1. Altitude: no more than 1000m;
2. The environment temperature: upper limit +40℃, lower limit -30℃;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;
4. Saturated steam pressure: daily average value is not higher than 2.2×10 -3 Mpa, monthly average is not higher than 1.8×10 -3 Mpa;
5. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Item | Unit | Parameter |
Technical parameter of combinations | ||
Rated voltage | kV | 12 |
Rated frequency | Hz | 50 |
The maximum rated current of the fuse | A | 125 |
Transfer current | A | 1550 |
The fuse triggered switch segment time | ms | 40±5 |
Rated short-circuit breaking current | kA | 31.5 |
Rated short-circuit closing current (prospective peak value) | kA | 80 |
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) | kV | 42/49 |
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) | kV | 75/85 |
Fuse impinger type | Medium-sized | |
Technical parameters of vacuum load switch of combined electrical appliance | ||
Rated voltage | kV | 12 |
Rated frequency | Hz | 50 |
Rated current | A | 630 |
Rated active load breaking current | A | 630 |
Rated close loop breaking current | A | 630 |
5% at rated load breaking current | A | 31.5 |
Rated cable charging breaking current | A | 10 |
Interrupting no load transformer capacity | kVA | 1250 |
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) | kV | 42/48 |
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) | kV | 75/85 |
4s rated short-time withstand current | kA | 31.5 |
Rated peak withstand current | kA | 80 |
Rated short-circuit closing current | kA | 80 |
Mechanical life | Times | 10000 |
Allowable cumulative thickness wear in contact | mm | 2 |
Opening and closing operating torque | N·m | ≤200 |
1. Cabinet bracket | 7. Static contact | 13. Insulated tension pole |
2. Disconnector | 8. Insulator | 14. Main axle |
3. Fuse | 9. Grounding knife | 15. Layshaft |
4. Insulated tension pole | 10. Grounding knife spring | 16. Adjusting yoke |
5. Upper bracket | 11. Opening spring | 17. Spring operating mechanism |
6. Vacuum interrupter | 12. The tripping driving device | - |