Product Overview
Product Details
Data Download
Related Products
The YCFK intelligent capacitor switching device uses thyristor switch and magnetic holding switch in parallel operation.
It has the advantage of controllable silicon zero-crossing switch at the moment of connection and disconnection, and zero power consumption of the mag- netic holding switch during normal connection.
Contact Us
Note: For Three-phase Individual Compensation (Y), the maximum rated current reaches 63A; the rated current corresponds to the compensation capacitor capacity as shown in the table.
Use environment
Environmental temperature: -20°C to +55°C
Relative humidity: ≤90% at 40°C
Altitude: ≤2500m
Environmental conditions: No harmful gases and vapors, no conductive or explosive dust, no severe mechanical vibrations.
Technical data
Rated working voltage |
Common compensation AC380V ±20% / Separate compensation AC220V ±20% |
Rated frequency |
50Hz |
Rated current |
45A, 63A, 80A |
Control capacitor capacity |
Three-phase ≤50Kvar Delta connection; Single-phase ≤30KvarY connec- tion |
Power consumption |
≤1.5VA |
Service life |
300,000 times |
Contact voltage drop |
≤100mV |
Contact withstand voltage |
>1600V |
Response time: |
1000ms |
Time interval between each connection and disconnection |
≥5s |
Time interval between each connection and disconnection |
≥5s |
Control signal |
DC12V ±20% |
Input impedance |
≥6.8KΩ |
Conduction impedance |
≤0.003Ω |
Inrush current |
<1.5In |
YCFK-□S(Standard type)
Compensation method |
Model |
Control capacity (Kvar) |
Control current(A) |
Number of poles |
Adaptation controller |
Three-phase Common Compensation |
YCFK- △ -400-45S |
≤ 20 |
45 |
3P |
JKWD5 |
YCFK- △ -400-63S |
≤ 30 |
63 |
3P |
JKWD5 |
|
YCFK- △ -400-80S |
≤ 40 |
80 |
3P |
JKWD5 |
|
Phase compensation |
YCFK-Y-400-45S |
≤ 20 |
45 |
A+B+C |
JKWF |
YCFK-Y-400-63S |
≤ 30 |
63 |
A+B+C |
JKWF |
YCFK-□D(with circuit breaker)
Compensation method |
Model |
Control capacity (Kvar) |
Control current(A) |
Number of poles |
Adaptation controller |
Three-phase Common Compensation |
YCFK- △ -400-45D |
≤ 20 |
45 |
3P |
JKWD5 |
YCFK- △ -400-63D |
≤ 30 |
63 |
3P |
JKWD5 |
|
Phase compensation |
YCFK-Y-400-45D |
≤ 20 |
45 |
A+B+C |
JKWF |
YCFK-Y-400-63D |
≤ 30 |
63 |
A+B+C |
JKWF |
Wiring diagram
Precautions:
Before use, it is essential to carefully check the terminal screws of the main circuit connection. They must be securely tightened; otherwise, loose screws during operation can easily lead to damage to the switch.
(The incoming and outgoing wire terminals of this product are equipped with anti-loosening self-locking nuts, effectively ensuring that the prod- uct does not experience secondary loosening of the connections due to factors such as transportation and vibrations after the connections are securely made.)