SBH15 Series High Voltage Oil Immersed Power Transformer with Oil Insulation current transformer
SBH15 Series High Voltage Oil Immersed Power Transformer with Oil Insulation current transformer
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

SBH15 Series High Voltage Oil Immersed Power Transformer with Oil Insulation current transformer
Picture
  • SBH15 Series High Voltage Oil Immersed Power Transformer with Oil Insulation current transformer
  • SBH15 Series High Voltage Oil Immersed Power Transformer with Oil Insulation current transformer

SBH15 Series High Voltage Oil Immersed Power Tr...

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Contact Us

Product Details

SBH15 Series Amorphous Alloy Oil-immersed Transformer

SBH15 series amorphous transformer is a low loss, high energy efficiency oil-immersed transformer. The iron core of this product is wound from amorphous alloystrip.

Its no-load loss is more than 70%,lower than that of traditional transformers using silicon steel sheets as iron cores. It is a new generation of energy-saving, safe, green and environmentally friendly high-tech products.

And it can replace ordinary oil-immersed transformers, and is mainly suitable for high-rise buildings, commercial centers, infrastructure, industrial and mining enterprises, power plants, etc.

Standard:IEC60076-1, IEC60076-2, IEC60076-3, IEC60076-5, IEC60076-10.

Standard

1

Operating conditions

1. Ambient temperature: maximum temperature:+40°C, minimum temperature:-25℃ .
2. Average temperature of the hottest month:+30℃, average temperature in the hottest year:+20℃ .
3. Altitude not exceeding 1000m.
4. The waveform of the power supply voltage is similar to a sine wave.
5. The three-phase supply voltage should be approximately symmetrical.
6. The total harmonic content of the load current shall not exceed 5% of the rated current.
7. Where to use: indoors or outdoors.

Features

1. The product has the characteristics of high efficiency, low loss, low noise, etc.
2. High mechanical strength, balanced ampere-turn distribution, and strong short-circuit resistance.
3. Low no-load and load loss.
4. Small size, reliable operation, long service life, and maintenance free.

Structure

1

■  Iron core:

 The iron core is made of high-quality, high-performance, high-permeability silicon steel sheet, with low no-load loss.

1

 Other configuration:

● Equipped with and  relief valve,signal thermometer, gas  relay, ensures the safe operation of the transformer.

2

■  Positioning structure:

● The  product  body  has  added a  positioning  structure to  prevent  displacement during  transportation,  and  all  fasteners  are  equipped  with  fastening  nuts  to ensure  that  the  fasteners  do  not  loosen  during  long-term  operation  of  the product.

3

■  Fully sealed structure:

 The product is a fully sealed structure. The vacuum oil filling process is used for

the  transformer packaging,  which   completely  removes  the   moisture  of  the transformer,

ensures the  isolation  of the transformer  oil from the  outside  air, prevents

the  aging  of  the  oil,  and  improves  the  operation  reliability  of  the transformer.

 

 Oil tank:

 The transformer oil tank is composed of corrugated walls, The surface is sprayed

with  dust  and  the paint  film   is  firm,With  cooling  function,The  elasticity

of corrugated heat sink can compensate for the volume change of transformer

oil caused by temperature rise and fall, so there is no oil conservator

in the fully sealed transformer, reducing the overall height of the transformer.

SBH15 technical data

Rated
capacity
(KVA)
Voltage combination Low
voltage
(KV)
Connection
group
label
No-load loss(W) Load   loss(W) No-load
current
(%)
Short circuit
impedance
(%)
Dimensions Gouge
Horizontal
and Vertical
(a×b)
Total
weight
(kg)
High
voltage
(KV)
Tapping
range
L W H
30 6
6.3
6.6
10
10.5
11
±2 ×2.5
±5
0.4 Dyn11 33 630/600 1.5 4 950 620 1040 400×550 680
50 43 910/870 1.2 1060 7770 1070 400×660 890
63 50 1090/1040 1.1 1240 920 1200 550×870 1030
80 60 1310/1250 1 1240 920 1200 550×870 1170
100 75 1580/1500 0.9 1280 920 1200 550×870 1230
125 85 1890/1800 0.8 1320 940 1200 660×870 1400
160 100 2310/2200 0.6 1340 940 1200 660×870 1470
200 120 2730/2600 0.6 1340 940 1200 660×870 1540
250 140 3200/3050 0.6 1370 1120 1260 660×1070 1720
315 170 3830/3650 0.5 1370 1120 1330 660×1070 2000
400 200 4520/4300 0.5 1520 1190 1360 820×1070 2400
500 240 5410/5150 0.5 1890 1220 1470 820×1070 2950
630 320 6200 0.3 4.5 1960 1210 1550 820×1070 3500
800 380 7500 0.3 2030 13110 1560 820×1070 4100
1000 450 10300 0.3 2570 1350 1800 820×1070 5550
1250 530 12000 0.2 2080 1540 1970 1070×1475 6215
1600 630 14500 0.2 2560 1690 2380 1070×1475 6600
2000 750 18300 0.2 5 2660 1800 2400 1070×1475 6950
2500 900 21200 0.2 2720 1800 2460 1070×1475 7260

Note 1 :for transformers with rated capacity of 500kVA and below,the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to theYyn0 coupling

group.

Note 2:when the average annual load rate of the transformer is belween 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.

Overall and mounting dimensions(mm)

1

Note:The dimensions and weights provided are only for reference in design and selection.the final size and weight are subject to our prodect drawings.

 

 

Write your message here and send it to us

Related Products