Product Overview
Product Details
Data Download
Related Products
YCM8C series external circuit breakers are suitable for distribution networks with AC 50Hz or 60Hz, rated insulation voltage of 1000V, rated voltage of 400V and below, and rated current of 1000A. Under normal circumstances, the circuit breaker can be used for the infrequent on-off control of the line and the infrequent start of the
Contact Us
General
YCM8C series external circuit breakers are suitable for distribution networks with AC 50Hz or 60Hz, rated insulation voltage of 1000V, rated voltage of 400V and below, and rated current of 1000A. Under normal circumstances, the circuit breaker can be used for the infrequent on-off control of the line and the infrequent start of the motor respectively.
Standard:IEC60947-2;IEC60947-1;
Operating Conditions
1. Extreme temperature range for storage and transportation: -10°C to 85°C;
2. Operating range: -10°C to 75°C;
3. Reference temperature: 55°C;
4. Atmospheric conditions: The maximum temperature is 75 ℃ and the maximum relative humidity is 95%;
5. External magnetic fields at the installation site must not exceed 5 times the strength of the earth's magnetic field, and the product should be kept away from strong electromagnetic interference (such as high-power motors or inverters). There should be no explosive or corrosive gases, no exposure to rain or snow, and the environment should be dry and well-ventilated;
6. Pollution level: level 3; installation category: category III.
Technical data
Frame current Inm(A) |
250S |
400S |
630S |
800S |
1000S |
|
Working voltage Ue(V) |
400 |
|||||
Rated insulation voltage Ui(V) |
AC1000 |
|||||
Rated impulse withstand voltage Uimp(KV) |
8 |
|||||
Number of poles (P) |
3 |
|||||
Rated current In(A) |
100,125,140,160, 180,200,225,250 |
250,315,350,400 |
400,500,630 |
630,700,800 |
800,1000 |
|
Ultimate breaking capacity Icu (KA) |
AC240V |
35 |
50 |
50 |
65 |
65 |
AC415V |
25 |
35 |
35 |
40 |
40 |
|
Operating breaking capacity Ics (KA) |
AC240V |
35 |
50 |
50 |
65 |
65 |
AC415V |
25 |
25 |
25 |
40 |
40 |
|
Electrical life (times) |
1000 |
1000 |
1000 |
500 |
500 |
|
Mechanical life (times) |
7000 |
4000 |
4000 |
2500 |
2500 |
|
Operating voltage |
AC230V(85%~110%) |
|||||
Wiring |
Up in and down out,down in and up out |
|||||
Protection degree |
IP30 |
|||||
Isolation function |
Yes |
|||||
Tripping type |
Thermomagnetic |
|||||
Accessories |
Shunt,alarm,auxiliary |
|||||
Certificate |
CE |
Product feature configuration
The operation interface of the electric operating mechanism is shown in Figure 1
1. Circuit breaker status indication window
2. Mechanism lock
3. Tripping button
4. Power and control wiring ports
5. Manual and automatic switching of cover plates
Electrical control schematic
Overall and mounting dimensions
Specifications |
250/3P |
400/3P |
630/3P |
800/3P |
1000/3P |
L |
165 |
257 |
275.5 |
275.5 |
275.5 |
W |
105 |
140 |
210 |
210 |
210 |
A |
35 |
43.5 |
70 |
70 |
70 |
B |
144 |
230 |
243.5 |
243.5 |
243.5 |
C |
24 |
31 |
45 |
45 |
45 |
D |
21 |
29 |
30 |
30 |
30 |
E |
22.5 |
30 |
24 |
26 |
28 |
F |
118 |
160 |
175 |
175 |
175 |
a |
126 |
194 |
243 |
243 |
243 |
b |
35 |
44 |
70 |
70 |
70 |
Φd |
4×Φ4.5 |
4×Φ7 |
4×Φ8 |
4×Φ8 |
4×Φ8 |
Dimensions with protective cover
Size |
250/3P |
400/3P |
630/3P |
800/3P |
1000/3P |
A |
208 |
278 |
418 |
418 |
418 |
B |
105 |
140 |
238 |
238 |
238 |
C |
67.5 |
103 |
103 |
103 |
103 |