Nombre del producto | Marco de concha | Capacidad de ruptura | PV DC | Número de polos | Corriente nominal | Voltaje de funcionamiento |
YCB8S | 63 | H | PVN | 2P | 20A | DC600 |
YCB8S | 63 | Valor predeterminado: 6ka H: 10ka | PVN: Fotovoltaica DC No polaridad | 1P 2P 3P 4P | 1A 2A 3A 4A 6A 10A 16A 20A 25A 32a 40A 50A 63a | DC300 DC600 DC900 DC1200 |
Número de polos | 1P | 2P | 3P | 4P |
Voltaje de operación nominal UE (V) | DC300 | DC600 | DC900 | DC1200 |
UI (V) de voltaje de aislamiento nominal (v) | DC300 | DC600 | DC900 | DC1200 |
Voltaje de soporte de impulso nominal (KV) | 6 | |||
Corriente de marco nominal (a) | 63 | |||
Corriente nominal en (a) | 1,2,3,4,6,10,16,20,25,32,40,50,63 | |||
Ufica de la capacidad de ruptura de cortocircuito de la UCI (KA) | Predeterminado: 6; H: 10 | |||
Característica de disparo instantáneo | B, C, K | |||
Vida útil (tiempos) | Mechanical 20000, Electrical Life 1500 | |||
Título de protección | IP20 | |||
Temperatura ambiental para su uso | -25 ℃ ~+40 ℃ | |||
Altitud | ≤2000m | |||
Habilidad de cableado (mm²) | 25 | |||
Conexión | Tanto las líneas entrantes superiores como las delicias son aceptables | |||
Categoría de uso | A | |||
Estándar | IEC60947-2 |
Corriente nominal (a) | Características de disparo de sobrecarga | Disparo instantáneo Características (a) | |
1.05 pulgadas de tiempo de no tropiezo acordado h (estado frío) | 1.30 ln Tiempo de viaje acordado H (estado caliente) | ||
En ≤63 | 1 | 1 | B (4 pulgadas ± 20%) C (8ln ± 20%) K (10 pulgadas ± 20%) |
En> 63 | 2 | 2 |
Corriente nominal (a) temperatura ambiente correspondiente a la corriente nominal (a) | ||||||||||||
En (a) | -25 ℃ | -20 ℃ | -10 ℃ | 0 ℃ | 10 ℃ | 20 ℃ | 30 ℃ | 35 ℃ | 40 ℃ | 50 ℃ | 60 ℃ | 75 ℃ |
6A | 10.12 | 9.77 | 9.03 | 8.26 | 7.49 | 6.75 | 6 | 5.59 | 5.19 | 4.75 | 4.62 | / |
10A | 17.41 | 16.75 | 15.41 | 14.04 | 12.71 | 11.35 | 10 | 9.09 | 8.21 | 7.9 | 8.7 | 7.86 |
16A | 21.72 | 21.15 | 20.15 | 19.12 | 18.08 | 17.04 | 16 | 15.49 | 15.1 | 14.38 | 13.52 | 12.75 |
20A | 25.86 | 25.79 | 24.61 | 23.47 | 22.32 | 21.16 | 20 | 19.43 | 18.83 | 18.58 | 17.1 | 16.3 |
25A | 32.41 | 31.74 | 30.37 | 28.98 | 27.69 | 26.35 | 25 | 24.33 | 23.65 | 23.3 | 24.7 | 23.8 |
32a | 44.83 | 43.62 | 41.29 | 38.96 | 36.67 | 34.33 | 32 | 30.83 | 29.67 | 30.7 | 30.8 | 30 |
40A | 50.34 | 49.35 | 47.51 | 45.62 | 43.73 | 41.87 | 40 | 39.04 | 38.11 | 38.6 | 36.2 | 35.8 |
50A | 63.79 | 62.48 | 59.99 | 57.48 | 54.98 | 52.5 | 50 | 48.76 | 47.48 | 47.1 | 47.5 | 46 |
63a | 80 | 78.46 | 75.38 | 72.28 | 69.17 | 66.09 | 63 | 61.46 | 59.93 | 55.6 | 53.8 | 52.4 |
Modelo | YCB8S-63 de | YCB8S-63 SD | YCB8S-63 MX | |
Número de contactos | 1NO+1NC | 1NO+1NC | / | |
Voltaje de control (VAC) | 110-415 48 12-24 | |||
Voltaje de control (V DC) | 110-415 48 12-24 | |||
Corriente de contacto de trabajo | AC-12 UE/LE: AC415/3A DC-12 UE/LE: DC125/2A | / | ||
Voltaje de control de derivación | UE/LE: AC: 220-415/ 0.5a AC/DC: 24-48/3 | |||
Ancho (mm) | 9 | 9 | 18 | |
Condiciones ambientales y instalación aplicables | ||||
Temperatura de almacenamiento (c) | -40 ℃ ~+70 ℃ | |||
Humedad de almacenamiento | La humedad relativa no excede el 95%cuando a+25 ℃ | |||
Título de protección | Nivel 2 | |||
Título de protección | IP20 | |||
Entorno de instalación | Lugares sin vibraciones e impacto significativos | |||
Categoría de instalación | Categoría ⅱ, categoría ⅲ | |||
Método de instalación | TH35-7.5/DIN35 Instalación ferroviaria | |||
Capacidad de cableado máxima | 2.5 mm² | |||
Torque terminal | 1n · m |