SC(B)□ Series Dry-type Transformer
Picture
  • SC(B)□ Series Dry-type Transformer
  • SC(B)□ Series Dry-type Transformer

SC(B)□ Series Dry-type Transformer

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

SC(B)口 Series Epoxy Resin Dry-type Transformer

The SC (B) series epoxy resin dry type transformers have the advantages of flame retardant, fireproof, explosion-proof, maintenance free, and small size due to their coils being encapsulated with epoxy resin. They can be directly installed in load centers and are widely used in power transmission and

transformation systems, as important places as commercial residences, public buildings, airports, as well as in harsh environments like subways, smelters, ships, and marine drilling.

Standard:IEC60076-1, IEC60076-11.

Selection

0

 

Operating conditions

1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25℃ .

2. Average temperature of the hottest month:+30℃, average temperature in the hottest year:+20℃ .

3. Altitude not exceeding 1000m.

4. The waveform of the power supply voltage is similar to a sine wave.

5. The three-phase supply voltage should be approximately symmetrical.

6. The relative humidity of the surrounding air should be lower than 93%.

7. And there should be no water droplets on the surface of the coil.

8. Where to use: indoors or outdoors.

 Features

1. The carefully designed coil structure and vacuum immersion treatment ensure that the SG (B) 10 transformer operates without.

partial discharge and will not exhibit crack performance throughout its service life. Its insulation level will remain in good condition as before.

2. The high-voltage part adopts continuous wire winding, low-voltage foil winding, vacuum immersion, curing treatment, and high-strength ceramic support, which has good resistance to sudden short circuit currents.

3. Flame retardant,explosion-proof, non-toxic, self-extinguishing, and fireproof.

4. The SG (B) 10 transformer produces almost no smoke when burned in a high-temperature open flame 5. The insulation level of the transformer is Class H (180℃).

6. The insulation layer is very thin, with strong short-term overload capacity, without the need for forced cooling, and can overload by 120% for long term use, 140% lasting for 3 hours. Due to its elasticity and non aging properties, this insulation material can be fully loaded at one time at ± 50℃ .

 

1
2
3
4
5
6

Structure

■ Iron core:

● The iron core is made of high-quality oriented cold-rolled silicon steel sheet, with a laminated

structure of 45° full oblique seam, and the core column is bound with insulating tape.

● The surface of the iron core is sealed with insulating resin paint to prevent moisture and

rust, and the clamps and fasteners are surface-treated to prevent rust.

■  Low voltage copper foil coil:

●  The  low-voltage  winding  is  wound  with  high-quality  copper  foil,

so  that zero  axial short-circuit  stress  can  be  achieved  in  the  case  of

short  circuit.  The  interlayer  and winding end are insulated with

thermosetting epoxy prepreg cloth. The whole winding is

placed  in  the oven. After  heating, the winding  is  aggregated

into  a  solid whole. Scientific  and  reasonable  design  and

pouring  process  make  the  product  partial discharge less,

noise lower, and heat dissipation capacity strong.

High voltage winding:

●  The high-voltage winding adopts enamelled copper wire or film-coated copper

wire, and glass fiber and epoxy resin composite material are used for insulation.

Its expansion coefficient is similar to that of copper conductor, and it has good impact

resistance, temperature change resistance, and crack resistance. All components of glass

fiber and epoxy resin are self-

extinguishing, flame retardant and non-polluting.

Epoxy resin has good insulation properties and is especially suitable for making high-voltage coils.

Temperature control device and air cooling system:

●  The temperature control device  has the functions of failure alarm,

over-temperature alarm,  over-temperature  trip,  automatic/manual

start  and  stop  of  the  fan,  and  is connected to the computer through the RS485 interface

for centralized monitoring and control.At the same time, it also has the function

of "black gate", which can record the winding temperature of the transformer when it is powered off.

●  The  air-cooling  system adopts a  cross-flow top-blowing cooling fan, which

has the characteristics of low noise, high wind pressure, and beautiful appearance.

It can run for a long time under the condition of forced air cooling at 125% of the rated load.

■  Shell:

●  Protect the shell and provide further safety protection

for the transformer,with protection levels such as IP20, IP23, etc.

●  The shell materials include cold-rolled steel plate,

stainless steel plate, aluminum alloy, etc. for users to choose from.

