Product Overview
Product Details
Data Download
Related Products
General
1.Protection against the effects of sinusoidal alternating earth fault currents
2.Protection against indirect contacts and additional protection against direct contacts
3.Protection against fire hazard caused byinsulation faults
4.Controlling and Switching
5.Used in residential building,non-residential building,energysources,industryand infrastructure
Contact Us
1. Protection against the effects of sinusoidal alternating earth fault currents
2. Protection against indirect contacts and additional protection against direct contacts
3. Protection against fire hazard caused by insulation faults
4. Controlling and Switching
5. Used in residential building, non-residential building, energy sources, industry and infrastructure
Type | Tripping sensitivity data | ||
AC | For residual sinusoidal alternating currents | 30mA | For personnel,material and fire protection,as well as Tor protection against airect contact |
A | For residual sinusoidal alternating currents and residual pulsating direct currents | 100mA | For providing protection against indirect contacts |
S | For selectivity,with time delay | 300mA | For providing fire protection in case of insulation faults |
Type | Standard | IEC/EN 61008-1 | |
Electrical features | Leakage type | Electromagnetic type | |
Rated current In | A | 16,25,32,40,50,63,80,100 | |
Type (wave form of the earth leakage sensed) | A,AC | ||
Poles | P | 1P+N,3P+N | |
Rated voltage Ue | V | 230/400 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity Inc=l4c | A | 600,010,000 | |
Rated impulse withstand voltage (1.2/50)Uimp | V | 6000 | |
Dielectric test voltage at ind.Freq.for 1min | kV | 2.5 | |
Rated sensitivity I△n | A | 0.03,0.1,0.3 | |
Rated residual making and breaking capacity l-m | A | 500(ln≤40A);630(In=50A/63A);1000(In=80A/100A) | |
Pollution degree | |||
Electrical life | t | 4000 | |
Mechanical features | Mechanical life | t | 8000 |
Protection degree | IP20 | ||
Storage temperature | ℃ | -25~+70 | |
Ambient temperature(with daily average≤35℃) | ℃ | -5~+40 | |
Terminal connection type | Cable/Pin-type busbar/U-type busbar | ||
Installation | Terminal size top /bottom for cable | mm² | 25/35 |
AWG | 18-3/18-2 | ||
Terminal size top /bottom for busbar | mm² | 10月16日 | |
AWG | 18-8/18-5 | ||
Tightening torque | N*m | 2.5 | |
In-Ibs | 22 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip | ||
Connection | From top or bottor |