YCB9-80M/H MCB
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCB9-80M/H MCB
Picture
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB
  • YCB9-80M/H MCB

YCB9-80M/H MCB

The YCB9-80 series miniature circuit breaker are suitable for overcurrent protection building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 80A circuits.
They have isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines under normal circumstances.
Circuit breakers are suitable for various places such as industry, commerce, high-rise buildings, and residential buildings.
Standard: IEC/EN 60898-1

Contact Us

Product Details

YCB9-80M 1P (45°)

General
The YCB9-80 series miniature circuit breaker are suitable for overcurrent protection of building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 80A circuits. They have isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines under normal circumstances. Circuit breakers are suitable for various places such as industry, commerce, high-rise buildings, and residential buildings.
Standard: IEC/EN 60898-1

 

YCB9 80  M 1P C 16  Double busbar
Model Shell grade
current
Breaking
capacity
Number
of poles
Tripping
characteristics
Rated
current
Others
Miniature
circuit breaker
80  M:6kA
H:10kA
1P
2P

3P
4P

B
C

D

1
2
4
6
10
16
20
25
32
40
50
63
80

/:Single busbar
DB:Double
busbar

Note: This product c)an be assembled with accessories(YCB9-80 OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc

Technical data

Type

Standard

 

 

 

Function

 

Overload, Short circuit, Isolation

Comprehensive data

Number of poles

 

1P,2P,3P,4P

Rated current In

A

1-80A

Rated frequency

Hz

50/60Hz

 

Rated voltage Ue

V

230/400

 

Rated insulation voltage Ui

V

500

 

Rated breaking capacity Icn

A

M:6000  H:10000

Electrical features

Rated impulse withstand voltage Uimp(1.2/50)

kA

4

Pollution degree

 

2

Use category

 

II、III

 

Trip type

 

Thermal magnetic release

 

Thermal magnetic tripping characteristics

 

B,C,D

 

Electrical and mechanical accessories

 

 

Mechanical life

Times

20000

 

Electrical life

Times

10000

 

 

Mechanical features

Protection degree

 

IP20

 

Antihumidity and heat resistance

 

The relative humidity of the air is not more than 50% when

the ambient air temperature is +40°C, and it can have a

higher relative humidity at a lower temperature

Reference ambient temperature

°C

30

 

Ambient temperature

°C

-5°C-+40°C, the average value of 24h does not exceed +35°C

 

Height

m

Not exceeding 2000

 

Busbar connection type

 

Single or Double bus bar Anti-mistake contact terminal block

 

 

 

 

Installation

Terminal connection type

 

Cable/U-type busbar/Pin-type busbar

 

Maximum

wire capacity

Terminal size

top/bottom for cable

mm²

25

AWG

18-3

Terminal size

top/bottom for busbar

mm²

25

AWG

18-3

Torque

N*m

2

In-lbs

18

 

Tool

18

Phillips screwdriver or flat-blade screwdriver

 

Installation

 

On DIN rail EN 60715 (35mm) by means of fast clip device

 

Wiring method

 

From top or bottom