GW1-12G(D) Isolation Switch
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

GW1-12G(D) Isolation Switch
Picture
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch
  • GW1-12G(D) Isolation Switch

GW1-12G(D) Isolation Switch

Operating conditions
1.The altitude above sealevel:2000m
2.The ambientair temperature:-40℃~40℃ wind speed does not exceed 35m/s.
3.The earthquake intensitydoes not exceed 8 degrees
4.The working situation is without frequentviolent vibration.
5.The installation site ofordinarytypeisolator should be kept awayfromgas,smoke chemical deposition,salt-spray fog,dust and other explosiveand corrosive maters that affect seriously insulation and conductioncapabilityof the isolator.
6.Pollutioni-proof type isolatoris applicable to severe filthyconduction area,however,it shouldn’t be anyexplosive matters and matters causing fire.

Contact Us

Product Details

Selection

0

Operating conditions

The altitude above sea level: 2000m

The ambient air temperature: -40℃~40℃ wind speed does not exceed 35m/s.

The earthquake intensity does not exceed 8 degrees.

The working situation is without frequent violent vibration.

The installation site of ordinary type isolator should be kept away from

gas,smoke chemical deposition, salt-spray fog, dust and other explosive

and corrosive maters that affect seriously insulation and conduction

capability of the isolator.

Pollutioni proof type isolator is applicable to severe filthy conduction area

however, it shouldn't be any explosive matters and matters causing fire.

1

Technical data

Item Unit Technical parameters
Rated voltage kV 10 15 20
Max. operating voltage kV 12 17.5 24
Rated insulation level 1min. power frequency withstand voltage To earth kV 38 42 50
Across open DS kV 42 48 60
Rated lightning impulse withstand voltage To earth kV 75 105 125
Across open DS kV 85 120 145
Rated frequency Hz 50
Rated current A 200 400 630 1250
4s short time withstand current kA 6.3 12.5 20 31.5
Peak withstand current kA 16 31.5 50 80
Mechanism supplied for disconnector CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism

Technical data

Item Unit Technical parameters
Rated voltage kV 12 24 33
Max. operating voltage kV 15 27 35
Rated insulation level 1min. power frequency withstand voltage To earth kV 40 50 80
Across open DS kV 47 60 90
Rated lightning impulse withstand voltage To earth kV 105 125 180
Across open DS kV 120 145 210
Rated frequency Hz 50
Rated current A 200 400 630 1250
4s short time withstand current kA 6.3 12.5 20 31.5
Peak withstand current kA 16 31.5 50 80
Mechanism supplied for disconnector CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism

Overall and mounting dimensions(mm)

1 (2)

Connect pole

1. Φ12Spindle

2. Washer12

3. Open bolt4 25

4. Bend coupling

5. M16Nut

6. Pole

7. 3/4" Water gas pipe

8. Connect pole head

Product model number A B C
GW1-12G/400A 510 555 18 ×24 =4
GW1-12G/630A 530 555 18 ×24 =4
GW1-24G/400A 510 555 18 ×24 =4
GW1-24G/630A 530 555 18 ×24 =4
Write your message here and send it to us

Related Products