CJX2i 12A 18A AC Contactor
CJX2i 12A 18A AC Contactor
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

CJX2i 12A 18A AC Contactor
Picture
Video
  • CJX2i 12A 18A AC Contactor
  • CJX2i 12A 18A AC Contactor
  • CJX2i 12A 18A AC Contactor
  • CJX2i 12A 18A AC Contactor
  • CJX2i 12A 18A AC Contactor
  • CJX2i 12A 18A AC Contactor
CJX2i 12A 18A AC Contactor Featured Image

CJX2i 12A 18A AC Contactor

Product Overview
CJX2i series AC Contactorwith novel appearance and compact structure is suitablefor using starting &controling the AC motor frequently,switching on and off thecircuit at a long distance.It is used in combinationwith thermal relayto compose amagneticmotor starter
Standard IEC 60947-1,IEC 60947-4-1.

Contact Us

Product Details

cjx2i-product-description1-1
cjx2i-product-description2-1
cjx2i-product-description3-1
cjx2i-product-description4-1

Product Overview

CJX2i series AC Contactor with novel appearance and compact structure is suitable for using starting & controlling the AC motor frequently, switching on and off the circuit at a long distance. It is used in combination with thermal relay to compose a magnetic motor starter.
Standard: IEC 60947-1, IEC 60947-4-1.

Specifications

Rated operation current(Ie): 9-95A;
Rated operation voltage(Ue): 220V~690V;
Rated insulation voltage: 690V; Poles: 3P;
Installation: Din rail and screw installation.

Operating and Installation Conditions

Type Operating and Installation Conditions
Installation category III
Pollution level 3
Protection degree CJX2i-09~38: IP20; CJX2i-40~95: IP10
Ambient temperature limit of temperature: -35℃~+70℃,normal temperature: -5℃~+40℃,The average no more than +35℃ within 24 hours.
Altitude ≤2000m
Ambient temperature The maximum temperature is 70 degrees, the relative humidity of the air does not exceed 50%, and the temperature below 50% can allow higher relative humidity. If the temperature is 20℃, the air relative  humidity could up to 90%, Special measures should betaken for occasional condensation due to humidity changes.
Installation position Inclination between installation surface and vertical surface should not exceed ±5°
Shock vibration Products should be installed and used without significant shake, shock and vibration.

Specifications

Appearance        
Type CJX2i-09 CJX2i-12 CJX2i-18 CJX2i-25 CJX2i-32 CJX2i-38 CJX2i-40 CJX2i-50 CJX2i-65 CJX2i-80 CJX2i-95
Main circuit characteristic
Poles 3P
Rated insulation voltage(Ui) V 690
Rated operating voltage(Ue) V 380/400, 660/690
Rated thermal current(Ith) ,AC-1 20 20 32 40 50 50 50 60 80 125 125
Rated
operating
current(Ie)
AC-3,380/400V A 9 12 18 25 32 38 40 50 65 80 95
AC-3,660/690V A 6.6 8.9 12 18 22 22 34 39 42 49 49
AC-4,380/400V A 3.5 5 7.7 8.5 12 14 18.5 24 28 37 44
AC-4,660/690V A 1.5 2 3.8 4.4 7.5 8.9 9 12 14 17.3 21.3
Rated
operating
power(Pe)
AC-3,380/400V kW 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
AC-3,660/690V kW 5.5 7.5 10 15 18.5 18.5 30 33 37 45 45
AC-4,380/400V kW 1.5 2.2 3.3 4 5.4 5.5 7.5 11 15 18.5 22
AC-4,660/690V kW 1.1 1.5 3 3.7 5.5 6 7.5 10 11 15 18.5
Mechanical life 10000
times
1200 1000 900 650
Electrical life AC-3 110 90 65
AC-4 22 22 17 11
Operating
frequency
AC-3 times/
hour
1200 600
AC-4 300 300
Connecting capability of main circuit terminal
Flexible wire 1 wire                   mm² 1…4 1.5…6 2.5…25 4…50
No terminal 2 wire mm² 1…4 1.5…6 2.5…16 4…25
Flexible wire 1 wire mm² 1…4 1…6 2.5…25 4…50
With terminals 2 wire mm² 1…2.5 1…4 2.5…10 4…16
Hard wire 1 wire mm² 1…4 1.5…6 1.5…10 2.5…25 4…50
No terminal 2 wire mm² 1…4 1.5… 2.5…10 4…25
Fastening torque N·m 1.2 1.8 5 9
Coil
Rated control
voltage(Us)
50Hz V 24、36、48、110、127、220/230、240、380/400、415、440
50/60Hz V 24、36、48、110、127、220/230、240、380/400、415、440
Allowed control
circuit voltage(Us)
Operation V Installation inclination angle ±22.5°: 85%~110%Us;   Installation inclination angle±5°: 70%~120%
Release V Installation inclination angle ±22.5°: 20%~75%Us;Installation inclination angle±5°: 20%~65%
Power
consumption
of coil
Actuation VA 60 70 200 200
Keep VA 6-9.5 6-9.5 15-20 15-20
Consumption W 1-3 1-3 6-10 6-10
Auxiliary contacts
Auxiliary contacts specification A 11
Rated thermal current (Ith) A 10
Rated operating
voltage (Ue)
AC V 380
DC V 220
Rated control
capacit
AC-15 VA 360
DC-13 W 33
Certification                                                                                                                            CE, TUV, CB

Overall and Mounting

CJX2i-09~38

cjx2i-product-description7-1

CJX2i-40~95

cjx2i-product-description8-1

Derived Products When The Contactor is Assembled With Following Accessory Module

cjx2i-product-description10-1
 Type Amax Bmax Cmax a b c d e f
CJX2i-09, 12, 18 74.5 45.5 85.5 35 50/60 - - - -
CJX2i-25, 32, 38 83 56.5 97 40 50/70 - - - -
CJX2i-40, 50, 65 127.5 74.5 117 - - 105 40 100/110 59
CJX2i-80, 95 127.5 85.5 125.5 - - 105 40 100/110 67

Specifications

Type Rated
operation
current(Ie)(A)
Rated thermal
current
(Ith)(A)
Rated operational power
in category AC-3 (kW)
380V 660V
CJX2s(CJX2i)-09N 9 20 4 5.5
CJX2s(CJX2i)-12N 12 20 5.5 7.5
CJX2s(CJX2i)-18N 18 32 7.5 10
CJX2s(CJX2i)-25N 25 40 11 15
CJX2s(CJX2i)-32N 32 50 15 18.5
CJX2s(CJX2i)-38N 38 50 15 18.5
CJX2s(CJX2i)-40N 40 50 18.5 30
CJX2s(CJX2i)-50N 50 60 22 33
CJX2s(CJX2i)-65N 65 80 30 37
CJX2s(CJX2i)-80N 80 95 37 45
CJX2s(CJX2i)-95N 95 95 45 55

Outline and Installation Dimensions

CJX2i-09~38N

cjx2i-product-description12-1

CJX2i-40~95N

cjx2i-product-description13-1
  Type Fmax F1max F2max c d e f h
CJX2s(CJX2i)-09N, 12N, 18N 107 120 131 60 25 60 50/60 95
CJX2s(CJX2i)-25N, 32N, 38N 129 142 153 71 31.5 71 50/60 111.5
CJX2s(CJX2i)-40N, 50N, 65N 163 180 193 - 50 90 100/110 130
CJX2s(CJX2i)-80N, 95N 186 202 215 - 60 100 100/110 140
Write your message here and send it to us