Product Overview
Product Details
Data Download
Related Products
Contact Us
General
YCM7YV series electronic plastic case circuit breaker (hereinafter referred to as: circuit breaker) is suitable for low-voltage power grids with AC 50Hz, rated insulation voltage 800V, rated operating voltage 400V and below, and rated operating current up to 800A. The circuit breaker has overload long-delay inverse time limit, short-circuit short-delay inverse time limit, short-circuit short-delay fixed time limit, short-circuit instantaneous and under-voltage protection functions. Under normal circumstances, the circuit
breaker is used for infrequent switching of circuits and infrequent starting of
motors.This series of circuit breakers has isolation function, and its corresponding symbol is " "
Standard: IEC60947-2.
Operating conditions
1. Ambient air temperature
a)The upper limit value does not exceed +40℃;
b)The lower limit value does not exceed -5℃;
c)The average value over 24 hours does not exceed +35℃;
2. Altitude
The altitude of the installation site does not exceed 2000m.
3. Atmospheric conditions
The relative humidity of the atmosphere does not exceed 50% when the ambient
maximum temperature is +40°C; it can have higher relative humidity at lower
temperatures; when the monthly average minimum temperature of the wettest
month is +25°C, the monthly average maximum temperature of the month is +25°C. The relative humidity is 90%, taking into account condensation that occurs on the
product surface due to temperature changes.
4. Pollution degree
Pollution degree 3, the accessories installed in the circuit breaker have a pollution degree 2.
5. Installation category
The main circuit of the circuit breaker shall be installation category III, and the auxiliary circuit and control circuitshall be installation category II.
6. Installation conditions.
Circuit breakers should generally be installed vertically, usually with upward wiring, and the external magnetic field at the installation site should not exceed 5 times the geomagnetic field in any direction.
Selection | |||||||||||
YCM7YV | 250 | M | / | 3 | 3 | 00 | 100-250A | ||||
Model | Shell frame | Breaking capacity | Number of poles | Tripping method | Accessorie | Rated current | |||||
YCM7YV | 160
250 400 630 |
M:Standard breaking | 3:3P | 3:Electronic | 00: No accessories |
16-32A
40-100A 64-160A 100-250A 252-630A |
Technical data
Type | YCM7YV-160M | YCM7YV-250M | YCM7YV-400M | YCM7YV-630M | |||||||
Frame(A) | 160 | 250 | 400 | 630 | |||||||
Number of poles | 3 | 3 | 3 | 3 | |||||||
Products | |||||||||||
Rated current adjustable range In(A) | 16-32,40-100, 64-160 |
100-250 | 160-400, | 160-400 252-630, |
|||||||
Rated voltage Ue(V) | AC400V | AC400V | AC400V | AC400V | |||||||
Rated insulation voltage Ui(V) | AC800V | AC800V | AC800V | AC800V | |||||||
Short-circuit breaking capacity Icu/1cs(kA) |
AC400V | 35/25 | 35/25 | 50/35 | 50/35 | ||||||
Operation life (cycle) | ON | 1500 | 1000 | 1000 | 1000 | ||||||
OFF | 8500 | 7000 | 4000 | 4000 | |||||||
Motor-driven operation | ● | ● | ● | ● | |||||||
External rotary handle | ● | ● | ● | ● | |||||||
Automatic tripping device | Electronic type | Electronic type | Electronic type | Electronic type |
Function Description
Specifications and functions |
|||
Classification |
Describe |
|
|
Display method |
LCD display+LED indicator |
● |
|
Interface operation |
key |
● |
|
Protection function |
Current protection |
Overload long delay protection function |
● |
Short circuit protection Time delayprotection |
● |
||
Short circuit instantaneous protection function |
● |
||
Overload warning function |
● |
||
Voltage protection |
Undervoltage protection work |
● |
|
Overvoltage protection function |
● |
||
Lack of phase protection function |
● |
||
Power side zero break protection function |
● |
||
Communication function |
D/LT645-2007 Multifunctional metercommunication protocol Modbus-RTu |
● |
|
Modbus-RTU communication protocol |
○ |
||
RS-485Communication hardware 1 RS-485 |
● |
||
External DI/0 port function |
Communication auxiliary power input |
○ |
|
One DI/0 programmable control input |
○ |
||
Fault record |
10 trip failure storage |
● |
|
80 protection function logout events recorded |
● |
||
10 gate position changeevents recorded |
● |
||
10 alarm event records |
● |
||
Time function |
With year, month, day, minute and second real-time clock function |
● |
|
Measurement function |
Measure electrical parameters |
Voltage 0.7Ue~1.3Ue,0.5% |
● |
Current 0.2In~1.2ln,0.5%: |
● |
||
Three-phase and total powerfactor 0.5~100005 |
● |
||
Three-phase and total active power, reactivpower,apparent power |
● |
||
Three-phase and total active energy, reactive energy,apparent energy |
● |
||
Voltage harmonics and total voltage harmonic distortion |
● |
||
Current harmonics and total current harmonic distortion |
● |
Note:
The symbol " ●" indicates that it has its function: the symbol " O"indicates that this function is optional; The symbol "-" indicates that thisfunction is unavailable
Model |
|
Mounting
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
160M |
105 |
- |
70 |
- |
- |
- |
- |
- |
165 |
144 |
104 |
59 |
110 |
- |
120 |
98 |
2 |
98 |
84 |
22.5 |
24 |
35 |
126 |
M8 |
250M |
105 |
- |
70 |
- |
- |
- |
- |
- |
165 |
144 |
104 |
59 |
110 |
- |
120 |
98 |
2 |
98 |
97 |
22.5 |
24 |
35 |
126 |
M8 |
400M |
140 |
- |
88 |
- |
140 |
- |
112 |
- |
257 |
230 |
179 |
100 |
110 |
42 |
155 |
110 |
3 |
110 |
97 |
29 |
30 |
44 |
194 |
M10 |
630M |
140 |
- |
88 |
- |
140 |
- |
112 |
- |
257 |
230 |
179 |
100 |
110 |
42 |
155 |
110 |
3 |
110 |
97 |
30 |
32 |
44 |
194 |
M10 |
800M |
210 |
- |
140 |
- |
180 |
- |
140 |
- |
257 |
243 |
192 |
90 |
110 |
87 |
155 |
107 |
5 |
104 |
97 |
25 |
25 |
70 |
243 |
M12 |