Product Overview
Product Details
Data Download
Related Products
General
The meter is used in three phase four wire power grid.The meter is designed tomeasure AC active energy.All of its functions comply with the relative technicalrequirement for class 1 three phase watt hour meter in IEC62053-21.It is a long lifemeter with the advantage of high stability,high over load capability,low power loss
Contact Us
The meter is used in three phase four wire power grid. The meter is designed to measure AC active energy. All of its functions comply with the relative technical requirement for class 1 three phase watt hour meter in IEC62053-21. It is a long life meter with the advantage of high stability, high over load capability, low power loss.
1. Mechanical step register 5+1(default) , 6 digit no decimal OR LCD display 6+1, 5+2;
2. Bi-directional total active energy measurement ,reverse active energy measure in the total active energy;
3. Three phase power supply , the meter also measure when loss one phase (any one wire in three phase three wire ) or when loss two phase (any two in three phase four wire;
4. Loss phase LED indicates working of phase;
5. Pulse LED indicates working of meter, Pulse output with optical coupling isolation; 6. Two type of cases (protective-class I and II) are available.
7. Internal connection between the voltage circuit hook and current circuit hook in order to anti-tamer.
Technical Index | Specification |
DTS726 three phase four wire | |
Rate voltage | 3 × 127/220V, 3 × 120/208V, 3 ×220/380V, |
3 ×230/400V, 3 ×240/415V | |
Working voltage range | 0.8~1.2Un |
Rate Current | 5A/CT,1.5(6)A,5(30)A,10(40)A,5(60)A,20(80)A,10(100)A, or other as required |
Frequency | 50Hz or 60Hz |
Connection mode | CT type or Direct type |
Display | mechanical step register or LCD |
Accuracy class | Active class 1.0 |
Power consumption | 0.5W/8VA each phase |
Start current | 0.004Ib |
AC voltage withstand | 4000V/25mA for 60 sec |
Impulse Voltage | 6kV 1.2μs waveform |
IP grade | IP51 or IP54 |
Constant | 400~6400 imp/kWh |
Pulse output | Passive pulse, pulse width is 80+5 ms |
Executive standard | IEC62053-21 ,IEC62052-11 |
Work temperature | -30℃~70℃ |
Outline dimension L×M×H | 215×145×69mm (short terminal cover L1) |
260×145×69mm (long terminal cover L2) | |
Weight | Approx 1.2kg |