Product Overview
Product Details
Data Download
Related Products
General
YCCH6Z series AC contactor (hereinafter referred to as the household
appliances control a contactor) is used for remote switch on and off without a
sense of feeling or low load, resistance furnace, household appliances and similar low load, motor and other household.
The main contactor is used in AC 50Hz/60Hz, rated voltage to 400V, rated current
of power system to 100A, AC-1, AC-7a (in no sense or sense of low load,
resistance furnace, household appliances and similar low load) categories, long distance switch and control circuit.
Contactor is not used for breaking short circuit current, so it is necessary to choose suitable short circuit protection electrical equipment.
Standard: IEC/EN 61095
Contact Us
General
YCCH6Z series AC contactor (hereinafter referred to as the household appliances control a contactor) is used for remote switch on and off without a sense of feeling or low load, resistance furnace, household appliances and similar low load, motor and other household.
The main contactor is used in AC 50Hz/60Hz, rated voltage to 400V, rated current of power system to 100A, AC-1, AC-7a (in no sense or sense of low load, resistance furnace, household appliances and similar low load) categories, long distance switch and control circuit.
Contactor is not used for breaking short circuit current, so it is necessary to choose suitable short circuit protection electrical equipment.
Standard: IEC/EN 61095
Type designation
(eg. YCCH6Z-25/20 AC/DC24V . It is 25A , 2NO ,230V AC/DC coil voltage)
1P, 1Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-16/10 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1
A2 2 |
YCCH6Z-20/10 |
20A |
7A |
||
YCCH6Z-25/10 |
25A |
9A |
||
YCCH6Z-32/10 |
32A |
12A |
||
YCCH6Z-16/01 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 l b
A2 R2 |
YCCH6Z-20/01 |
20A |
7A |
||
YCCH6Z-25/01 |
25A |
9A |
||
YCCH6Z-32/01 |
32A |
12A |
1P, 2Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-40/10 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1
A2 2 |
YCCH6Z-63/10 |
63A |
25A |
||
YCCH6Z-40/01 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 l b
A2 R2 |
YCCH6Z-63/01 |
63A |
25A |
2P, 1Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-16/20 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3
A2 2 4 |
YCCH6Z-20/20 |
20A |
7A |
||
YCCH6Z-25/20 |
25A |
9A |
||
YCCH6Z-32/20 |
32A |
12A |
||
YCCH6Z-16/11 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 3
A2 R2 4 |
YCCH6Z-20/11 |
20A |
7A |
||
YCCH6Z-25/11 |
25A |
9A |
||
YCCH6Z-32/11 |
32A |
12A |
||
YCCH6Z-16/02 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3
A2 2 4 |
YCCH6Z-20/02 |
20A |
7A |
||
YCCH6Z-25/02 |
25A |
9A |
||
YCCH6Z-32/02 |
32A |
12A |
2P, 2Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-40/20 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3
A2 2 4 |
YCCH6Z-63/20 |
63A |
25A |
||
YCCH6Z-40/11 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 3
A2 R2 4 |
YCCH6Z-63/11 |
63A |
25A |
