Product Overview
Product Details
Data Download
Related Products
Contact Us
General
Cage type isolation switch YCISC8 series is suitable for DC power systems with rated voltage DC1200V and below and rated current 32A and below. This product is used for infrequent on/off, and can disconnect 1~2 MPPT lines at the same time. It is mainly used in the control cabinet, distribution box and combiner box of the photovoltaic power generation system, and is used for isolation of the DC power distribution system. The external waterproof performance of this product reaches IP66.
Standard: IEC/EN60947-3: AS60947.3, UL508i.
Features
● E type external installation can reach IP66 waterproof level at any angle;
● UV resistant and V0 flame retardant material;
● Contact silver plating, silver layer thickness reaches the highest standard in the industry;
● Arc extinguishing time(3ms);
● The bottom of the external box is equipped with a breather valve;
● Nonpolarity;
● Lockable in closed position;
● 4 installation modes optional.
Selection
Accessory Selection
YCISC8 | - | 32 | X | PV | P | 2 | MC4 | 13A | + | YCISC8-C |
Model | Rated current | With lock or not | Usage | Installation mode | Wiring mothod | Joint type | Rated current | Model | ||
Isolation switch | 32 | /: No lock X: With lock | PV: Photovoltaic/ direct-current |
No: Din rail installation | 244B 4T4S | /: No | DC1000 DC1200 | C: Terminal shield | ||
P: Panel installation |
/: No | |||||||||
D: Door lock installation | /:No MC4: MC4joint |
|||||||||
E: External installation |
Note: The "Din rail installation" and "external installation" can only be with the lock
Technical data
Model | YCISC8-32PV | |||
Standard | IEC/EN60947-3:AS60947.3, UL508i | |||
Use category | DC-PV1, DC-PV2 | |||
Appearance | Din rail installation | Panel installation | Door lock installation | External |
Wiring method | 2,2H,4,4T,4B,4S | /,2MC4,4MC4 | ||
Shell frame grade | 32 |
Electrical performance | ||||
Rated heating current Ith(A) | 32 | |||
Rated insulation voltage Ui(V DC) | 1500 | |||
Rated working voltage Ue(V DC) | 1000V or 1200V | |||
Rated impulse voltage Uimp(kV) | 8 | |||
Rated short-time withstand current Icw(1s)(kA) | 1kA | |||
Rated short-time making capacity(Icm)(A) | 1.7kA | |||
Rated short circuit current(Icn) | 3kA | |||
Overvoltage category | II | |||
Polarity | No polarity, "+" and "-" polarity can be interchanged | |||
Switch knob position | 9 o'clock position off, 12 o'clock position on (or 12 o'clock position off, 3 o'clock position on) |
|||
Service life | Mechanical | 10000 | ||
Electrical | 3000 | |||
Applicable environmental conditions and installation | ||||
Maximum wiring capacity (including jumper wires) | ||||
Single wire or standard(mm²) | 4月16日 | |||
Flexible cord(mm²) | 4月10日 | |||
Flexible cord (+ stranded cable end)(mm²) | 4月10日 | |||
Torque | ||||
Tightening torque of terminal M4 screw(Nm) | 1.2-1.8 | |||
Tightening torque of upper cover mounting screw ST4.2 (304 stainless steel)(Nm) | 1.5-2.0 | |||
Tightening torque of knob M3 screw(Nm) | 0.5-0.7 | |||
Bottom wiring torque(Nm) | 1.1-1.4 | |||
Environment | ||||
Protection degree | IP20; External type IP66 | |||
Operating temperature(℃) | -40~+85 | |||
Storage temperature(℃) | -40~+85 | |||
Pollution degree | 3 | |||
Overvoltage category | III |
Wiring diagram
Type | 2-Pole | 4-Pole | 4-Pole with Input and Output on top | 4-Pole with Input and Output bottom | 4-Pole with Input on top Output bottom |
YCISC8-32 DC1000/DC1200 |
2 | 4 | 4T | 4B | 4S |
Contacts Wiring graph |
|||||
Switching example |
Din rail installation
Panel installation
Door lock installation
Photovoltaic Isolator switch
External installation
Current/Voltage category parameter table
The following current data IEC/EN60947-3:2009+A1+A2, AS60947.3, use category DC-PV1, DC-PV2
Model | Series | Wiring method | 300V | 600V | 800V | 1000V | 1200V | |||||
PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | |||
YCISC8-32XPV □2 DC1000 | 1 | 2 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | / | / |
YCISC8-32XPV □2 DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | 13 | 9 | |
YCISC8-32XPV □4 DC1000 | 2 | 4 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | / | / |
YCISC8-32XPV □4 DC1200 | 2 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | 13 | 9 | |
YCISC8-32XPV □4S DC1000 | 1 | 4S | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4S DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | |
YCISC8-32XPV □4B DC1000 | 1 | 4B | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4B DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | |
YCISC8-32XPV □4T DC1000 | 1 | 4T | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4T DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 |
Data comply with AS60947-3
Main contact | Voltage | DC1000 | DC1200 |
Rated thermal current Ithe | 32A | ||
Rated insulation voltage Ui | 1500V | ||
Contact spacing (per pole) | 8mm | ||
Rated working current Ie(DC-PV2) | |||
4 layers, only 2 layers in series, with two loads 1 2 |
300V | 32A | 32A |
600V | 32A | 32A | |
800V | 16A | 16A | |
1000V | 9A | 9A | |
1200V | / | 9A | |
4 layers, 4 layers in series, one load 2 3 4 |
300V | 32A | 32A |
600V | 32A | 32A | |
800V | 32A | 32A | |
1000V | 32A | 32A | |
1200V | / | 32A |
AS60947-3
Type | 35 25 20 15 10 5 40 50 60 70 80 90 100 Temperature around the switch(℃) 500V/6mm² 600V/6mm² 700V/6mm² 800V/4mm² 1000V/2.5mm² |
|||||
Number of poles | 4-pole | |||||
Terminal name, main circuit | 1; 3; 5;7; 2; 4; 6; 8 | |||||
Terminal type, main circuit | Screw terminal | |||||
Cable cross-section | 4.0-16mm² | |||||
Conductor type | 4-16mm (rigidity: solid or stranded) | |||||
4-10mm Flexible | ||||||
Number of wires per terminal | 1 | |||||
Preparation required for wire | Yes | |||||
Stripping length (mm),main circuit | 8mm | |||||
Tightening torque (M4), main circuit | 1.2~1.8N.m |