Product Overview
Product Details
Data Download
Related Products
Contact Us
YCQ9 | 63 | 3 | A | 16A | FFD |
Model | Shell frame | Number of poles | Controller type | Rated current | Function |
Automatic transfer switch(PC cass) |
63(16~63A) | 2:2P 3:3P 4:4P |
A: Economy |
16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 200A 225A 250A 315A 350A 400A 450A 500A 630A |
|
125(50~125A) | B: Standard |
/:Fire control linkageFF:Fire feedbackD:GeneratorFFD:Fire feedback, Generator |
|||
250(125~250A) | |||||
630(250~630A) |
Model | YCQ9-63 | YCQ9-125 | YCQ9-250 | YCQ9-630 |
Function | Isolation, switch | |||
Structure | Integrated | |||
Electric equipment level | PC class | |||
Utilization category | AC-33B | |||
Number of poles | 2P、 3P、4P |
Rated insulation voltage Ui(V) | AC800 | AC1000 | |||
Rated operating voltage Ue (V) | AC400(2P product AC230) | AC415 | |||
Rated current Ie(A) | 16,20,25,32,40,50,63 | 50,63,80,100,125 | 125,160,200,225,250 | 250,315,350,400,450,000,000 | |
Rated operating frequency (Hz) | 50 | ||||
Rated impulse withstand voltage Uimp (kV) | 8 | 12 | |||
Rated impulse withstand current Icw(kA) | 5/30ms | 10/30ms | 25/1ms | ||
Rated short-circuit making capacity Icm(kA) |
8 | 17 | 52.5 | ||
Contact transfer time(s) | 0.6±20% | ||||
Operating transfer time(s) | 1.3±10% | ||||
Return time(s) | 1.3±10% | ||||
Power outage time(s) | 0.6±20% | ||||
Operation method | Auto/Manual | ||||
Switch position | Normal(I)、Power outage(O)、Standby(II) | ||||
Mechanical endurance (times) | 8000(*) | 4000( *) | |||
Electrical endurance (times) | 2000(*) | 1000(*) | |||
Applicable environmental conditions and installation | |||||
Working temperature(℃) | -5~+40 | ||||
Altitude(m) | ≤2000 | ||||
Atmospheric conditions |
The relative humidity of the atmosphere shall not exceed 50% at the highest ambient temperature of +40 ℃. At lower temperatures, there can be higher relative humidity, such as reaching 90% at+20 ℃ . Special measures should betaken for occasional condensation caused by temperature changes; |
||||
Pollution degree | 3 | ||||
Installation environment | Places without obvious vibration and impact | ||||
EMC environment | Environment B | ||||
Protection degree | IP20 | ||||
Power supply voltage deviation range(V) | 160±10% | ||||
Normal working voltage range | 85%Ue~110%Ue | ||||
Installation | Vertical fixed installation | ||||
Wiring method | Screw wiring | ||||
Connection | Front connection | ||||
Maximum number of conductors allowed to be clamped in | 1 | 2 | |||
Maximum screw torque | 2.5 | 6 | 10 | 22 |
Parameters of controller
Type | Type A | Type B |
Power supply and opening/closing indication | ■ | ■ |
Automatically transfer and restore operation | ■ | ■ |
Grid-grid | ■ | ■ |
Grid-generator(start/stop) | - | □ |
Three-phase monitoring commonly used to detect phase loss in power supply | ■ | ■ |
Three-phase monitoring commonly used to detect power loss in power supply | ■ | ■ |
Single-phase monitoring commonly used to detect phase loss in power supply | ■ | ■ |
Single-phase monitoring commonly used to detect power loss in power supply | ■ | ■ |
Handle manual operation | ■ | ■ |
External wiring terminal of indicator light | ■ | ■ |
Fire control linkage(24VDC) | - | □ |
Fire feedback | - | □ |
Specifications | A | B | H | A1 | B1 | A2 | A3 | A4 | H1 | H2 | H3 | H4 | C | C1 | D | φX | ||||
2P | 3P | 4P | 2P | 3P | 4P | |||||||||||||||
63 | 171 | 193 | 215 | 138 | 68 | 44 | 66 | 88 | 106 | 136 | 22 | 13 | 152 | 52 | 24 | 43 | 2 | 13 | 5.2 | 6 |
125 | 229 | 259 | 289 | 136 | 102 | 214 | 244 | 274 | 100 | 162 | 30 | 15 | 240 | 77 | 35 | 62 | 4 | 21 | 7 | 6 |
250 | 302 | 347 | 393 | 170 | 128 | 283 | 328 | 374 | 125 | 207 | 45.5 | 25 | 257 | 96 | 44 | 79 | 4 | 22 | 9 | 8 |
630 | 460 | 528 | 596 | 255 | 192 | 433 | 501 | 569 | 188 | 325 | 68 | 49 | 367 | 144 | 65 | 118 | 6 | 40 | 13 | 120 |