Type | Tripping sensitivity data | ||
AC | For residual sinusoidal alternating currents | 30mA | For personnel, material and fire protection, as well as for protection against direct contact |
A | For residual sinusoidal alternating currents and residual pulsating direct currents | 100mA | For providing protection against indirect contacts |
S | For selectivity, with time delay | 300mA | For providing fire protection in case of insulation faults |
Type | Standard | lEC/EN 61008-1 | |
Electrical features |
Leakage type | Electromagnetic type | |
Rated current In | A | 16, 25, 32, 40, 50, 63, 80, 100 | |
Type (wave form of the earth leakage sensed) | A, AC | ||
Poles | P | 2, 4 | |
Rated voltage Ue | V | 230/400 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity Inc=I△c | A | 6000A | |
Rated impulse withstand voltage (1.2/50) Uimp | V | 6000 | |
Dielectric test voltage at ind. Freq. for 1min | kV | 2.5 | |
Rated sensitivity IΔn | A | 0.03, 0.1, 0.3 | |
Rated residual making and breaking capacity I△m | A | 500(In≤40A); 630(In=50A/63A);1000(In=80A/100A) | |
Pollution degree | 2 | ||
Mechanical features | Electrical life | t | 4000 |
Mechanical life | t | 8000 | |
Protection degree | IP20 | ||
Storage temperature | ℃ | -25~+70 | |
Installation | Ambient temperature (with daily average≤35℃) | ℃ | -5~+40 |
Terminal connection type | Cable/Pin-type busbar | ||
Terminal size top / bottom for cable | mm2 | 25/35 | |
AWG | 18-3/18-2 | ||
Terminal size top / bottom for busbar | mm2 | 10月16日 | |
AWG | 18-8/18-5 | ||
Tightening torque | N*m | 2.5 | |
In-Ibs | 22 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |