GW5 outdoor MV isolating switch isused for three-phase AC 50Hz outdoor high voltage electrical equipment,used for the line toswitching under voltagepressed no load condition,and electrical isolation the maintenanced high voltage bus,circuit breakersand other electrical equipment and chargedhigh voltage line,canalso be used for the opening and dosing small capacitanceorinductance current.When the knife in the normal break position,can provide a insulation distance consistent with safetyrequirements.Widely used in 35~110kV substation
Contact Us
GW5 outdoor MV isolating switch is used for three-phase AC 50Hz outdoor high voltage electrical equipment, used for the line to switching under voltage pressed no load condition, and electrical isolation the maintenanced high voltage bus, circuit breakers and other electrical equipment and charged high voltage line, can also be used for the opening and closing small capacitance or inductance current. When the knife in the normal break position, can provide a insulation distance consistent with safety requirements. Widely used in 35~110kV substation.
1. The ambient temperature: upper limit +40℃,lower limit -40 ℃;
2. Altitude: no more than 3000m;
3. Wind speed: not more than 35m/s;
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution level: no more than III;
6. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Item | Unit | Parameters | ||||
GW5- 40.5 | GW5-72.5 | GW5-126 | GW5-145 | |||
Voltage, current parameters | ||||||
Rated voltage | kV | 40.5 | 72.5 | 126 | 145 | |
Rated current | A | 630/1250/1600/2000 | ||||
Rated frequency | Hz | 50 | ||||
Disconnector | Rated peak withstand current | kA | 50/80/100 | |||
Rated short-time withstand current | kA | 20/31.5/40 | ||||
Rated short circuit duration | s | 4 | ||||
I type earth knife | Rated peak withstand current | kA | 25 | |||
Rated short-time withstand current | kA | 10 | ||||
Rated short circuit duration | s | 4 | ||||
II type earth knife | Rated peak | kA | 100 | |||
withstand current | ||||||
Rated short-time withstand current | kA | 40 | ||||
Rated short circuit duration | s | 2 |