JN22-40.5/31.5 Indoor Grounding Switch
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

JN22-40.5/31.5 Indoor Grounding Switch
Picture
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch
  • JN22-40.5/31.5 Indoor Grounding Switch

JN22-40.5/31.5 Indoor Grounding Switch

JN22-40.5/31.5 series indoor MV earthing switch is researched and developed by XIAN HV Electric research organization,withadvanced design and steady performance,simple structures,simple mounting and adjustment,suitable of electric power system with 40.5KV,Three-phase,AC 50Hz.Support with KYNo-40.5 and other various kinds of MV switchgear and as earthingc protection.
Standard:IEC129,IEC 62271-102

Contact Us

Product Details

● JN22-40.5/31.5 series indoor MV earthing switch is researched and developed by XI'AN HV Electric research organization,with advanced design and steady performance, simple structures, simple mounting and adjustment, suitable of electric power system with 40.5KV, Three-phase, AC 50Hz.. Support with KYN□-40.5 and other various kinds of MV switchgear and as earthing protection.
● Standard: IEC 129,IEC 62271-102.

Selection

1

Operating conditions

1. Ambient temperature:-10~+40℃

2. Altitude: ≤1000m

3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree

5. Appliable in the place without corrosive, flammable gas and water place

6. With no frequently intense vibrant place around.

Technical data

Item Units Data
Rated voltage kV 35
Maximum voltage kV 40.5
Rated short time withstand current kA 31.5
Rated short circuit withstand time s 4
Rated short circuit making current kA 80
Rated peak withstand current kA 80
Rated 1min power frequency withstand voltage kV 95
insulation level Lightning Impulse withstand voltage kV 185
Central distance between poles mm 300; 350; 400

Overall and mounting dimensions(mm)

2

B H L
280 750 1180
300 790 1180
350 890 1280
400 990 1374

Order Notes

1. Indicate product specification, rated voltage, thermal stability current, central distance between poles.

2. If need shaft operating mechanism, indicate right operation mechanism or left operation mechanism according to the operation position shows in the drawing above.

3. If need sensors with electric display device, please indicate the display type.

4. Please consult with our company if you have any special request.

B H
280 750
300 790
350 890
400 990
Write your message here and send it to us