||
YCCH6Z-40/02 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3
A2 2 4 |
YCCH6Z-63/02 |
63A |
25A |
3P, 2Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-16/30 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5
A2 2 4 6 |
YCCH6Z-20/30 |
20A |
7A |
||
YCCH6Z-25/30 |
25A |
9A |
||
YCCH6Z-32/30 |
32A |
12A |
||
YCCH6Z-16/03 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 R3 R5
A2 R2 R4 R6 |
YCCH6Z-20/03 |
20A |
7A |
||
YCCH6Z-25/03 |
25A |
9A |
||
YCCH6Z-32/03 |
32A |
12A |
3P, 3Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-40/30 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5
A2 2 4 6 |
YCCH6Z-63/30 |
63A |
25A |
||
YCCH6Z-40/03 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 R3 R5
A2 R2 R4 R6 |
YCCH6Z-63/03 |
63A |
25A |
4P, 2Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 |
AC-7b AC-3 |
|||
YCCH6Z-16/40 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5 7
A2 2 4 6 8 |
YCCH6Z-20/40 |
20A |
7A |
||
YCCH6Z-25/40 |
25A |
9A |
||
YCCH6Z-32/40 |
32A |
12A |
||
YCCH6Z-16/04 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 R3 R5 R7
A2 R2 R4 R6 R8 |
YCCH6Z-20/04 |
20A |
7A |
||
YCCH6Z-25/04 |
25A |
9A |
||
YCCH6Z-32/04 |
32A |
12A |
||
YCCH6Z-16/22 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 1 3 R3
A2 R2 2 4 R4 |
YCCH6Z-20/22 |
20A |
7A |
||
YCCH6Z-25/22 |
25A |
9A |
||
YCCH6Z-32/22 |
32A |
12A |
||
YCCH6Z-16/31 |
16A |
6A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5 R1
A2 2 4 6 R2 |
YCCH6Z-20/31 |
20A |
7A |
||
YCCH6Z-25/31 |
25A |
9A |
||
YCCH6Z-32/31 |
32A |
12A |
4P, 3Modules
Contactor Model |
Ie Rating |
Uc |
Circuit Diagram |
|
AC-7a AC-1 AC-7b AC-3 |
||||
YCCH6Z-40/40 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5 7
A2 2 4 6 8 |
YCCH6Z-63/40 |
63A |
25A |
||
YCCH6Z-40/40 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 R3 R5 R7
A2 R2 R4 R6 R8 |
YCCH6Z-63/04 |
63A |
25A |
||
YCCH6Z-40/22 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 R1 1 3 R3
A2 R2 2 4 R4 |
YCCH6Z-63/22 |
63A |
25A |
||
YCCH6Z-40/31 |
40A |
18A |
12V AC/DC 24V AC/DC 48V AC/DC 110V AC/DC 230V AC/DC |
A1 1 3 5 R1
A2 2 4 6 R2 |
YCCH6Z-63/31 |
63A |
25A |
Modular contactor power consumption
Poles |
Ie Rating |
Uc (VAC)(50Hz) |
Power consumption |
Max power |
||
AC-7a |
AC-7b |
Hold on |
Pull in |
|||
2P |
16A |
6A |
230 |
2.1VA |
2.1VA |
2.0VA |
20A |
7A |
230 |
2.1VA |
2.1VA |
2.0VA |
|
25A |
9A |
230 |
2.1VA |
2.1VA |
2.0VA |
|
32A |
12A |
230 |
2.1VA |
2.1VA |
2.0VA |
|
40A |
18A |
230 |
2.3VA |
2.3VA |
2.0VA |
|
63A |
25A |
230 |
2.3VA |
2.3VA |
2.0VA |
|
4P |
16A |
6A |
230 |
2.3VA |
2.3VA |
2.0VA |
20A |
7A |
230 |
2.3VA |
2.3VA |
2.0VA |
|
25A |
9A |
230 |
2.3VA |
2.3VA |
2.0VA |
|
32A |
12A |
230 |
2.3VA |
2.3VA |
2.0VA |
|
40A |
18A |
230 |
6.0VA |
6.0VA |
5.5VA |
|
63A |
25A |
230 |
6.0VA |
6.0VA |
5.5VA |
Modular contactor auxiliary
Auxiliary Contacts
The Auxiliary contacts are indicator contactor contacts status switch OFF or ON
AC-12 |
AC-12 |
AC-12 |
Rated Current |
Circuit Diagram |
||||
C.V. |
V.A. |
C.V. |
