode
dichotomous
Grid -Power Grid
Grid --generators
self-referral
abandon oneselfand not return
serve as a backup
Monitor common power supplies and failover ■Phase failure/loss of voltage,undervoltage,overvoltage faults
Monitor backup power and failover ■Phase failure/loss of voltage,undervoltage,overvoltage faults
Fire control input(passive)
Fire Feedback Output
Adjustable delay time
conversion delay Os-30s adjustable
Return delay Os-30s adjustable
Common and standby closing indication
Common and standby power indication
malfunction alarm
overvoltage conversion
Undervoltage conversion
Loss of Pressure Conversion
Out-of-phase conversion
communication function
Display Module light-emitting diode

 

Note: " ■ " means this function is available; " □ " means this function is optional; " △ "means Customers require factory adjustments.

 

 

Product Structure Schematic

Automatic Transfer Switch ATS Product Structure Schematic
1-Mounting hole;                5-Operating handle;                                 9-Handle padlock;
2-Product model;               6-Wiring terminal;                                   10-Fuse tube;
3-Company logo;                7-Changeover position indication;        11-Secondary terminal block
4-Controller;                       8-Grounding screw;
 

Controller Panel and Description

Automatic Transfer Switch ATS Controller Panel and Description
1- Common power indicator;          5-Normal to backup conversion delay setting;
2- Common closing indicator;        6-Backup to normal return delay setting;
3- Standby power indicator;            7-Auto/Manual switching gear.
4- Standby closing indicator;
 

Description of Controller Indicator Messages

Product status
Common power supply normal Ever Bright      
Common power closing   Ever Bright    
Backup power supply normal     Ever Bright  
Standby power closed       Ever Bright
Commonly used circuit breaker release Adorable Adorable    
Spare circuit breaker release     Adorable Adorable
Standby conversion delay       Adorable
Standby constant return delay   Adorable    
Product Conversion Failure Adorable   Adorable  
Fire switch   Adorable   Adorable

Controller secondary wiring terminal wiring instructions

Automatic Transfer Switch ATS Controller secondary wiring terminal wiring instructions
  • 101#, 102# commonly used power supply external indication signal output (AC220V/0.5A active), 3P products commonly used zero line connected to the 101# terminal ;
  • 103#, 104# common closing external indication signal output (AC220V/0.5A active) ;
  • 201#, 202# standby power external indication signal output (AC220V/0.5A active), 3P products standby zero line connected to 201# terminal ;
  • 203#, 204# common closing external indication signal output (AC220V/0.5A active) ;
  • 301#, 302#, 303# for generator start control signal passive output terminal, 301# for the public terminal, 302# for the normally closed terminal; 303# for the normally open terminal, common power supply is normal when 303# and 301# closed, 302# and 301# disconnected ; common power supply is abnormal when 302# and 301# closed, 303# and 301# disconnected ;
  • 401 #, 402 # for the fire linkage signal passive input, the port can only be connected to a set of external passive normally open contacts (if the fire signal is an active signal, must be transferred through a small relay relay normally open contacts into the port) when the external contact closure controller immediately after control
  • 403# and 404# are passive output terminals for fire fighting feedback signals. Under normal condition, the ports are normally open, and 403# and 404# are closed when there is a fire fighting signal input to the controller to make the switch switch switch to the breaking position ;
  • 501#, 502#, 503# are communication function consoles.

Description of the handle padlock function

Line maintenance and fault repair, first switch the switching appliances automatic / manual switching gear to manual, and then switch the switching appliances to the double points position ; pull the handle padlock and lock, can prevent accidents, the diameter of the lock hole is Ø5.5.
Automatic Transfer Switch ATS Description of the handle padlock function