Product Overview
Product Details
Data Download
Related Products
Contact Us
CJX2s | 120 | AC/DC 220V | |||
Model | Rated current | Coil control voltage | Auxiliary contact | Frequency | |
AC contactor |
Listed:
120:120A; 160:160A 185:185A; 225:225A Not listed: 265:265A; 265:265A 330:330A; 400:400A 500:500A; 630:630A |
AC/DC110V AC/DC127V AC/DC220V AC/DC380V |
Standard: 2NO2NC |
Standard: 50/60Hz |
Model I |
th A |
AC-3 Use category | AC-4 Use category | Intermittentduty | |||||||||||
IeA | Pe kW | IeA | Pe kW | ||||||||||||
220/230V |
380/400V |
660/690V |
220/230V | 380/400V | 660/690V | 220/230V | 380/400V | 660/690V | 220/230V | 380/400V | 660/690V | AC-3 | AC-4 | ||
CJX2s-120 |
200 |
120 | 120 | 86 | 37 | 55 | 80 | 54 | 54 | 48 | 18.5 | 30 | 50 |
220/380V: 1200time /h660V: 300time/h |
220/380V: 120time/ h660V: 30time/h |
CJX2s-160 | 160 | 160 | 107 | 45 | 75 | 100 | 68 | 68 | 57 | 22 | 37 | 55 | |||
CJX2s-185 | 275 | 185 | 185 | 107 | 55 | 90 | 100 | 81 | 81 | 65 | 30 | 45 | 63 |
220/380V: 600time/ h660V: 300time/h |
|
CJX2s-225 | 225 | 225 | 118 | 63 | 110 | 110 | 96 | 96 | 85 | 30 | 55 | 80 | |||
CJX2s-265 | 315 | 265 | 265 | 170 | 75 | 132 | 160 | 117 | 117 | 105 | 37 | 63 | 100 | ||
CJX2s-330 | 380 | 330 | 330 | 235 | 90 | 160 | 200 | 125 | 125 | 115 | 40 | 75 | 110 | ||
CJX2s-400 | 450 | 400 | 400 | 303 | 132 | 200 | 300 | 150 | 150 | 135 | 45 | 90 | 132 | ||
CJX2s-500 | 630 | 500 | 500 | 353 | 160 | 250 | 335 | 175 | 175 | 150 | 55 | 100 | 150 | ||
CJX2s-630 | 700 | 630 | 630 | 400 | 200 | 355 | 350 | 225 | 225 | 200 | 75 | 110 | 185 |
Model | CJX2s-120 | CJX2s-160 | CJX2s-185 | CJX2s-225 | CJX2s-265 | CJX2s-330 | CJX2s-400 | CJX2s-500 | CJX2s-630 | |
Electrical characteristics | ||||||||||
Number of poles | 3P | |||||||||
Rated insulation voltage(Ui) | 690V | |||||||||
Rated working voltage(Ue) | AC220/230V;380/400V;660/690V | |||||||||
Agreed heating current,
AC-1 Rated working current |
200 | 200 | 275 | 275 | 315 | 380 | 450 | |||
Rated working current(Ie) |
AC-3;220/230V(A) | 120 | 160 | 185 | 225 | 265 | 330 | 400 | ||
AC-3;380/400V(A) | 120 | 160 | 185 | 225 | 265 | 330 | 400 | |||
AC-3;660/690V(A) | 86 | 107 | 107 | 118 | 170 | 225 | 303 | |||
Rated working power(Pe) |
AC-3;220/230V(kW) | 37 | 45 | 55 | 63 | 75 | 90 | 132 | ||
AC-3;380/400V(kW) | 55 | 75 | 90 | 110 | 132 | 160 | 220 | |||
AC-3;660/690V(kW) | 80 | 100 | 110 | 110 | 165 | 220 | 300 | |||
Mechanical life (10,000 times) | 1000 | 1000 | 1000 | 1000 | 600 | 600 | 600 | |||
Electrical life (10,000 times) | AC-3 | 120 | 120 | 110 | 110 | 90 | 90 | 90 | ||
Operating frequency (times/hour) | AC-3 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | ||
Main circuit terminal wiring capa |
city | |||||||||
Flexible wire
without terminal blocks |
1 wire (mm2) | — | — | — | — | — | — | — | ||
2 wires(mm2) | — | — | — | — | — | — | — | |||
Flexible wire
with terminal blocks |
1 wire(mm2) | 10~150 | 10~150 | 10~150 | 10~150 | 10~150 | 10~150 | 10~150 | ||
2 wires(mm2) | 10~75 | 10~75 | 10~75 | 10~75 | 10~75 | 10~75 | 10~75 | |||
Solid wire
without terminal blocks |
1 wire(mm2) | 10~150 | 10~150 | 10~150 | 10~150 | 10~150 | 50~240 | 50~240 | ||
2 wires(mm2) | 10~75 | 10~75 | 10~75 | 10~75 | 10~75 | 50~240 | 50~240 | |||
N·m Main circuit tightening torque | 12 | 12 | 12 | 12 | 14 | 14 | 14 | |||
Coil | ||||||||||
Rated control circuit voltage(Us) | 50/60Hz | AC/DC :110V,127V,220V,380V | ||||||||
Allow control circuit voltage | Running | Attracting voltage 85%~110% and installation tilt angle ±30° | ||||||||
Release | AC/DC :20%~60%Us | |||||||||
Coil power consumption |
Attract(VA) | 500 | 500 | 500 | 600 | 600 | 600 | 800 | ||
Hold(VA) | 78 | 78 | 78 | 78 | 25 | 25 | 25 | |||
Power consumption(W) | 30~78 | 30~78 | 30~78 | 30~78 | 3~10 | 3~10 | 3~10 | |||
AC/DC(W) | 4.5~18.5 | 4.5~18.5 | 4.5~18.5 | 4.5~18.5 | 3~6 | 3~6 | 3~6 | |||
Auxiliary contact | ||||||||||
Contact specifications | 22 | 22 | 22 | 22 | 22 | 22 | 22 | |||
Agreed heating current(Ith) | 10A | |||||||||
Rated working voltage(Ue) | AC | 380V | ||||||||
DC | 220V | |||||||||
Rated control capacity |
AC-15 | 360VA | ||||||||
DC-13 | 33W | |||||||||
FC-4 | CCC | |||||||||
Certification | CE/CB |
Reversible contactor (horizontal installation) | Rated caoacity(kW)AC-3 | Rated current(A)AC-3 | Agreed heating current(A) Rated current AC-1 | ||
380V | 660V | 380V | 660V | ||
CJX2s-120N | 55 | 80 | 120 | 86 | 200 |
CJX2s-160N | 75 | 100 | 160 | 107 | 200 |
CJX2s-185N | 90 | 100 | 185 | 107 | 275 |
CJX2s-225N | 110 | 110 | 225 | 118 | 275 |
CJX2s-265N | 132 | 160 | 265 | 170 | 315 |
CJX2s-330N | 160 | 200 | 330 | 235 | 380 |
CJX2s-400N | 200 | 300 | 400 | 303 | 450 |
CJX2s-500N | 250 | 335 | 500 | 353 | 630 |
CJX2s-630N | 355 | 350 | 630 | 400 | 700 |