Product Overview
Product Details
Data Download
Related Products
Contact Us
VYC Type Center-mounted Vacuum Contactor-Fuse Combination Electrical Appliance is suitable for indoor switchgear equipment with a rated voltage of 3.6-12 kV and a three-phase AC frequency of 50 Hz.
This product is designed for places that require frequent circuit breaking and closing operations.
It can meet the user's requirements for frequent operations and has advantages such as long lifespan, stable operation, and reasonable functionality.
It is suitable for center-mounted switchgear cabinets with widths of 650mm and 800mm.
It is applied in various industrial and mining enterprises such as metallurgy, petrochemicals, and mining.
It is used to control and protect high-voltage motors, variable frequency drives, induction furnaces, and other load switching equipment.
Standard: IEC60470:1999.
Operating conditions
1. The ambient temperature is higher than +40℃ and not lower than -10℃ (storage and transportation are allowed at -30℃).
2. The altitude does not exceed 1500m.
3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average saturated vapor pressure is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa.
4. The earthquake intensity does not exceed 8 degrees.
5. Places without risk of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Technical data
Main specifictions
Number |
Item |
Unit |
Value |
|||
1 |
Rated voltage |
KV |
3.6 |
7.2 |
12 |
|
2 |
Rated insulation level |
Rated lightning impulse withstand voltage peak |
KV |
46 |
60 |
75 |
1min |
KV |
20 |
32 |
42 |
||
3 |
Rated current |
A |
400 |
315 |
160 |
|
4 |
Short-time withstand current |
KA |
4 |
|||
5 |
Short-term withstand current duration |
s |
4 |
|||
6 |
Rated peak withstand current |
KA |
10 |
|||
7 |
Rated short-circuit breaking current (fuse) |
KA |
50 |
|||
8 |
Rated transfer current |
A |
3200 |
|||
9 |
Rated switching current |
A |
3200 |
|||
10 |
Rated duty system |
|
Continuous duty |
|||
11 |
Use category |
|
AC3、AC4 |
|||
12 |
Operating frequency |
Times/h |
300 |
|||
13 |
Electrical life |
Times |
250000 |
|||
14 |
Mechanical life |
Times |
300000 |
Mechanical characteristic parameters after assembly adjustment of combined electrical appliances
Number |
Item |
Unit |
Value |
1 |
Contact spacing |
mm |
6±1 |
2 |
Contact stroke |
mm |
2.5±0.5 |
3 |
Opening time (rated voltage) |
ms |
≤100 |
4 |
Closing time (rated voltage) |
ms |
≤100 |
5 |
Contact bounce time on closing |
ms |
≤3 |
6 |
Different phases of three-phase closing |
ms |
≤2 |
7 |
Allowable cumulative thickness of wear for moving and static contacts. |
mm |
2.5 |
8 |
Main circuit resistance |
µΩ |
≤300 |
Opening and closing coil parameters
Number |
Item |
Unit |
Value |
|
1 |
Control circuit rated operating voltage |
V |
DAC/DC110 |
AC/DC220 |
2 |
Closing current |
A |
20 |
10 |
3 |
Holding current (electrical holding) |
A |
0.2 |
0.1 |
Structural features
1. Simplified transmission links,reduced energy consumption, and improved mechanical reliability.
2. The pole is formed through APG (Automatic Pressure Gelation) process, providing waterproof, dustproof, and dirt-resistant properties, enhancing operational reliability.
3. Electromagnetic operating mechanism with reliable closing operation and low power consumption during long-term operation.
4. Convenient assembly and maintenance.
Overall and mounting dimensions(mm)
The fuse should be selected to protect the motor, and the model to be used is XRNM1. Please refer to Figure for the external dimensions of the fuse.