Product Overview
Product Details
Data Download
Related Products
KYN28A-12 indoor metal clad movable switchgear is a complete power distribution device for 3.6kV~12KV,3 phase AC 50/60Hz,single bus sectionalized system.It is mainly used for power transmissionof middle/smallgenerators in power plants,powerreceiving,transmission for substations in power distribution and power system of factories,mines and enterprises etc.so as tocontrol,protectand monitor the system.
Standard.IEC62271-200
Contact Us
KYN28A-12 indoor metal clad movable switchgear is a complete power distribution device for 3.6kV~12KV, 3 phase AC 50/60Hz, single bus sectionalized system. lt is mainly used for power transmission
of middle/smallgenerators in power plants, power receiving, transmission for substations in power distribution and power system of factories, mines and enterprises etc. so as to control, protect and monitor the system.
Standard: IEC62271-200
1. Ambient air temperature: -15℃ ~+40℃ .
2. Altitude: ≤1000m.
3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa.
4. Earthquake intensity: ≤magnitude 8.
5. Applicable in the places without corrosive and flammable gas and water vapor.
6. Used in place without frequently intense vibrant. Note: Customized products are available.
1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment, andisassembled by bolts or rivets. The structure is fully assembled.
2. The switchgear has various functions to prevent misoperation, including preventing the load-bearing handcart from moving, preventing the live closing and grounding
3. The switchgear is equipped with high-performance VS1 series medium-voltage AC vacuum circuit breakers and solid-sealed vacuum circuit breakers.
4. The busbar adopts heat-shrinkable insulation materials and optimized electrode shapes, with a compact cabinet structure.
This switchgear is technologically advanced, with stable performance, reasonable structure, convenient use, and safe and reliable power distribution equipment
No. | Item | Unit | Data | ||
1 | Rated voltage | kV | 3.6, 7.2, 12 | ||
2 | Rated frequency of circuit breaker | Hz | 50 | ||
3 | Rated current of circuit breaker | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | ||
4 | Rated current of switchgear | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | ||
5 | Rated short-time withstand current (4s) | kA | 16, 20, 25, 31.5, 40, 50 | ||
6 | Rated withstands current (peak) | kA | 40, 50, 63, 80, 100, 25 | ||
7 | Rated short-circuit breaking current | kA | 16, 20, 25, 31.5, 40, 50 | ||
8 | Rated short-circuit closing current (peak) | kA | 40, 50, 63, 80, 100, 25 | ||
9 | Rated insulation level | 1 min power frequency withstands voltage | between poles, pole to earth | kV | 24, 32, 42 |
between open contacts | kV | 24, 32, 48 | |||
Lightening impulse withstands voltage (peak) |
between poles, pole to earth | kV | 40, 60, 75 | ||
between open contacts | kV | 46, 70, 85 | |||
10 | Protection level | Shell: IP4X; IP2X when the CPT and CB doors are open |
Note:
1. The short circuit capacity of the current transformer should be separately considered.
2. See technical parameters of ZN63A-12 in related catalogues of our company.
Item | Unit | Value | ||||
Contact distance | mm | 12 | ||||
Contact travel | 75 | |||||
Average closing speed (6mm~contact closed) | m/s | 42 | ||||
Average opening speed (contact separation -6mm) | 20 | 25 | 31.5 | 40 | ||
Opening time (rated voltage) | m/s | 630 | 630, 1250, 1600, | 1250, 1600, 2000, | ||
Closing time (rated voltage) | 1250 | 2000, 2500, 3150 | 2500, 3150, 4000 | |||
Contact closing bounce time | m/s | 20 | 25 | 31.5 | 40 | |
Three phase opening asynchrony | 63 | 80 | 100 | |||
Allowable cumulative thickness of wear for moving and stationary contacts | mm | 50 | 63 | 80 | 100 | |
Rated short-circuit breaking current breaking times | Times | 80 | 50 | 30 | ||
Secondary circuit power frequency withstand current | V | 2000 | ||||
Rated operating sequence | Opening -0.3s – closing and opening -180s – closing and opening -180s – closing and opening -180s – closing and opening (40kA | |||||
Rated thermal stability time | S | 4 | ||||
Rated single/back to back capacitor bank breaking current | A | 630/400 | 800/400 | |||
Mechanical life | Times | 20000 | 10000 |
Shape | Description | Size(mm) |
Width (W) | Rated current of branch bus ≤1250A, heat stable current≤40KA | 800(650) |
Rated current of branch bus ≥1600A | 1000 | |
Depth (C) | Cable Incoming and outgoing feeder | 1500 |
Overheaded incoming and outgoing feeder | 1660 | |
Height (B) 2300(2200) |
Outline size Picture 2
Sheet 4
Continued Sheet 4
Continued Sheet 4
Continued Sheet 4
Continued Sheet 4
Continued Sheet 4