Product Overview
Product Details
Data Download
Related Products
Contact Us
FZN25, FZRN25 vacuum load switch and composite apparatus, suitable for three-phase AC 50Hz ring network or terminal power supply and industrial electrical equipment, for load control and short circuit protection use, load switch open and close the closed loop current, no-load transformer and cable charging current, composite apparatus can break any current till rated short circuit current.
Adopt the straight move or isolating fracture and vacuum interrupter linkage. With function of manual and electric operation.
FZN25, FZRN25 special transmission structure design, arc extinguish chamber only withstand voltage in the moment of closing and breaking, small size, low price.
FZN25, FZRN25 can realize isolation fracture and arc extinguish chamber fracture disposable operating.
FZN25, FZRN25 has a grounding switch mutual linkage grounding valve between the static contact and movable conductive cylinder, ensures safety and convenient maintenance.
Standard: IEC 60265-1,IEC 62271-105.
1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at - 30℃), 24h average value is not higher than +35℃; 2. Altitude: no more than 1000m;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: do not exceed 8 degree;
5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution; 6. No regular violent vibration;
7. Contamination grade: II class;
Item | Unit | FZN25-12D/ | FZRN25-12D/ |
T630-20 | T125-20 | ||
Voltage, current parameters | |||
Rated voltage | kV | 12 | |
Rated frequency | Hz | 50 | |
Rated current | A | 630 | 125 |
Rated short time power frequency withstand voltage (1min) | kV | Interrupter fracture 30;phase to earth 42;isolation fracture 48 | |
Rated lightning impulse withstand voltage (peak) | kV | Phase to earth 75;isolation fracture 85 |
|
Rated peak withstand current | kA | 50 | - |
4s rated short-time withstand current | kA | 20 | - |
Rated active load breaking current | A | 630 | - |
Rated loop breaking current | A | 630 | - |
Rated cable charging breaking current | A | 10 | - |
Interrupting no load transformer capacity | kVA | 1250 | - |
Rated short-circuit breaking current | kA | - | 31.5 |
Rated transfer current, rated AC current | A | - | 2000 |
Fuse type | SDLAJ-12 SFLAJ-12 |
||
The impactor energy output | J | 2-5 (medium) | |
Rated short-circuit closing current | kA | 50 | |
Grounding switch rated stability current | kA | 50 | |
Grounding switch 2S thermal stability current | kA | 20 | |
The auxiliary circuit rated voltage | V | ≌220/110 | |
Mechanical life | Times | 10000 |