Product Overview
Product Details
Data Download
Related Products
General
1.Protection againstoverload and short-circuit currents
2.Protection against the effectsof sinusoidal alternating earth fault currents
3.Protection against indirect contacts and additional protection against directcontacts.
4.Protection against fire hazard causedbyinsulation faults
5.Usedin residentialbuilding
6.According tothe type of instantaneousrelease classified as follows:type B(3-5)In,type C(5-10)In
Contact Us
1. Protection against overload and short-circuit currents.
2. Protection against the effects of sinusoidal alternating earth fault currents.
3. Protection against indirect contacts and additional protection against direct contacts.
4. Protection against fire hazard caused by insulation faults.
5. Used in residential building.
6. According to the type of instantaneous release classified as follows: type B(3-5)ln, type C(5-10)ln.
YCB9HL-63 RCBO is an combined structure,the N pole is on the right side of the product. It has the following characteristics:
Without auxiliary power supply, it overcomes the defects of electronic products;
poor anti-interference, be greatly affected by power grid voltage fluctuation and can't be protected if the neutral line is disconnected;
Test circuit is dynamic controlled, and the test resistance is not easy to burn;
N pole contact can be opened and closed separately, with isolation function;
The impulse withstand voltage between L pole and N pole can reach up to 6000V;
The impulse withstand voltage between L pole, N pole and the metal support can reach up to 8000V;
Under the impact current of 200A, it has the ability to bear, and does not cause misoperation.
Type | Test current | Tripping time | Expected result |
B,C | 1.13In | t≤1h(In≤63A) | Not tripping |
1.13In | t≤2h(In>63A | ||
B,C | 1.45In | t<1h(In≤63A) | Tripping |
145In | t<2h(In>63A) | ||
B,C | 2.55In | s<t<60s(In≤32A) | Tripping |
2.55In | 1s<t<120s(In>32A) | ||
B | 3In | t≤0.1s | Not tripping |
C | 5In | t≤0.1s | |
B | 5In | t<0.1s | Tripping |
C | 0In | t<0.1s |
Type | Standard | EC/EN 61009-1 | |
Electrical features | Leakage type | Electromagnetic type | |
Rated current In | A | 6,10,16,20,25,32,40,50,63 | |
ype(wave form of the earth leakage sensed) | A,AC | ||
Poles | P | 1P+N | |
Rated voltage Ue | V | 230 | |
nsulation voltage Ui | V | 500 | |
Rated frequenc) | Hz | 50/60 | |
Rated breaking capacity Icn | A | 6000 | |
Rated impulse withstand voltage (1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind.Freq.for 1min | kV | 2 | |
Rated sensitivity I△n | A | 0.03,0.05,0.1 | |
Break time under I△n | S | ≤0.1 | |
Rated residual making and breaking capacity I△m | A | 500 | |
Pollution degree | 2 | ||
Mechanica features | Electrical life | t | 4000 |
Mechanical life | t | 8000 | |
Protection degree | IP20 | ||
Storage temperature | ℃ | 25~+70 | |
Ambient temperature (with daily average≤35℃) | ℃ | -5~+40 | |
Installation | Terminal connection type | Cable/U-type bar/Pin-type busbar | |
Terminal size top /bottom for cable | mm² | 16 | |
AWG | 5月18日 | ||
Terminal size top /bottom for busbar | mm² | 16 | |
AWG | 5月18日 | ||
Tightening torque | N*m | 1.2 | |
In-Ibs | 11 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip | ||
Connection | From top or bottom |
Can you supply the relevant documentation?
Yes, we can provide most documentation including Certificates of Analysis / Conformance; Insurance; Origin, and other export documents where required.
What is the average lead time?
For samples, the lead time is about 7 days. For mass production, the lead time is 20-30 days after receiving the deposit payment. The lead times become effective when (1) we have received your deposit, and (2) we have your final approval for your products. If our lead times do not work with your deadline, please go over your requirements with your sale. In all cases we will try to accommodate your needs. In most cases we are able to do so.