Product Overview
Product Details
Data Download
Related Products
Operating conditions
1.The altitude does not exceed1000m;
2.Ambientair temperature:-10℃~+40℃;
3.Relative humidity:dailyaverage value is not greater than 95%,monthlyaveragevalue is not greater than 90%;
4.Contamination grades:no serious dust,corrosiveand explosive material place;
5.Earthquake intensity:do notexceed 8 degree;No regularviolent vibration place.
Contact Us
GN30-12 (D) rotary indoor MV isolating switch is a new type isolation switch of rotary knife type, the main structure is fixed two groups of insulator and contact on the two plane of three-phase chassis, through the rotary contact, realize the switch on-off.
GN30-12 (D) switch is a new type added grounding knife on the GN30-12 type switch basis, which can meet the needs of different power systems.
The product design is with compact, small occupied space, strong insulating ability, easy installation and adjustment, its performance meets the GB1985-89 "AC high voltage isolating switch and the grounding switch" requirements, applicable to the rated voltage 10kV AC 50Hz and below indoor power system, to open and close the circuit when voltaged, no load. It can be used with the high voltage switch cabinet, and also can be used separately.
1. The altitude does not exceed 1000m;
2. Ambient air temperature: -10 ℃ ~+40 ℃;
3. Relative humidity: daily average value is not greater than 95%, monthly average value is not greater than 90%;
4. Contamination grades: no serious dust, corrosive and explosive material place;
5. Earthquake intensity: do not exceed 8 degree; No regular violent vibration place.
Product specifications Parameter Item |
GN30-12/400-12.5 | GN30-12/630-12.5 | GN30-12/1000-12.5 | GN30-12/1250-12.5 | GN30-12/1600-12.5 | |
GN30-12D/400-12.5 | GN30-12D/630-12.5 | GN30-12D/1000-12.5 | GN30-12D/1250-12.5 | GN30-12D/1600-12.5 | ||
Voltage, current parameters | ||||||
Rated voltage (kV) | 12 | |||||
Rated current (A) | 400 | 630 | 1000 | 1250 | 1600~3150 | |
Rated short-time withstand current (kA) | 12.5 | 20 | 31.5 | 31.5 | 40 | |
Rated short-time duration (S) | 4 | 4 | 4 | 4 | 4 | |
Rated peak withstand current (KA) | 31.5 | 50 | 80 | 80 | 100 | |
Rated insulation level | 1 min power frequency withstand voltage (KV) | Between pole, pole to earth 42 fracture 48 | ||||
Lightning impulse voltage (kV) | Between pole, pole to earth 75 fracture 85 |
1. Vertical incoming contact
2. Vertical contact support
3. Rotating moving contact
4. Insulator
5. Grounding contact
6. Parallel contact support
7. Parallel outgoing contact
8. Rack
9. Name plate
10.Opening and closing crank arm
Notes
Outline and installation dimensions of isolation switches on a distance of 210mm The incoming and outgoing line methods are: parallel incoming line and parallel out going line: