Ringkesan Produk
Rincian Produk
DATA DOWNLOAD
Produk sing gegandhengan
Hubungi kita
YCB8 | - | 125 | PV | 4P | 63 | DC250 | + | YcB8-63 saka |
Model | Saiki kelas Shell | Dianggo | Jumlah cagak | Rated saiki | Coltage rated | Aksesoris | ||
Miniatur sirkuit breaker | 125 | PV: Heteropoloritas PVN: Nonpolaris | 1P | 63A, 80A, 100A, 125A | DC250v | YCB8-1OXING: auxiliary | ||
2P | DC500V | YCB8-125 SD: weker | ||||||
3P | DC750V | YCB8-125 mx: Shunt | ||||||
4P | DC1000V |
CATETAN: voltase sing dirating kena pengaruh saka jumlah cagak lan mode wiring.
Tunggal DC250v, rong cagak ing seri yaiku DC500V, lan liya-liyane.
Standar | IEC / en 60947-2 | ||||
Jumlah cagak | 1p | 2p | 3p | 4p | |
Dirating arus kelas pigura | 125 | ||||
Kinerja listrik | |||||
RATED Makarya voltase UE (V DC) | 250 | 500 | 750 | 1000 | |
Rated saiki ing (a) | 63,80,100,125 | ||||
Rated insulasi voltase ui (v dc) | 1000v | ||||
Dipedahaken impulse voltase uimp (kv) | 6 | ||||
Kapasitas Breaking Ultimate ICu (Ka) | PV: 6 PVN: 10 | ||||
Kapasitas Breaking Operasi (Ka) | PV: ICS = 100% ICU PVN: ICS = 75% ICU | ||||
Jinis kurva | li = 10ln | ||||
Jinis Tripping | Thermomagnetic | ||||
Layanan layanan (wektu) | Mekanik | 20000 | |||
Listrik | PV: 1000 PVN: 300 | ||||
Cara Inline | Bisa munggah lan mudhun menyang garis | ||||
Aksesoris Listrik | |||||
Hubungan tambahan | □ | ||||
Hubungi Alarm | □ | ||||
Rilis Shunt | □ | ||||
Kahanan lingkungan lan instalasi | |||||
Suhu sing digunakake (℃) | -35 ~ + 70 | ||||
Suhu panyimpenan (℃) | -40 ~ + 85 | ||||
Rintangan Kelembapan | Kategori 2 | ||||
Altitude (m) | Gunakake kanthi deterik ing ndhuwur 2000m | ||||
Gelar Polusi | Tingkat 3 | ||||
Gelar Perlindhungan | IP20 | ||||
Lingkungan Instalasi | Papan tanpa geter lan pengaruh sing signifikan | ||||
Kategori Instalasi | Kategori III | ||||
Cara instalasi | Rail standar Din35 | ||||
Kapasitas wiring | 2.5-50mm² | ||||
Tork Terminal | 3.5n · m |
■ Standard □ Opsional ─ Ora
Cathetan:
L + pasokan tenaga positif
Katem l-daya
Pole positif breaker sirkuit
Kutub Negatif saka Circuit Breaker
Jinis Tripping | DC saiki | Negara wiwitan | Wektu sing ditunjuk | Asil samesthine |
Kabeh jinis | 1.05in | Negara kadhemen | t≤2h | Ora tripping |
1.3in | Negara termal | t <2h | Tripping | |
II = 10in | 8in | Negara kadhemen | t≤0.2s | Ora tripping |
12in | t <0.2s | Tripping |
Rated saiki (a) | Suhu (℃) | -25 | -20 | -10 | 0 | 10 | 20 | 30 | 40 | 50 | 60 |
63A | 77.4 | 76.2 | 73.8 | 71.2 | 68.6 | 65.8 | 63 | 60 | 56.8 | 53.4 | |
80A | 97 | 95.5 | 92.7 | 89.7 | 86.6 | 83.3 | 80 | 76.5 | 72.8 | 68.9 | |
100A | 124.4 | 120.7 | 116.8 | 112.8 | 108.8 | 104.5 | 100 | 95.3 | 90.4 | 87.8 | |
