VYC MV Vacuum Contactor
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

VYC MV Vacuum Contactor
Picture
  • VYC MV Vacuum Contactor
  • VYC MV Vacuum Contactor

VYC MV Vacuum Contactor

VYC Type Center-mounted Vacuum Contactor-Fuse Combination Electrical Appliance is suitable for indoor switchgear equipment
with a rated voltage of 3.6-12 kV and a three-phase AC frequency of 50 Hz.

Contact Us

Product Details

VYC Type Center-mounted Vacuum Contactor-Fuse Combination Electrical Appliance is suitable for indoor switchgear equipment with a rated voltage of 3.6-12 kV and a three-phase AC frequency of 50 Hz.
This product is designed for places that require frequent circuit breaking and closing operations.
It can meet the user's requirements for frequent operations and has advantages such as long lifespan, stable operation, and reasonable functionality.
It is suitable for center-mounted switchgear cabinets with widths of 650mm and 800mm.
It is applied in various industrial and mining enterprises such as metallurgy, petrochemicals, and mining.
It is used to control and protect high-voltage motors, variable frequency drives, induction furnaces, and other load switching equipment.
Standard: IEC60470:1999.

Operating conditions

1. The ambient temperature is higher than +40℃ and not lower than -10℃ (storage and transportation are allowed at -30℃).

2. The altitude does not exceed 1500m.

3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average saturated vapor pressure is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa.

4. The earthquake intensity does not exceed 8 degrees.

5. Places without risk of fire, explosion, serious pollution, chemical corrosion and severe vibration.

Technical data

Main specifictions

Number

Item

Unit

Value

1

Rated voltage

KV

3.6

7.2

12

2

Rated insulation level

Rated lightning impulse withstand voltage peak

KV

46

60

75

1min

KV

20

32

42

3

Rated current

A

400

315

160

4

Short-time withstand current

KA

4

5

Short-term withstand current duration

s

4

6

Rated peak withstand current

KA

10

7

Rated short-circuit breaking current (fuse)

KA

50

8

Rated transfer current

A

3200

9

Rated switching current

A

3200

10

Rated duty system

 

Continuous duty

11

Use category

 

AC3、AC4

12

Operating frequency

Times/h

300

13

Electrical life

Times

250000

14

Mechanical life

Times

300000

Mechanical characteristic parameters after assembly adjustment of combined electrical appliances

Number

Item

Unit

Value

1

Contact spacing

mm

6±1

2

Contact stroke

mm

2.5±0.5

3

Opening time (rated voltage)

ms

≤100

4

Closing time (rated voltage)

ms

≤100

5

Contact bounce time on closing

ms

≤3

6

Different phases of three-phase closing

ms

≤2

7

Allowable cumulative thickness of wear for moving and static contacts.

mm

2.5

8

Main circuit resistance

µΩ

≤300

Opening and closing coil parameters

Number

Item

Unit

Value

1

Control circuit rated operating voltage

V

DAC/DC110

AC/DC220

2

Closing current

A

20

10

3

Holding current (electrical holding)

A

0.2

0.1

Structural features

1. Simplified transmission links,reduced energy consumption, and improved mechanical reliability.

2. The  pole  is  formed through APG  (Automatic  Pressure  Gelation)  process, providing waterproof,  dustproof,  and  dirt-resistant  properties,  enhancing operational reliability.

3. Electromagnetic operating mechanism with reliable closing operation and low power consumption during long-term operation.

4. Convenient assembly and maintenance.

Overall and mounting dimensions(mm)

 
Overall and mounting dimensions fuse

 

The fuse should be selected to protect the motor, and the model to be used is XRNM1. Please refer to Figure  for the external dimensions of the fuse.

Write your message here and send it to us

Related Products