SZ□-35KV Oil-Immersed Transformer.
Picture
  • SZ□-35KV Oil-Immersed Transformer.
  • SZ□-35KV Oil-Immersed Transformer.

SZ□-35KV Oil-Immersed Transformer.

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

SZ□-35KV Series On-load Voltage Regulating Transformer

This kind of product is applied to power system of three-phase, 50Hz as well as 35kV and below,is the main transformer equipment of medium and small-sized transformer substation, supplies power distribution, power and illumination for the industry and agriculture.

The company introduces in domestic and overseas advanced technique, adopts the latest material and optimizes design, which enables the product structure more reasonable, and greatly improves the product electric strength, mechanical strength and heat- sinking capability.

Standard

0

Operating conditions

1. Altitude: ≤1000m.

2. Ambient temperature: the highest temperature +40℃, the highest monthly average temperature +30℃; The highest yearly average temperature +20℃ .

3. Installation environment: inclination of installation place<3°, no obvious dirt and corrosive or flammable gas.

Features

1. Iron core:

The iron core is made of high-quality cold-rolled silicon steel sheet, and adopts various forms such as fully biased multi-stage j oints, without punch holes,wind cores, etc., and clamp them with stainless steel stays and epoxy glass tapes.

2. Coil:

The conductor is made of high-quality oxygen-free copper enameled wire or paper-wrapped flat copper wire, and the coil is made

of drum type, spiral type, improved spiral type, continuous type, staggered type and other types.

3. Oil tank:

The oil tank is barrel type or shielded type, and the heat dissipation element adopts corrugated plate or electroplating radiator.The transformer is not equipped with a trolley, but a base that conforms to the national standard gauge is welded on the bottom of the box for your convenience.

4. Safety protection device:

According to national standards and user requirements, the transformer can be equipped with the following safety protection devices:pressure relief valve, gas relay, signal thermometer, oil filter, oil conservator, oil sample valve, etc.

SZ9-35KV technical data

Rated
capacity
(kVA)
Voltage combination Connection symbol No-load loss(W) Load   loss(W) No-load
current
(%)
Short circuit
impedance
(%)
(kV)H.V Tapping range of high voltage L.V
(kV)
2000 35 ±3×2.5 6.3
10.5
Yd11 2900 20200 0.9 6.5
2500 3400 22700 0.9
3150 35~38.5 4100 26000 0.8 7
4000 4900 30700 0.8
5000 5800 36000 0.75
6300 7000 38700 0.75 8
8000 6.3
6.6
10.5
Ynd11 9900 43000 0.7
10000 11600 50600 0.7
12500 13800 59900 0.7
16000 16200 73000 0.7
20000 19500 84600 0.7
25000 22500 100200 0.7 10
31500 26400 124000 0.6

SZ11-35KV technical data

Rated
capacity
(kVA)
Voltage combination Connection symbol No-load loss(W) Load   loss(W) No-load
current
(%)
Short circuit
impedance
(%)
(kV)H.V Tapping range of high voltage L.V
(kV)
2000 35 ±3×2.5 6.3
10.5
Yd11 2300 19240 0.8 6.5
2500 2720 20640 0.8
3150 35~38.5 3230 24710 0.72 7
4000 3870 29160 0.72
5000 4640 31200 0.68
6300 6.3
6.6
10.5
Ynd11 5630 36770 0.68 7.5
8000 7870 40610 0.6
10000 9280 48050 0.6
12500 10940 56860 0.56 8
16000 13170 70320 0.54
20000 15570 82780 0.54

SZ13-35KV technical data

Rated capacity
(kVA)
Voltage combination Connected group label No-load loss(W) Load
loss(W)
No-load
current
(%)
Short circuit
impedance
(%)
High voltage(kv) Tapping range Low voltage
2000 35 ±3×2.5 6.3
10.5
Yd11 2300 19200 0.5 6.5
2500 2720 20600 0.5
3150 35~38.5 3230 24700 0.5 7
4000 3870 29100 0.5
5000 4640 34200 0.5
6300 5630 36700 0.5 8
8000 6.3
6.6
10.5
Ynd11 7870 40600 0.4
10000 9280 48000 0.4
12500 1090 56800 0.35
16000 1310 70300 0.35
20000 1550 82100 0.35
25000 1830 97800 0.3 10
31500 2180 716000 0.3

Overall and mounting dimensions(mm)

0

Note :outline dimension is designed according to requirements.

 

 

 