Product Overview
Product Details
Data Download
Related Products
Rating:Rated voltage:380V. 50-60Hz
Application:
mainly applicable in power station,power substation industrial and mining enterprises as energy converter,distributor and controller of power,light and distribution device.
Standard:IEC60439-1
Contact Us
Rating: Rated voltage: 380V.
50-60Hz
Application:
mainly applicable in power station, power substation industrial and mining enterprises as energy converter, distributor and controller of power, light and distribution device.
Standard: IEC60439-1
1. Ambient air temperature: -15℃ ~+40℃
Daily average temperature: ≤35℃
When the actual temperature exceed the range, it should be used by reducing the
capacity accordingly.
2. Transport and store temperature: -25℃ ~+55℃. do not exceed +70℃ in short
time.
3. Altitude: ≤2000m
4. Relative humidity: ≤50%, when temperature is +40℃
When temperature is low, larger relative humidity is allowed. when it is +20℃,
relative humidity can be 90%. Since the temperature change will make out
condensation.
5. Installation inclination: ≤5%
6. Applicable in the places without corrosive and flammable gas.
Note: Customized products are available.
1. Main technical data Sheet 1
Type | Rated voltage (V) |
Rated current (A) |
Rated short-circuit breaking current (kA) |
Rated short-circuit withstand current (1s)(1kA) |
Rated peak withstand voltage (kA) |
GGD1 | 380 | A 1000 | 15 | 15 | 30 |
380 | B 600(630) | 15 | 15 | 30 | |
380 | C 400 | 15 | 15 | 30 | |
GGD2 | 380 | A 1500(1600) | 30 | 30 | 63 |
380 | B 1000 | 30 | 30 | 63 | |
380 | C 600 | 30 | 30 | 63 | |
GGD3 | 380 | A 3150 | 50 | 50 | 105 |
380 | B 2500 | 50 | 50 | 105 | |
380 | C 2000 | 50 | 50 | 105 |
2. Main bus
1) Single copper busbar adopted when the rated current<=1500A 2) Double copper busbar adopted when the rated current>1600A.
3) Brushing &anodizing process adopted which is better than traditional zinc-coated process.
3. Selection of horizontal bus Sheet 2
Rated current (A) |
Copper Busbar specification (mm) |
400 | 40×4 |
630 | 50×5 |
1250 | 60×10 |
1600 | 80×10 |
2000 | 2×(60×10) |
2500 | 2×(80×10) |
3150 | 2×(100×10) |
4. Selection of neutral earthgin bus Sheet 3
Cross section of phase conductor (mm²) |
Cross section of PE(N) conductor (mm²) |
500~720 | 40×5 |
1200 | 60×6 |
>1200 | 60×10 |
1. The accuracy and quality of the switchgear could be ensured as the framework parts and special parts supplied by CNC. Modular
design of the Overall and mounting dimensions(mm) s concering(E=20mm), which has cut production time and enhanced efficiency.
2. The heat dispensation channel at the top and bottom of the switchgear formulate a ventilation loop to dispens the beat.
3. Easy for installation and dismantling.
4. The switchgear with perfect earthing protection system.
5. The cover of the switchgear could be removed for installation and adjustment of the main bus bar. there are also rings for lifting and delivery of switchgear
6. The protection degree is IP30,As per you requirements,switchgearswith protection degree of IP20~IP40 are available.
7. Flexible circuit plans are available.
mm
Product code | A | B |
GGD 06 | 600 | 600 |
GGD06A | 600 | 800 |
GGD8 | 800 | 600 |
GGD08A | 800 | 800 |
GGD10 | 1000 | 600 |
GGD10A | 1000 | 800 |
GGD12 | 1200 | 800 |
Installation Overall and mounting dimensions(mm) Picture 2
Product code | A | B | C | D | |
GGD 06 | 600 | 600 | 450 | 556 | |
GGD06A | 600 | 800 | 450 | 756 | |
GGD8 | 800 | 600 | 650 | 556 | |
GGD08A | 800 | 800 | 650 | 756 | |
GGD10 | 1000 | 600 | 850 | 556 | |
GGD10A | 1000 | 800 | 850 | 756 | |
GGD12 | 1200 | 800 | 1050 | 756 |
Please specify the following information when ordering:
1. The full model,including main circuit plan and auxiliary circuit plan.
2. The diagram of main circuit system allocation.
3. Inner allocation diagram of the switchgear.
4. Electric diagram of auxiliary contact.
5. Name ,Model,Specification and list of adopted components.
6. Customized products are available.