GCS Low Voltage Switchgear
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

GCS Low Voltage Switchgear
Picture
Video
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
  • GCS Low Voltage Switchgear
GCS Low Voltage Switchgear Featured Image

GCS Low Voltage Switchgear

Rating:Ratedvoltage400V,690V,rated current reach to 4000A.

Application

mainly applicable in place with high automation and need to communicate with computer,like largepower station andpetrochemistry system,as the low voltage distribution device of the distribution and motor controlling,and reactive powercompensation in power system.
Protection degree:IP30,IP40
Standard:IEC60439-1

Contact Us

Product Details

Low Voltage Switchgear
GCS Low-voltage Switchgear Panel, Withdrawable Type

Rating: Rated voltage 400V, 690V, rated current reach to 4000A.
Application:
mainly applicable in place with high automation and need to communicate with computer, like large power station and petrochemistry system, as the low voltage distribution device of the distribution and motor controlling, and reactive power compensation in power system.
Protection degree: IP30, IP40
Standard: IEC60439-1

Selection

1

Operating conditions

1. Ambient air temperature: -15℃ ~+40℃
Daily average temperature: ≤35℃
When the actual temperature exceed the range, it should be used by reducing the
capacity accordingly.
2. Altitude: ≤2000m
3. Relative humidity: ≤50%, when temperature is +40℃
When temperature is low, larger relative humidity is allowed. when it is +20℃,
relative humidity can be 90%. Since the temperature change will make out
condensation.
4. Installation inclination: ≤5%
5. Applicable in the places without corrosive and flammable gas.
Note: Customized products are available.

Technical data                                                                                                                                                                                                                                  Sheet 1

Item Data
The main circuit of rated voltage(V) AC400, 690
The auxiliary circuit of rated voltage(V) AC220, 400; DC110, 220
Rated frequency(Hz) 50(60)
Rated insulation voltage(V) 660(1000)
Rated current(A) Horizontal busbar ≤4000
Vertical bus(MCC) 1000
Busbar rated short time withstand current(KA/1S) 50, 80
Busbar rated peak withstand current(KA/0.1s) 105, 176
Power frequency test Main circuit 2500
voltage (V/1Min) Auxiliary circuit 2000
Main Busbar 3 Phase 4 Wires A, B, C, N
3 Phase 5 Wires A, B, C, PE, N

Features

1. C type material adopted for the mainframe, frame use the form of Assembling structure. Main frame have the installation modular hole E=20mm
2. The Compartment is divided into functional unit rooms, bus room, cable rooms,Each unit is relatively independent .”
3. Take the drawer as main body, meanwhile have the draw out type and fixed type, can mixed combination, Arbitrary selection.

4. Cabinet size (refer to sheet 2)                                                                                                                                                                                                 Sheet 2

Height 2200
Width 400 600 800 1000
Depth 600 800 1000

5. Functional unit
1) The higher modulus of drawer is 160mm, divide to1/2 unit, 1 unit, 1.5unit, 2 unit,3 unit 5 different size series. Unit loop rated voltage below 400A.
2) The same functional unit of the drawer has good interchangeability.Each MCC cabinet can install max 11 set drawer with 1 unit, or 3) 22 sets drawer with 1/2 unit. Drawer with more than 1 unit adopt multi-functional plate .
4) Drawer incoming and outgoing line adopt the same standardized plug of slice structure with different quantity according to current 5) The transfer between ½ unit drawer and cable cabinet use ZJ-2 adapter..
6) The transfer between drawer which is above 1 unit and cable cabinet use standardized bar type or tube type ZJ-1 adapter according to different current rated.
7) Drawer panel have the open, close, test, draw out position indicator.
8) Drawer unit have Mechanical linkage.
9) Feeder cabinet and motor control cabinet have special cable insulation cabinet. The connection between functional unit and cable cabinet adopt adapter.Not only improves the reliability of the cable, and greatly facilitates the user safety and repair of cable.

6. Busbar
In order to improve the bus dynamic thermal stability and improved contact surface temperature rise, device use TMY-T2 series of hard copper, Copper plate surface will be treated with new advanced oxidation process. The performance index is superior to the traditional tin plating process.
1) Horizontal busbar
Horizontal busbar is arranged in Busbar compartment at the back of cabinet,double busbar for above 2500 A, single layer busbar for current below 2500A.Each phase is composed of 4 or 2 pcs busbar ,improve the Short circuit strength of bus.
2) Vertical bus
"L" shape hard copper tin bus is used for vertical busbar of drawer.L type bus specification(mm):
(Height ×thickness)+(button×Thickness)(50 ×5)+(30 ×5)Rated current 1000A
Neutral grounding busbar
3) Adopt hard copper. Through the level of neutral grounding wire (PEN) or ground +neutral line (PE+N).

Overall and mounting dimensions(mm)

Electric power, communication cabinet installation diagram                                                             Picture 1

1

(mm) Sheet 3

Cabinet code A B C D Remark
GCS-TG1010-4 1000 1000 900 900 Communication cabinet
GCS-TG0810-4 800 1000 700 900 Electric power cabinet
GCS-TG0808-4 800 800 700 700 Electric power cabinet
GCS-TG0608-4 600 800 500 700 Electric power cabinet

PC cabinet installation diagram                                                                                                                                                           Picture 2

1

(mm) Sheet 4

Cabinet code A B C D E F ×G
GCS-TG1010-2 1000 1000 900 900 60 400×400
GCS-TG0810-2 800 1000 700 900 160 200×400
GCS-TG1008-2 1000 800 900 700 60 400×400
GCS-TG0808-2 800 800 700 700 160 200×400
2

(mm) Sheet 5

Cabinet code A B C D E F ×G
GCS-TG1008-1 1000 800 900 700 60 400×350
GCS-TG1006-1 1000 600 900 500 60 400×350
GCS-TG0806-1 800 600 700 500 160 200×350

Main single line diagram                                                                                                                           Sheet 5

3

Continued Sheet 5

1

Continued Sheet 5

7

Continued Sheet 5

6

Continued Sheet 5

4

Continued Sheet 5

5

Continued Sheet 5

1
Write your message here and send it to us

Related Products