YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
Picture
  • YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
  • YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
  • YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications
  • YCB7LE-125 Electronic RCBO Electronic Residual Current Breaker RCBO Electronic specifications and applications

YCB7LE-125 Electronic RCBO Electronic Residual ...

Function

1.  Personnel and fire protection

2.  Cable and line protection against overload and short-circuits.

Selection

1.  I∆n ≤ 30 mA: additional protection in the case of direct contact.

2.  I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.

3.  AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.

Contact Us

Product Details

YCB7LE-125 样本-23.11.18_00

 

Function

1.  Personnel and fire protection

2.  Cable and line protection against overload and short-circuits.

Selection

1.  I∆n ≤ 30 mA: additional protection in the case of direct contact.

2.  I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.

3.  AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.

Function

1.  Personnel and fire protection

2.  Cable and line protection against overload and short-circuits.

Selection

1.  I∆n ≤ 30 mA: additional protection in the case of direct contact.

2.  I∆n ≤300 mA: preventative fire protection in the case of ground fault currents.

3.  AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.

Release

Type Tripping time I△n(A) Expected result Note
I△n 2I△n 5I△n 6I△n
General 63,80,100,125 ≥0.03 0.1 0.07 0.04 0.04 Minimum time for tripping
Time delay Time limit for not tripping 0.06s ≥0.03 0.3 0.2 0.15 0.15 Minimum time for tripping
≥0.03 0.13 0.06 0.05 0.04 Minimum time for not tripping
0.1s ≥0.03 0.6 0.4 0.3 0.2 Minimum time for tripping
≥0.03 0.23 0.1 0.06 0.05 Minimum time for not tripping

 

Release

Type Test current Tripping time Expected result
C,D 1.05In t≤1h(In≤63A),t≤2h(In≤63A) Not tripping
C,D 1.3In t≤1h(In≤63A),t≤2h(In≤63A) Tripping
C,D 2.55In 1s<t<120s Tripping
C 8In ×80% t≤0.2s Not tripping
D 12In ×80% t≤0.2s Not tripping
C 8In × 120% t<0.2s Tripping
D 12In × 120% t<0.2s Tripping

Specifications

Type Standard   IEC/EN 60947-2
Electrical features 

 

 

 

 

 

 

Mechanical features

Type (wave form of the earth leakage sensed)   AC
Thermo-magnetic release characteristic   (C)Ii=8In,(D)Ii=12In
Rated current In A 63, 80, 100
Poles   1P+N, 2P, 3P, 3P+N, 4P
Rated voltage Ue V 230/400
Rated sensitivity IΔn A 0.03, 0.1, 0.3
Rated short-circuit capacity lcn A 6000
Break time under I△n s ≤0.1
Rated impulsewithstand voltage (1.2/50)Uimp V 4000
Dielectric TEST voltage at ind. Freq. for 1min kV 1.89
Insulation voltage Ui V 500
Pollution degree   3
Electrical life   1500
Mechanical life   8500
Contact position indicator   Yes
Protection degree   IP20

Ambient temperature(with daily average≤35℃)

-5… +40
Storage temperature -25… +70
Installation Terminal connection type   Cable/Pin-type busbar
Terminal size top/bottom for cable mm² 16~50
AWG 6-1/0
Terminal size top/bottom for busbar mm² 16~35
AWG 6-2
Tightening torque N·m 3.5
In-Ibs. 31
Mounting Connection   On DIN rail EN 60715 (35mm) by means of fast clip device From top

YCB7LE-125 样本-23.11.18_01