1. Personnel and fire protection
2. Cable and line protection against overload and short-circuits.
Selection
1. I∆n ≤ 30 mA: additional protection in the case of direct contact.
2. I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.
3. AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
Contact Us
1. Personnel and fire protection
2. Cable and line protection against overload and short-circuits.
1. I∆n ≤ 30 mA: additional protection in the case of direct contact.
2. I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.
3. AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
1. Personnel and fire protection
2. Cable and line protection against overload and short-circuits.
1. I∆n ≤ 30 mA: additional protection in the case of direct contact.
2. I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.
3. AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
Type | Tripping time | I△n(A) | Expected result | Note | |||||
I△n | 2I△n | 5I△n | 6I△n | ||||||
General | 63,80,100,125 | ≥0.03 | 0.1 | 0.07 | 0.04 | 0.04 | Minimum time for tripping | ||
Time delay | Time limit for not tripping | 0.06s | ≥0.03 | 0.3 | 0.2 | 0.15 | 0.15 | Minimum time for tripping | |
≥0.03 | 0.13 | 0.06 | 0.05 | 0.04 | Minimum time for not tripping | ||||
0.1s | ≥0.03 | 0.6 | 0.4 | 0.3 | 0.2 | Minimum time for tripping | |||
≥0.03 | 0.23 | 0.1 | 0.06 | 0.05 | Minimum time for not tripping |
Release
Type | Test current | Tripping time | Expected result |
C,D | 1.05In | t≤1h(In≤63A),t≤2h(In≤63A) | Not tripping |
C,D | 1.3In | t≤1h(In≤63A),t≤2h(In≤63A) | Tripping |
C,D | 2.55In | 1s<t<120s | Tripping |
C | 8In ×80% | t≤0.2s | Not tripping |
D | 12In ×80% | t≤0.2s | Not tripping |
C | 8In × 120% | t<0.2s | Tripping |
D | 12In × 120% | t<0.2s | Tripping |
Type | Standard | IEC/EN 60947-2 | |
Electrical features
Mechanical features |
Type (wave form of the earth leakage sensed) | AC | |
Thermo-magnetic release characteristic | (C)Ii=8In,(D)Ii=12In | ||
Rated current In | A | 63, 80, 100 | |
Poles | 1P+N, 2P, 3P, 3P+N, 4P | ||
Rated voltage Ue | V | 230/400 | |
Rated sensitivity IΔn | A | 0.03, 0.1, 0.3 | |
Rated short-circuit capacity lcn | A | 6000 | |
Break time under I△n | s | ≤0.1 | |
Rated impulsewithstand voltage (1.2/50)Uimp | V | 4000 | |
Dielectric TEST voltage at ind. Freq. for 1min | kV | 1.89 | |
Insulation voltage Ui | V | 500 | |
Pollution degree | 3 | ||
Electrical life | 1500 | ||
Mechanical life | 8500 | ||
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Ambient temperature(with daily average≤35℃) |
℃ | -5… +40 | |
Storage temperature | ℃ | -25… +70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 16~50 | |
AWG | 6-1/0 | ||
Terminal size top/bottom for busbar | mm² | 16~35 | |
AWG | 6-2 | ||
Tightening torque | N·m | 3.5 | |
In-Ibs. | 31 | ||
Mounting Connection | On DIN rail EN 60715 (35mm) by means of fast clip device From top |