 

Structure

■ The factory configuration of SCB without protective shell (IP00) is as follows

● 4 bi-directional flat wheels (when requested by the customer)

● 4 lugs

● Towing holes on the base

● 2 grounding points

● 1 nameplate

● 2 "Electric Hazard" warning signs

● No load voltage regulating tap, operated when the transformer is powered off, to adapt

the transformer to the actual supply voltage

● High voltage side connecting rod with connecting wire from above

● Low-voltage outgoing busbar with upward outlet

The factory configuration of SCB with IP21, IP23 metal protective shell is as follows

All contents mentioned above for SCB without protective casing (Ip00)

● 1 set of IP21 metal protective housing, standard anti-corrosion protection

SCB9-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
220 750 2.4 4 700 350 620 250
50 310 1060 2.4 710 350 635 295
80 420 1460 1.8 860 730 780 430
100 450 1670 1.8 940 710 795 520
125 530 1960 1.6 1000 710 860 670
160 610 2250 1.6 1080 710 1020 840
200 700 2680 1.4 1100 710 1060 960
250 810 2920 1.4 1150 710 1100 1120
315 990 3670 1.2 1150 770 1125 1230
400 1100 4220 1.2 1190 870 1175 1485
500 1310 5170 1.2 1230 870 1265 1580
630 1510 6220 1 1465 870 1245 1840
630 1460 6310 1 6 1465 870 1245 1840
800 1710 7360 1 1420 870 1395 2135
1000 1990 8610 1 1460 870 1420 2500
1250 2350 10260 1 1580 970 1485 2970
1600 2760 12400 1 1640 1120 1715 3900
2000 3400 15300 0.8 1780 1120 1710 4225
2500 4000 18180 0.8 1850 1120 1770 4790

Overall and mounting dimensions(mm)

0

Note:The dimensions and weights provided are only for reference in design and selection. The final size and weight are subject to our prodect drawings.

SCB10-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
190 710 2 4 580 450 650 300
50 270 1000 2 600 450 650 380
80 370 1380 1.5 880 500 800 470
100 400 1570 1.5 970 500 820 560
125 470 1850 1.3 970 500 860 650
160 540 2130 1.3 980 650 950 780
200 620 2530 1.1 1000 650 970 880
250 720 2760 1.1 1040 760 1070 1030
315 880 3470 1.0 1100 760 1110 1250
400 980 3990 1.0 1170 760 1235 1400
500 1160 4880 1.0 1190 760 1250 1600
630 1340 5880 0.85 1220 760 1250 1900
630 1300 5960 0.85 6 1220 760 1250 1900
800 1520 6960 0.85 1330 760 1330 2580
1000 1770 8130 0.85 1350 920 1450 2850
1250 2090 9690 0.85 1440 920 1550 3200
1600 2450 11700 0.85 1510 1170 1620 3800
2000 3060 14400 0.7 1530 1170 1785 4280
2500 3600 17100 0.7 1560 1170 1930 5250

Overall and mounting dimensions(mm)

1

Note:The dimensions and weights provided are only for reference in design and selection. The final size and weight are subject to our prodect drawings.

SCB11-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
170 710 2.3 4 955 750 840 270
50 240 1000 2.2 970 750 860 340
80 330 1380 1.7 1015 750 925 460
100 360 1570 1.7 1030 750 960 530
125 420 1850 1.5 1060 750 1000 605
160 480 2130 1.5 1090 900 1045 730
200 550 2530 1.3 1105 900 1080 825
250 640 2760 1.3 1180 900 1125 1010
315 790 3470 1.1 1225 900 1140 1165
400 880 3990 1.1 1330 900 1195 1490
500 1040 4880 1.1 1345 900 1255 1650
630 1200 5880 0.9 1540 1150 1175 1915
630 1170 5960 0.9 1540 1150 1175 1915
800 1360 6960 0.9 6 1600 1150 1220 2305
1000 1590 8130 0.9 1645 1150 1285 2690
1250 1880 9690 0.9 1705 1150 1345 3225
1600 2200 11700 0.9 1765 1150 1405 3805
2000 2740 14400 0.7 1840 1150 1475 4435
2500 3240 17100 0.7 1900 1150 1560 5300
1600 2200 12900 0.9 8 1765 1150 1405 3805
2000 2740 15900 0.7 1840 1150 1475 4435
2500 3240 18800 0.7 1900 1150 1560 5300

Overall and mounting dimensions(mm)

2

Note:The dimensions and weights provided are only for reference in design and selection. The final size and weight are subject to our prodect drawings.

SCB12-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
150 710 2.3 4 955 750 840 270
50 215 1000 2.2 970 750 860 340
80 295 1380 1.7 1015 750 925 460
100 320 1570 1.7 1030 750 960 530
125 375 1850 1.5 1060 750 1000 605
160 430 2130 1.5 1090 900 1045 730
200 495 2530 1.3 1105 900 1080 825
250 575 2760 1.3 1180 900 1125 1010
315 705 3470 1.1 1225 900 1140 1165
400 785 3990 1.1 1330 900 1195 1490
500 930 4880 1.1 1345 900 1255 1650
630 1070 5880 0.9 1540 1150 1175 1915
630 1040 5960 0.9 1540 1150 1175 1915
800 1210 6960 0.9 6 1600 1150 1220 2305
1000 1410 8130 0.9 1645 1150 1285 2690
1250 1670 9690 0.9 1705 1150 1345 3225
1600 1960 11700 0.9 1765 1150 1405 3805
2000 2440 14400 0.7 1840 1150 1475 4435
2500 2880 17100 0.7 1900 1150 1560 5300
1600 1960 12900 0.9 8 1765 1150 1405 3805
2000 2440 15900 0.7 1840 1150 1475 4435
2500 2880 18800 0.7 1900 1150 1560 5300

Overall and mounting dimensions(mm)

3

Note:The dimensions and weights provided are only for reference in design and selection. The final size and weight are subject to our prodect drawings.

