Product Overview
Product Details
Data Download
Related Products
General
Time Switch is control element with time as control unit and can automatically turn on or tunrn off power supply of various consumer equipments according to preset time by user. The controlled objects are circuit equipments and household appliances such as street lamps, neon lamps, advertising lamps, manufacturing equipments, broadcast & television equipments, etc., which requires turning on and off at definite time
Contact Us
Overall and mounting dimensions(mm)
Rated insulation voltage Ui: AC380V
Rated control voltage: AC110V, AC220V, AC380V
Usage category: Ue: AC110V/AC220V/AC380V; Ie: 6.5 A/ 3 A/ 1.9 A; Ith: 10 a; Ac-15
Protection degree: IP20
Pollution degree: 3
Load power: resistive load: 6kW; Inductive load: 1.8KW; Motor load: 1.2KW; Lamp load:
Operating mode | Time automatic control | ||||
Rated operating current | AC-15 3A | ||||
Rated operating voltage | AC220V 50Hz/60Hz | ||||
Electrical life | ≥10000 | ||||
Mechanical life | ≥30000 | ||||
Times of ON/OFF | 16 opens & 16 closes | ||||
Battery | AA size battery (replaceable) | ||||
Timing error | ≤2s/day | ||||
Ambient temperature | -5°C~+40°C | ||||
Installation mode | Guide rail type,wall-mounted type,unit style | ||||
External dimension | 120×77×53 |
Wiring for direct control mode:
direct control mode can be used for electrical apparatus which is single-phase phase power supply and its power consumption doesn’t exceed
rated value of this switch.See Figure 1 for wiring method;
Wiring for single-phase dilatancy mode:
it is required a AC contactor with larger capacity than electrical apparatus power consumption for dilatancy when the controlled electrical apparatus
is single-phase power supply, whereas its power consumption exceeds rated value of this switch.
See Figure 2 for wiring method;
wiring for three-phase operation mode:
if the controlled electrical apparatus is three-phase power supply, it is required toexternally connect three-phase AC contactor.
See Figure 3 for wiring, control contactor @ AC220V coil voltage,50Hz;
See Figure 4 for wiring, control contactor @ AC 380V coil voltage,50Hz