Product Overview
Product Details
Data Download
Related Products
Contact Us
General
The YCB9-80 series miniature circuit breaker are suitable for overcurrent protection of building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 80A circuits. They have isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines under normal circumstances. Circuit breakers are suitable for various places such as industry, commerce, high-rise buildings, and residential buildings.
Standard: IEC/EN 60898-1
YCB9 | 80 | M | 1P | C | 16 | Double busbar |
Model | Shell grade current |
Breaking capacity |
Number of poles |
Tripping characteristics |
Rated current |
Others |
Miniature circuit breaker |
80 | M:6kA H:10kA |
1P 2P 3P |
B C D |
1 |
/:Single busbar DB:Double busbar |
Note: This product c)an be assembled with accessories(YCB9-80 OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc
Technical data
Type |
Standard |
|
|
|
|
Function |
|
Overload, Short circuit, Isolation |
|
Comprehensive data |
Number of poles |
|
1P,2P,3P,4P |
|
Rated current In |
A |
1-80A |
||
Rated frequency |
Hz |
50/60Hz |
||
|
Rated voltage Ue |
V |
230/400 |
|
|
Rated insulation voltage Ui |
V |
500 |
|
|
Rated breaking capacity Icn |
A |
M:6000 H:10000 |
|
Electrical features |
Rated impulse withstand voltage Uimp(1.2/50) |
kA |
4 |
|
Pollution degree |
|
2 |
||
Use category |
|
II、III |
||
|
Trip type |
|
Thermal magnetic release |
|
|
Thermal magnetic tripping characteristics |
|
B,C,D |
|
|
Electrical and mechanical accessories |
|
□ |
|
|
Mechanical life |
Times |
20000 |
|
|
Electrical life |
Times |
10000 |
|
Mechanical features |
Protection degree |
|
IP20 |
|
Antihumidity and heat resistance |
|
The relative humidity of the air is not more than 50% when the ambient air temperature is +40°C, and it can have a higher relative humidity at a lower temperature |
||
Reference ambient temperature |
°C |
30 |
||
|
Ambient temperature |
°C |
-5°C-+40°C, the average value of 24h does not exceed +35°C |
|
|
Height |
m |
Not exceeding 2000 |
|
|
Busbar connection type |
|
Single or Double bus bar Anti-mistake contact terminal block |
|
Installation |
Terminal connection type |
|
Cable/U-type busbar/Pin-type busbar |
|
Maximum wire capacity |
Terminal size top/bottom for cable |
mm² |
25 |
|
AWG |
18-3 |
|||
Terminal size top/bottom for busbar |
mm² |
25 |
||
AWG |
18-3 |
|||
Torque |
N*m |
2 |
||
In-lbs |
18 |
|||
|
Tool |
18 |
Phillips screwdriver or flat-blade screwdriver |
|
|
Installation |
|
On DIN rail EN 60715 (35mm) by means of fast clip device |
|
|
Wiring method |
|
From top or bottom |