 

SCB12-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
150 710 2.3 4 955 750 840 270
50 215 1000 2.2 970 750 860 340
80 295 1380 1.7 1015 750 925 460
100 320 1570 1.7 1030 750 960 530
125 375 1850 1.5 1060 750 1000 605
160 430 2130 1.5 1090 900 1045 730
200 495 2530 1.3 1105 900 1080 825
250 575 2760 1.3 1180 900 1125 1010
315 705 3470 1.1 1225 900 1140 1165
400 785 3990 1.1 1330 900 1195 1490
500 930 4880 1.1 1345 900 1255 1650
630 1070 5880 0.9 1540 1150 1175 1915
630 1040 5960 0.9 1540 1150 1175 1915
800 1210 6960 0.9 6 1600 1150 1220 2305
1000 1410 8130 0.9 1645 1150 1285 2690
1250 1670 9690 0.9 1705 1150 1345 3225
1600 1960 11700 0.9 1765 1150 1405 3805
2000 2440 14400 0.7 1840 1150 1475 4435
2500 2880 17100 0.7 1900 1150 1560 5300
1600 1960 12900 0.9 8 1765 1150 1405 3805
2000 2440 15900 0.7 1840 1150 1475 4435
2500 2880 18800 0.7 1900 1150 1560 5300

Overall and mounting dimensions(mm)

4

Note:The dimensions and weights provided are only for reference in design and selection.

The final size and weight are subject to our prodect drawings.

SCB18-30~2500/10KV technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
30 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Dyn11
Yyn0
Dyn5
105 640 2 4 590 560 780 /
50 155 900 2 590 545 870 /
80 210 1240 1.5 720 620 845 /
100 230 1415 1.5 840 610 1005 /
125 270 1665 1.3 850 750 1010 /
160 310 1915 1.3 870 790 1010 /
200 360 2275 1.1 900 740 1020 /
250 415 2485 1.1 900 750 1060 /
315 510 3125 1 990 755 1110 /
400 570 3590 1 1020 780 1160 /
500 670 4390 1 1050 820 1150 /
630 775 5290 0.85 1240 890 1150 /
630 750 5365 0.85 6 1290 940 1100 /
800 875 6265 0.85 1300 920 1160 /
1000 1020 7315 0.85 1360 895 1195 /
1250 1205 8720 0.85 1420 920 1255 /
1600 1415 10555 0.85 1500 1010 1360 /
2000 1760 13005 0.7 1540 1010 1415 /
2000 2080 15445 0.7 1700 1120 1415 /

Overall and mounting dimensions(mm)

5

Note:The dimensions and weights provided are only for reference in design and selection.

The final size and weight are subject to our prodect drawings.

SCB-30~2500 technical data

Rated
capacity
(KVA)
Voltage combination Connection group label No-load loss(W) Load   Loss(w) 120℃ No-load
current
(%)
Short circuit  impedance(%) Dimensions Total
weight
(kg)
High
voltage
(KV)
Tapping
range
Low
voltage
(KV)
L W H
50 20
10
6
±5
±2×2.5
0.4 Dyn11
Yyn0
Dyn5
180 1500 1.8 4 1120 850 1000 /
100 252 1800 1.6 1160 850 1100 /
160 360 2600 1.4 1200 900 1150 /
250 468 3400 1.2 1250 900 1200 /
400 675 4500 1 1290 900 1200 /
630 990 7100 0.9 1340 900 1540 /
800 1170 8000 0.9 6 1400 900 1640 /
1000 1395 9000 0.8 1500 1200 1650 /
1250 1620 11000 0.8 1540 1200 1750 /
1600 1980 13000 0.8 1620 1200 1920 /
2000 2340 16000 0.6 1770 1200 2000 /
2500 2790 19000 0.6 1800 1200 2210 /
3150 3420 22000 0.6 1830 1200 2200 /

Overall and mounting dimensions(mm)

6

Note:The dimensions and weights provided are only for reference in design and selection.

The final size and weight are subject to our prodect drawings.

Carry

● The transformer is equipped with safe handling devices.

●  For transformers without enclosures and transformers with top door openings, use the four lifting lugs of the transformer for lifting (must be lifted vertically, not diagonally);

For transformers with 2 lifting lugs in the center of the top of the casing, use 2 lifting lugs for lifting. The angle formed by the

sling should not exceed 60° .

●  Firstly, the forking capacity of the forklift should be checked. If appropriate, the fork arm should be inserted into the base channel steel after removing the rollers.

●  Pulling and moving the transformer should be carried out from the base. For this purpose, holes with a diameter of 27 mm are made on each side of the base. Dragging is

possible in two directions: the axis of the base and the direction perpendicular to this axis.

7

Figure 1- Lifting with a sling or forklift                                           Figure 2- Installation of the roller

Write your message here and send it to us