Product Overview
Product Details
Data Download
Related Products
Type | The adjustable type | Frame Inm | Breaking capacity Icu/Ics(kA) |
YCM8 | RT | 160 | H |
Moulded-case circuit breaker(MCCB) | RT:Overload+short circuit | 160, 250, 400, 630, 800 | S H |
T/A:Overload | Note: | 160 25/18 35/25 | |
160 is the upgraded 100 frame, | 225 25/18 35/25 | ||
225 is the upgraded 250 frame, | 400 35/25 50/35 | ||
630 is the upgraded 400 frame | 630 35/25 50/35 | ||
800 - 50/35 |
Operation | Poles | Tripping mode and inner accessory | Rated Current (A) |
Z | 3 | 300 | 160 |
Dc1, DC2, DC3 | 3: three poles | The first digit represents release type | 125: 20-25, 25-32, 32-40, 40-50, 50-63,63-80, 80-100, 100-125, 125-160 |
P: electric operation | 4: four poles | 2: has instantaneous release only | 250: 100-125, 125-160, 160-200, 200-250 |
Z : rotary handle | 3: complex release | 400: 200-250, 250-320, 320-400 | |
W: direct operation | Note: | 630: 400-500, 500-630 | |
① Electric operation DC3 | Later two digits are the code of accessories (see accessory table) | 800: 400-500, 500-630, 630-800,1250 |
Application | Option for 4P MCCB | Accessory voltage | ||
2 | A | Q1 | ||
1: power distribution | A: N-pole without protection, cannot close or open | Under Voltage Release | Shunt Release | Auxiliary Alarm |
2: motor protection | B: N-pole without protection, can close and open | Q1: AC220V | F1: AC220V | J1: AC125V |
C: N-pole with protection, can close and open | Q2: AC240V | F2: AC380V | J2: AC250V | |
D: N-pole with protection, cannot close or open | Q3: AC380V | F3: DC110V | J3: DC125V | |
Q4: AC415V | F4: DC24V | J4: DC24V |
Motor-driven operation voltage | Connection | With the connection plate or not |
D1 | Q | 2 |
DC3 | Q: Front-board | 1: Not |
Electric Operating | H: Back-board | 2: Yes |
D5: AC230V | C: Plug-in type | |
D6: AC110V | ||
D7: DC220V | ||
D8: DC110V | ||
D9: AC110-240V | ||
D10: DC100-220V |
Type | YCM8T-160S YCM8T/A-160S | YCM8RT-160H YCM8T/A-160H | YCM8RT-250S YCM8T/A-250S | CM8RT-250H YCM8RT-250H | |
Frame Current(A) | 160 | 250 | |||
Pole number | 3,4 | 3,4 | |||
Rated Current (A) | 20-25,25-32,32-40,40-50,50-63,63-80,80-100,100-125,,125-160 | 100-125,125-160,160-200,200-250 | |||
Rated voltage (V) | AC400V | AC400V | |||
Rated insulation voltage (V) | AC1000V | AC1000V | |||
Short Circuit Breaking Capacity (kA) Icu/Ics | AC400V | 25/18 | 35/25 | 25/18 | 35/25 |
Operating Circle Times | Charged ON | 3000 | 3000 | ||
Not charged OFF | 7000 | 7000 | |||
Dimension(mm) a-b-c-ca | 3P | 90-155-68-90 | 105-165-68-92 | ||
4P | 120-155-68-90 | 140-165-68-92 | |||
Weight(kg) | 3P | 1.0 | 1.0 | 1.5 | |
4P | 1.1 | 1.4 | 1.9 | ||
Electric operating device (MD) | ● | ● | |||
External drive handle | ● | ● | |||
Automatic release | Thermal electromagnetic type | Thermal electromagnetic type |
Type | YCM8RT-400S YCM8T/A-400S | YCM8RT-400H YCM8T/A-400H | YCM8RT-630S YCM8T/A-630S | YCM8RT-630H YCM8T/A-630H | YCM8RT-800H YCM8T/A-800H | YCM8RT-1250H YCM8T/A-1250H | |
Frame Current(A) | 400 | 630 | 800 | 1250 | |||
Pole number | 3,4 | 3,4 | 3,4 | 3,4 | |||
Rated Current (A) | 200-250, 250-320, 320-400 | 400-500, 500-630 | 400-500, 500-630,630-800 | 800-1000,1000-1250 | |||
Rated voltage (V) | AC400V | AC400V | AC400V | ||||
Rated insulation voltage (V) | AC1000V | AC1000V | AC1000V | ||||
Short Circuit Breaking Capacity (kA) Icu/Ics | AC400V | 35/25 | 50/35 | 35/25 | 50/35 | 50/35 | |
Operating Circle Times | Charged ON | 2000 | 2000 | 1500 | |||
Not charged OFF | 4000 | 4000 | 4000 | ||||
Dimension(mm) a-b-c-ca | 3P | 140-257-103-155 | 140-257-103-155 | 210-275-103-155 | |||
4P | 185-257-103-155 | 185-257-103-155 | 280-275-103-155 | ||||
3P | 5.5 | 5.7 | 9.5 | ||||
Weight(kg) | 4P | 7 | 7.5 | 12.5 | |||
Electric operating device (MD) | ● | ● | ● | ||||
External drive handle | ● | ● | ● | ||||
Automatic release | Thermal electromagnetic type | Thermal electromagnetic type | Thermal electromagnetic type |