JDZ□□18(10)-3,6,10 Voltage Transformer
Picture
  • JDZ□□18(10)-3,6,10 Voltage Transformer
  • JDZ□□18(10)-3,6,10 Voltage Transformer

JDZ□□18(10)-3,6,10 Voltage Transformer

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

JDZ口口18(10)-3,6,10 Voltage Transformer

The voltage transform is the type of cast resin insulation and full enclosed, used for electric energy metering, voltage control and relay protection in the power systems of rated voltage 3kV, 6kV, and 10kV or below.

Standard:IEC 61869-3

Selection

0

Technical data

1. Technical data form.

2. Partial dischanage is inline with GB1207-2006 voltage transformer.

3. Anti-pollution degree: see fig.

Technical data

Type Rated voltage
ratio(V)
Rated output(VA) Ultimate
output(VA)
Rated
insulation
level(kV)
0.2 0.5 1 6P
JDZ18-3
RZL10
3000/100 15 30 60 500 3.6/25/40
JDZ18-6
RZL10
6000/100 7.2/32/60
JDZ18-10
RZL10
10000/100 12/42/75
JDZF18-3 3000/100/100 10 10 30 2 ×250 3.6/25/40
JDZF18-6 6000/100/100 7.2/32/60
JDZF18-10 10000/100/100 12/42/75
JDZX18-3
REL10
3000/√3/100/ √3/100/3 15 30 100 200 3.6/25/40
JDZX18-6
REL10
6000/√3/100/ √3/100/3 7.2/32/60
JDZX18-10 REL10 10000/√3/100/ √3/100/3 12/42/75
JDZXF18-3 3000/√3/100/    √3/100/√3/100/3 10 10 60 200 3.6/25/40
JDZXF18-6 6000/√3/100/    √3/100/√3/100/3 7.2/32/60
JDZXF18-10 10000/√3/100/   √3/100/√3/100/3 12/42/75

Overall and mounting dimensions(mm)

Chart 1 Outline and installation size of JDZ(F)18-6,10B

0

Chart 2 Outline and installation size of JDZ10-6,10(RZL)

0

Chart 3 Outline and installation size of JDZX10-6,10(REL10)

0

 