Product Overview
Product Details
Data Download
Related Products
Contact Us
Type | Test current | Tripping time | Expected result | Type | Test current | Tripping time | Expected result |
B,C | 1.13In | t≤1h(In≤63A) | Not tripping | B | 3In | t≤0.1s | Not tripping |
1.13In | t≤2h(In>63A) | Tripping | |||||
C | 5In | t≤0.1s | |||||
B,C | 1.45In | t<1h(In≤63A) | Tripping | ||||
1.45In | t<2h(In>63A) | B | 5In | t<0.1s | Tripping | ||
B,C | 2.55In | 1s<t<60s(In≤32A) | |||||
C | 10In | t<0.1s | |||||
2.55In | 1s<t<120s(In>32A) |
Type | Standard | lEC/EN 60898-1 | |
Electrical features | Rated current ln | A | 6, 10, 16, 20, 25, 32 |
Poles | P | 1P+N | |
Rated voltage Ue | V | 230 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 3000 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind. Freq. for 1min | kV | 2 | |
Pollution degree | 2 | ||
Thermo-magnetic release characteristic | B, C | ||
Mechanical features | Electrical life | t | 4000 |
Mechanical life | t | 10000 | |
Protection degree | IP20 | ||
Reference temperature for setting of thermal element | ℃ | 30 | |
Ambient temperature | ℃ | -5~+40 | |
(with daily average≤35℃) | |||
Storage temperature | ℃ | -25~+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top / bottom for cable | mm2 | 16 | |
AWG | 5月18日 | ||
Terminal size top / bottom for busbar | mm2 | 10 | |
AWG | 5月18日 | ||
Tightening torque | N*m | 2 | |
In-Ibs | 18 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top or bottom |
1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln