YCM6, YCM6RT series circuit breaker is a new generation of breaker.
This breaker is applied for the distribution network of AC 50/60Hz, rated insulation voltage 800V, rated working current up to 800A, which is for electric energy distribution, circuit protection, protecting power supply facility from being destroyed by the fault of overloading, short circuit and undervoltage. And it is also used for protecting, overloading, short circuit and undervoltage of the motor.
This breaker has such characteristics as high short circuit interrupting capacity, shortarcing and etc., which is a ideal product for users. This breaker can be installed vertically or hori-zontally.
Standard:lEC60947-2
Contact Us
1. Design miniaturized
The miniaturization of product volume can meet the individual needs of customers on installation size.
2. Size uniformed
Completely consistent installation size with same shell level beyond different breaking capacity(S,M) and different functions(air,leakage).
3. Reasonable parameter setting
Circuit breaker can realize long-time delay overload inverse time, short circuit instantaneous action protection functions such as parameter setting, users can set their own protective properties required, the distribution network is used in the circuit breaker on the lower level with more reasonable.
1. Altitude less than 2000m
2. Ambient medium temperature is from -5°C to +40°C (+45°C for shipping product)
3. Humidity resistance
4. Bacteria resistance
5. Nuelear radiation resistance
6. Max lean degree is 22.5 degree.
7. Can operate normally when it comes to vibrataion of ship.
8. Can operate normally when it comes to earthquake(4g).
9. The medium should be no risk of blasting and can't erode the metal and damage insulating gas as well as conductive dust.
10.Work in the places where is no rain and snow.
1. The circuit breaker (for power distribution) has reverse time breaking characteristics of overcurrent release in all pole states and is energized simultaneously at room temperature 40°C.
Test current | Current time | Conventional time | Inta status | |
In≤63 | In<63 | |||
Conventional non-trip current | 1.05 | 1h | 2h | Cold status |
Conventional trip current | 1.30 | <1h | <2h | Hot status |
2. When ambient temperature is +40'c for electrmotor protection breaker, power on for every pole, inverse time limit characteristic of no temperature compensation is in the following sheet.
Test current | Current time | Conventional time | Initial status |
In≤800 | |||
Conventional non-trip current | 1.0 | 2h | Cold status |
Conventional trip current | 1.2 | <2h | Hot status |
3. Action property of the short-circuit release of the breaker
♦ Instant trip (for power distribution)l=10ln
♦ Instant trip (for motor protection)l=12ln
♦ Current setting accuracy ±20%
YCM6 - 125 L P / 4 300 2 A 125A Q1 D1 Q 2
Type | Frame Inm | Breaking capacity Icu/lcs(kA) | Operation | Poles | |||||||||||||||
YCM6 | 125 | L | P | 4 | |||||||||||||||
MCCB | 125,160,250,400,630,000 | 125 18/9
160 18/9 250 25/18 400 35/25 630 35/25 800 50/35 |
P:Motor-driven
Z:Rotory handle W:Directly |
3:3P
4:4P |
Tripping mode and inner accessory | Application | Option for 4P MCCB | Rated current(A) | |||||||||||||||||
300 | 2 | A | 125A | |||||||||||||||||
First figure means tripping unit way
2:Only with magnetic release 3:Thermal release+,magnetic release body Remark: The last two figures means accessory code (see accessories list) |
1.Power distribution
2.Motor-protection |
A:N pole without protection,N poleis always ON B:N pole without protection,N pole makes with the other three poles |
125 32,40,50,63,80,100, 125 160 40,50,63,80,100,125, 140,160,100 250 125,140,160,180,200, 225,250 400 400,250,315,350,400 630 500,630 800 630,700,800 |
Accessory voltage | Motor-driven operation voltage | Connection | With the connection plate or not | |||||||||||||||
Q1 | D1 | Q | 2 | |||||||||||||||
UVT Q1:AC220V Q2:AC240V Q3:AC380V Q4:AC415V |
Shunt F1:AC220V F2:AC380V F3:DC110V F4:DC24V |
Auxiliary J1:AC125V J2:AC250V J3:DC125 J4:DC24V |
DC3 D5:AC220V D6:AC110V D7:DC220V D8:DC110V D9:AC110~240V D10:DC100~220V |
Q:Front H:Rear C:Plug-in |
1: not 2: yes |
Model case Circuit breaker |
Overall dimensions | Installing dimensions |
Bolt | |||||||||||||||||||||
A | A1 | A2 | A3 | B | B1 | B2 | B3 | B5 | B6 | H | H1 | H2 | H3 | H4 | H5 | H6 | A4 | B4 | ||||||
3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||||||||||
YCM6-125L | 75 | 100 | 50 | 75 | 130 | 114 | 85 | 50 | 50 | 72 | 4 | 68 | 61 | 41 | 24 | 41 | 25 | 111 | M8/M6 | |||||
YCM6-160L | 90 | 120 | 60 | 90 | 155 | 134 | 103 | 50 | 50 | 72 | 4 | 68 | 61 | 41 | 24 | 41 | 30 | 132 | M8 | |||||
YCM6-250L | 105 | 140 | 70 | 105 | 165 | 144 | 103 | 50 | 100 | 72 | 4 | 68 | 61 | 46 | 24 | 46 | 35 | 126 | M8 | |||||
YCM6-400L | 140 | 185 | 88 | 132 | 140 | 196 | 112 | 168 | 257 | 230 | 179 | 90 | 110 | 43 | 107 | 5 | 105 | 97 | 64 | 36 | 64 | 44 | 194 | M10 |
YCM6-630L | 140 | 185 | 88 | 132 | 140 | 196 | 112 | 168 | 257 | 230 | 179 | 90 | 110 | 42 | 107 | 5 | 105 | 97 | 64 | 36 | 64 | 44 | 194 | M10 |
YCM6-800L | 210 | 280 | 140 | 210 | 180 | 250 | 140 | 210 | 275 | 243 | 192 | 90 | 110 | 87 | 107 | 5 | 104 | 97 | 65 | 24 | 65 | 70 | 242.5 | M12 |
Thermal magnetic trip circuit breaker |
Themal adjustable circuit breaker |
Overalldmensions | Instaling dmensions |
Bolt | |||||||||||||||||||||
A | A1 | A2 | A3 | B | B1 | B2 | B3 B5 | B6 | H | H1 | H2 | H3 | H4 | H5 | H6 | A4 | B4 | |||||||||
3P 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||||||||||||
YCM6RT-160L | YCM6T/A-160S | 90 | 120 | 60 | 90 | 155 | 134 | 103 | 50 | 50 | 94 | 72 | 4 | 68 | 61 | 47 | 24 | 30 | 132 | M8 | |||||
YCM6RT-250L | YCM6T/A-250S | 105 | 140 | 70 | 105 | 165 | 144 | 103 | 50 | 100 | 96 | 72 | 4 | 68 | 61 | 46 | 24 | 35 | 126 | M8 | |||||
YCM6RT-400L | YCM6T/A400S | 140 | 185 | 88 | 132 | 140 | 196 | 112 | 168 | 257 | 230 | 179 | 90 | 110 | 42 | 155 | 107 | 5 | 105 | 97 | 64 | 36 | 44 | 194 | M10 |
YCM6RT-630L | YCM6T/A630M | 140 | 185 | 88 | 132 | 140 | 196 | 112 | 168 | 257 | 230 | 179 | 90 | 110 | 42 | 155 | 107 | 5 | 105 | 97 | 64 | 36 | 44 | 194 | M10 |
YCM6RT-800L | YCM6T/A-800M | 210 | 280 | 140 | 210 | 180 | 250 | 140 | 210 | 175 | 243 | 192 | 90 | 110 | 87 | 155 | 107 | 5 | 104 | 97 | 65 | 24 | 70 | 242.5 | M12 |
Internal accessories of YCM6,YCM6RT series include undervoltage release, shunt release and auxiliary alarm release, their main technical parameters and wiring diagram are as follows:
The main technical parameters, dimensions and installation diagrams of external accessories for YCM7, YCM7RT and YCM7E series are as follows:
DC3 electric operating mechanism.
DIN Rail Adapter | Applicable frame | Rated thermal current Ith |
![]() |
YCM6-125 | 3P |
YCM6-160 | ||
YCM6-250 |