Product Overview
Product Details
Data Download
Related Products
GW4 outdoor MV isolation switch is used for three-phase AC 50Hz outdoor high-voltage electrical equipment,switching of linesunder high-voltage no-load conditions,and electrically isolating electrical equipment such as high-voltage busbars,circuitbreakers,and live high-voltage equipment for maintenance voltage lines,can also be used to switchsmall capacitor or inductorcurrent.Whenthe knifeis in the normal open circuit position,it can provide insulation distancethat meets safety requirements Widely used in 35-110kV substations
Contact Us
GW4 outdoor MV isolation switch is used for three-phase AC 50Hz outdoor high-voltage electrical equipment, switching of lines under high-voltage no-load conditions, and electrically isolating electrical equipment such as high-voltage busbars, circuit breakers, and live high-voltage equipment for maintenance voltage lines , can also be used to switch small capacitor or inductor current. When the knife is in the normal open circuit position, it can provide insulation distance that meets safety requirements. Widely used in 35-110kV substations.
Item | Unit | Parameters | |||||
GW4-40.5 | GW4-72.5 | GW4-126 | GW4-126G | GW4-145 | |||
Rated voltage | KV | 40.5 | 72.5 | 126 | 126 | 145 | |
Rated current | A | 630 1250 2000 2500 |
630 1250 2000 2500 4000 |
630 1250 2000 2500 |
630 1250 |
1250 2000 2500 |
|
Rated short-time withstand current (RMS) | KA | 20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 |
20 31.5 40(46) |
|
Rated peak withstand current (peak) | KA | 50 80 100(104) |
50 80 100(104) |
50 80 100(104) |
50 80 |
50 80 100(104) |
|
Rated short-time withstand voltage (effective value) | To the ground | KV | 80 | 140 | 185(230) | 185 | 375 |
Fracture | 110 | 160 | 210(265) | 210 | 315 | ||
Rated lightning impulse withstand voltage (peak) |
To the ground | KV | 185 | 325 | 450(550) | 450 | 650 |
Fracture | 215 | 375 | 520(630) | 550 | 750 | ||
Wiring terminal rated the horizontal tension |
490(735) | 735 | 735 | 735 | 960 | ||
Weight of single pole | 80 | 200 | 240 | 300 | 300 |
1. Ambient temperature: upper limit +40℃, lower limit -30℃
2. Altitude: no more than 3000m;
3. Wind speed: no more than 35m/s;
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution level: no more than III class
6. No severe vibration, no corrosive gas, no fire, no explosion danger place.
1. Wiring terminal