SG(B)10 Dry-type Transformer

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

SG(B)10 Insulated Three-phase Dry-type Transformer

The non-encapsulated coil three-phase dry type power transformer that adopt UL certificated NOMEX insulation system, with advantages of safe, reliable, energy saving, fireproof, explosion resistant, simple maintaining and so on. It has superior design, reasonable structure, elegant appearance, and its

main performance index is superior to domestic standard, such as local discharge level, no-load loss, load loss,noise and capability of operating in serious humid environment, it can be installed in humid environment like places near lake, sea or river, also suitable for areas that require high fireproof

capability and high load, such as high-rise, airport, station,dock,underground railway,hospital,electric power plant,metallurgy industry,shopping center, residential area, petrochemical industry, nuclear power station,nuclear submarine, etc.

Standard

0

Operating conditions

1. Ambient temperature: -50℃~+50℃ .

2. Altitude:≤1000m.

3. Other requirements that are beyond the stipulation range of this technical manual,please negotiate with our technical department and indicate out when placing an order.

Features

1. The elaborate designed coil structure and vacuum immersed treatment enable SG(B)10 transformer operates without local.

discharging,and no crack performance will be find during the whole service life, and its insulation level will be kept as good as beginning.

2. The high voltage part adopts continuous wire winding, LV foil winding, vacuum immersed, curing processed and high strength ceramics supporting, with fine withstand capability to paroxysmal short-circuit current.

3. Flame resisting, flameproof, nontoxic, self-extinguishing, fireproof.

4. When burn SG(B)10 transformer in high temperature and open fire, almost no fume will by produced. 5. Insulation of the transformer is H grade (180℃).

6. The insulation layer is very thin, with strong short-time over load capability,needless of forced cooling, can be overloaded for 120% for long term and 140% for 3 hours. As this kind of insulation material has elasticity and will not be aged,it can be full loaded at

once under ±50℃ .

SG(B)10 series of non-encapsulated coil three-phase dry type power transformer main technical parameters

1. Voltage grade:high voltage (kV): 3, 6, 6.3, 6.6, 10, 10.5, 11;Low voltage:0.4, 0.69.

2. High voltage tap range:±5% or ±2×2.5%.

3. Mark of joint group:Yyn0 or Dyn11.

Model and
capacity
(kVA)
No-load loss(W) Load loss(W)(145℃) No-load current(%) Sound level(LPA)dB Short circuit
impedance
(%)
Body
weight
(kg)
Enterprise standard National standard Enterprise standard National standard Enterprise standard National standard Enterprise standard National standard
SG(B)10-100/10 405 510 1880 2550 2.4 2.4 40 55 4 590
SG(B)10-160/10 560 700 2550 3650 2 2 42 58 4 870
SG(B)10-200/10 660 820 3100 4680 2 2 42 58 4 970
SG(B)10-250/10 760 950 3600 5500 1.8 2 44 58 4 1160
SG(B)10-315/10 880 1100 4600 6600 1.8 1.8 46 60 4 1350
SG(B)10-400/10 1040 1300 5400 7800 1.8 1.8 46 60 4 1580
SG(B)10-500/10 1200 1500 6600 9350 1.8 1.8 47 62 4 1830
SG(B)10-630/10 1340 1680 7900 11500 1.6 1.6 47 62 6 2060
SG(B)10-800/10 1690 2120 9500 13600 1.3 1.6 48 63 6 2450
SG(B)10-1000/10 1980 2480 11400 15700 1.3 1.4 48 63 6 2910
SG(B)10-1250/10 2380 2980 12500 18400 1.3 1.4 49 65 6 3190
SG(B)10-1600/10 2730 3420 13900 21300 1.3 1.4 50 66 6 4160
SG(B)10-2000/10 3320 4150 17500 15000 1.2 1.2 50 66 6 4860
SG(B)10-2500/10 4000 5000 20300 29100 1.2 1.2 51 67 6 5860

Outline size list

Model and capacity
(kVA)
Non-enclosed type
(without protective enclosure)
m n Non-enclosed type
(without protective enclosure)
m n
L H B L H B
SG(B)10-100/10 940 920 500 660 400 1340 1150 800 660 400
SG(B)10-160/10 940 960 500 660 400 1340 1150 800 660 400
SG(B)10-200/10 1100 1050 550 660 450 1500 1280 900 660 450
SG(B)10-250/10 1120 1120 550 660 450 1500 1280 900 660 450
SG(B)10-315/10 1190 1210 860 660 660 1700 1460 1000 660 660
SG(B)10-400/10 1300 1330 860 820 660 1700 1460 1000 820 660
SG(B)10-500/10 1330 1410 860 820 660 1900 1610 1000 820 660
SG(B)10-630/10 1450 1365 860 820 660 1900 1610 1000 820 660
SG(B)10-800/10 1500 1480 1020 820 820 2000 1770 1100 820 820
SG(B)10-1000/10 1590 1570 1020 820 820 2000 1770 1100 820 820
SG(B)10-1250/10 1610 1700 1270 1070 1070 2100 2130 1270 1070 1070
SG(B)10-1600/10 1660 1770 1270 1070 1070 2100 2130 1270 1070 1070
SG(B)10-2000/10 1700 1930 1270 1070 1070 2100 2130 1270 1070 1070

Note:The dimensions and weights provided are only for reference in design and selection.

The final size and weight are subject to our prodect drawings.

 Overall and mounting dimensions(mm)

Size drawing of SG(B)10-100~400kVA                            Size drawing of SG(B)10-500~2500kVA

0

Note:the outline dimensions and track gauge dimensions covered in the catalog are only for reference.

welcome to contact us for accurate dimensions

Outline diagram of standard side coiling out of SG(B)10 type non-encapsulated coil power transformer

0

Outline diagram of IP20 of SG(B)10 type non-encapsulated coil power transformer (HS1)

0

Outline diagram of IP20 of SG(B)10 type non-encapsulated coil power transformer (HS2)

0

Outline diagram of IP20 of SG(B)10 type non-encapsulated coil power transformer (HS3)

0

Diagram of LV terminal

0

 

 

 

 