V.A. |
C.V. |
V.A. |
|||
YCCH6Z-AUC11 |
240V |
5A |
240V |
5A |
240V |
5A |
5A |
R1 1
R2 2 |
YCCH6Z-AUC20 |
240 |
5A |
240 |
5A |
240 |
5A |
5A |
1 3
2 4 |
Spacing piece
Spacers are used to reduce the temperature rise of devices mounted side by side. It is recommended to separate electronic equipment (temperature adjustment devices, programmable timer etc.) from electromechanical equipment (impulse relays,contactors)
Main parameter and technical performance
Power circuit |
|
|
Voltage rating (Ue) |
1P, 2P |
250V AC |
3P, 4P |
400V AC |
|
Frequency |
50/60Hz |
|
Endurance(O-C) |
1,000,000 cycles |
|
Electrical |
100,000 cycles |
|
Maximum number of switching operation a day |
100 |
|
Insulation vwltage (Ui) |
500 V AC |
|
Pollution degree |
2 |
|
Rated impulse withstand voltage (Uimp) |
2.5kV(4kV for 12/24/48VAC) |
|
Degree of protection (IEC 60529) |
Device only |
IP20 |
Device in modular enclosure |
IP40 |
|
Operating temperature |
-5℃~+60℃ |
|
Storage temperature |
-40℃~+70℃ |
|
Tropicalization (IEC 60068.1) |
Treatment 2 (relative humidity 95% at 55℃) |
ELSV compliance(Extra Low Safety Voltage)for 12/24/48vac versions
The product control conforms to the SELV (safety extra low voltage) requirements
(1)In the case of contactor mounting in a enclosure for which the interior temperature is in range detween 50 ℃ and 60 ℃, it is necessary to use a spacer, between each
contactor
Packing information
Poles |
Rated Current (A) |
Box Qty |
CTN Qty |
Automatic Contactor |
Automatic Contactor |
Carton Size (mm) |
||
G.W.(kg) |
N.W.(kg) |
G.W.(kg) |
N.W.(kg) |
|||||
2P |
16 |
230 |
2.1VA |
2.1VA |
2.0VA |
2.1VA |
2.0VA |
500×260×190 |
20 |
230 |
2.1VA |
2.1VA |
2.0VA |
2.1VA |
2.0VA |
500×260×190 |
|
25 |
230 |
2.1VA |
2.1VA |
2.0VA |
2.1VA |
2.0VA |
500×260×190 |
|
32 |
230 |
2.1VA |
2.1VA |
2.0VA |
2.1VA |
2.0VA |
500×260×190 |
|
40 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
|
63 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
|
4P |
16 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
20 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
|
25 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
|
32 |
230 |
2.3VA |
2.3VA |
2.0VA |
2.3VA |
2.0VA |
500×260×190 |
|
40 |
230 |
6.0VA |
6.0VA |
5.5VA |
6.0VA |
5.5VA |
500×260×190 |
|
63 |
230 |
6.0VA |
6.0VA |
5.5VA |
6.0VA |
5.5VA |
500×260×190 |
Type |
Box Qty |
CTN Qty |
G.W.(kg) |
N.W.(kg) |
Carton Size (mm) |
Auxiliary Contacts |
12 |
120 |
5.56 |
3.96 |
500×260×190 |
3mm Spacing piece |
72 |
720 |
5.56 |
3.36 |
500×260×190 |
9mm spacing piece |
24 |
360 |
6.38 |
5.18 |
455×230×240 |
Connection parameter
Type |
Rating |
Lenght tripping |
Circuit |
Tightening torque |
Copper cables |
|||
Rigid |
Flexible or ferrule |
|||||||
|
|
|
|
|
|
|||
YCCH6Z |
PZ1:4mm |
16-63A |
9mm |
Control |
0.8N.m |
1.5~2.5mm2 2×1.5mm2 |
1.5~2.5mm2 2×2.5mm2 |
|
16-32A |
Power |
1.5~6mm2 |
1~4mm2 |
|||||
PZ2:6mm |
40A-63A |
14mm |
3.5N.m |
6~25mm2 |
6~16mm2 |
|||
BACTs |
PZ1:4mm |
- |
9mm |
- |
0.8N.m |
1.5~2.5mm2 2×1.5mm2 |
1.5~2.5mm2 2×2.5mm2 |