Type | Test curren | Tripping time | Expected result | Type | Test current | Tripping time | Expected result |
B,C,D | 1.13In | t≤1h(In≤63A) | Not tripping | B | 3In | t≤0.1s | Not tripping |
1.13In | t≤2h(In>63A) | C | 5ln | t≤0.1s | |||
B,C,D | 1.45In | t<1h(In≤63A) | Tripping | D | 10ln | t≤0.1s | |
1.45ln | t<2h(In>63A) | B | 5ln | t<0.1s | Tripping | ||
B,C,D | 2.55In | 1s<t<60s(In≤32A) | Tripping | C | 10ln | t<0.1s | |
2.55ln | 1s<t<120s(In>32A) | D | 20ln | t<0.1s |
1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows: type B(3-5)ln, type C(5-10)ln, type D(10-20)ln
Type | Standard | IEC/EN 60898-1 | |
Electrical features | Rated current In | A | 1, 2, 3, 4, 6, 10, 16,20,25,32,40,50, 63 |
Poles | P | 1, 2, 3,4 | |
Rated voltage Ue | V | 230/400 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 4500 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind. Freq.for 1min | kV | 2 | |
Pollution degree | 2 | ||
Thermo-magnetic release characteristic | B, C,D | ||
Mechanical features | Electrical life | t | 6000 |
Mechanical life | t | 20000 | |
Protection degree | IP20 | ||
Reference temperature for setting of thermal element | ℃ | 30 | |
Ambient temperature(with daily average≤35℃) | ℃ | -5~+40 | |
Storage temperature | ℃ | -25~+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top / bottom for cable | mm2 | 25 | |
AWG | 18-3 | ||
Terminal size top / bottom for busbar | mm2 | 25 | |
AWG | 18-3 | ||
Tightening torque | N*m | 2 | |
In-1bs | 18 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top or bottom |