General
YCB7RL-100 series electromagnetic residual current operated circuit breaker is mainlysuitable for AC distribution networks with a rated working voltage of 230V or 400V at 50Hzand a rated current of 63A.Used for indirect contact protection of people,and can also beused to prevent fire hazards caused by insulation damage to circuits and equipment,resulting in ground fault currents.
Contact Us
YCB7RL-100 series electromagnetic residual current operated circuit breaker is mainly suitable for AC distribution networks with a rated working voltage of 230V or 400V at 50Hz and a rated current of 63A.Used for indirect contact protection of people,and can also be used to prevent fire hazards caused by insulation damage to circuits and equipment, resulting in ground fault currents.
Protection against the effects of sinusoidal alternating earth fault currents.The leakage protection feature does not require an auxiliary power supply.Not affected by voltage fluctuations in the power grid.
YCB7RL | 100 | 1P+N | 63 | 100mA | A Type | |
Mode | Shell grade current |
Pole | Rated current | Rated residua operating current |
Type | |
RCCB Electromagnetic |
100 | 1P+N 3P+N |
6 10 16 20 25 32 40 50 63 |
Default: 30mA 100mA 300mA |
Default:AC Type A Type |
Model | YCB7RL-100 | ||||
Electrical features |
Leakage type | Electromagnetic type | |||
Rated current In | A | 6,10,16,25,32,40,50,63,80,100 | |||
Type (wave form of the earth leakage sensed) | A,AC | ||||
Poles | P | 1P+N,3P+N | |||
Rated voltage Ue | V | 230/400 | |||
Insulation voltage Ui | V | 500 | |||
Rated frequency | Hz | 50/60 | |||
Rated breaking capacity Inc=I△c | A | 600,010,000 | |||
Rated impulse withstand voltage (1.2/50)Uimp | V | 6000 | |||
Dielectric test voltage at ind.Freq.for 1min | Kv | 2.5 | |||
Rated sensitivity I△n | A | 0.03,0.1,0.3 | |||
Rated residual making and breaking capacity lAm | A | 500(In≤40A);630(In=50A/63A);1000(In=80A/100A | |||
Pollution degree | 2 | ||||
Electrical life | t | 4000 | |||
Mechanical features |
Mechanical life | t | 8000 | ||
Protection degree | IP20 | ||||
Storage temperature | ℃ | -25~+70 | |||
Ambient temperature (with daily average≤35℃) | ℃ | -5~+40 | |||
Terminal connection type | Cable/Pin-type busbar/U-type busbar | ||||
Installation | Terminal size top /bottom for cable | mm² | 25/35 | ||
Terminal size top /bottom for busbar | AWG | 18-3/18-2 | |||
Tightening torque | mm² | 10/16 | |||
AWG | 18-8/18-5 | ||||
Mounting | N*m | 2.5 | |||
In-Ibs | 22 | ||||
Connection | On DIN rail EN 60715(35mm)by means of fast clip device | ||||
From top or bottom |