125A | 157 | 152.2 | 147.2 | 141.9 | 136.5 | 130.8 | 125 | 118.8 | 112.3 | 105.4 |
Faktor koreksi saiki ing macem-macem altitudes
Rated saiki (a) | Faktor koreksi saiki | ||
≤2000m | 2000-3000M | ≥3000m | |
63, 80, 100, 125 | 1 | 0,9 | 0,8 |
Tuladha: Yen sirkuit breaker kanthi arus 100A digunakake ing 2500m,
Saiki arus sing dirating kudu diserang 100A × 90% = 90A
Rated saiki ing (a) | Bagean salib konduktor tembaga nominal (MM²) | Konsumsi daya maksimal saben kutub (w) |
63 | 16 | 13 |
80 | 25 | 15 |
100 | 35 | 15 |
125 | 50 | 20 |
Aksesoris
Aksesoris ing ngisor iki cocog kanggo seri ycb8-125pv, sing bisa nyedhiyani fungsi remot kontrol breaker, otomatis sirkuit fault, indikasi status (ngilangi / nutup tripping)
a. Total aksesoris aksesoris sing dipasang ing 54mm, tatanan kiwa menyang tengen: saka kiwa kiwa menyang tengen: saka, SD (3max) + mv + mn, mv (1max) + mcB; SD mung bisa ngumpul nganti 2 potongan;
b. Dipasang karo awak, ora ana alat sing dibutuhake;
c. Sadurunge instalasi, priksa apa parameter teknis produk kasebut cocog karo syarat, lan ngoperasikake gagang mbukak lan nutup kaping pirang-pirang kanggo mriksa apa Mekanisme kasebut bisa dipercaya.
Aksesoris Miniatur Circuit Breaker
● kontak bantu
Indikasi remot nutup / pambuka status pemutus sirkuit.
● Alarm kontak sd
Nalika perjalanan siram breaker sirkuit, dikirim sinyal, bebarengan karo indikasi abang ing ngarep piranti. ● shunt ngeculake mx
Nalika voltase sumber daya listrik yaiku 70% ~ 110% utawa lelungan pemecahan sirkuit remot sawise nampa sinyal kasebut.
● Menang lan Mecah Minimal: 5ma (DC24V)
● Urip layanan: 6000 kaping (frekuensi operasi: 1s)
MX + Outline lan Ukuran Instalasi
Model | Ycb8-125 saka | YCB8-125 SD | Ycb8-125 mx | |||
Penampilan | ||||||
Jinis | ||||||
Jumlah kontak | 1no + 1nc | 1no + 1nc | / | |||
Voltase Kontrol (V DC) | 110-415 48 12-24 | |||||
Nganggo kontak saiki | AC-12 UE / IE: AC415 / 3A DC-12 UE / IE / IE: DC125 / 2A | / | ||||
Tegangan Kontrol Shunt | UE / IE: AC: 220-415 / 0.5a AC / DC: 24-48 / 3 | |||||
Jembar (MM) | 9 | 9 | 18 | |||
Kahanan lingkungan lan instalasi | ||||||
Suhu panyimpenan (℃) | -40 ℃ ~ ~ + 70 ℃ | |||||
Kelembapan panyimpenan | Kelembapan relatif ora ngluwihi 95% nalika ing + 25 ℃ | |||||
Gelar Perlindhungan | Tingkat 2 | |||||
Gelar Perlindhungan | IP20 | |||||
Lingkungan Instalasi | Papan tanpa geter lan pengaruh sing signifikan | |||||
Kategori Instalasi | Kategori II, Kategori III | |||||
Cara instalasi | Instalasi rel th35-7.5 / Din35 Din35 | |||||
Kapasitas wiring maksimal | 2.5mm² | |||||
Tork Terminal | 1n · m |
Outline kontak Alarm lan dimensi instalasi